REMOTETRAKTM

PRODUCT DATASHEET
RM-16DO2
REMOTETRAKTM
Select RM-16DO2 when you need the lowest cost per channel discrete outputs with load current
requirements below 1 Amp per channel
PRODUCT HIGHLIGHTS
n
High density outputs save space
n
Lowest cost per channel discrete outputs
n
Ideal for driving indicator lights and small relays
n
Surge suppressors safely clamp inductive loads
PRODUCT HIGHLIGHTS
n
Number of channels 16
n
Output range 10-30 VDC
n
n
Max. output current per channel 1 Amp
Max. output current (entire module) 10 Amps
n
Max. OFF state leakage current 0.05 mA
n
Min. load current per channel 0.1 mA
n
Inrush current (100 mS surge) 5 Amps
n
Typical ON resistance 0.3 Ohms
n
Typical ON voltage drop (@ 1 Amp) 0.3 VDC
MECHANICAL DRAWING
ENVIRONMENTAL
n
RS485 isolation 1200 Volts RMS 1 minute
n
Required supply voltage 10-30 VDC (0.5 watt typical)
n
Operating temperature range -30 to 70° C
n
Storage temperature range -40 to 85° C
n
Humidity (non-condensing) 5 to 95%
n
Flammability (module plastic) UL 94V-0 materials
n Electrical safety UL 508, CSA C22.2/14; EN61010-1
(IEC1010), CE
n
EMI emissions FCC part 15, ICES-003, Class A;
EN55022, CE
n EMC immunity EN50082-1 (IEC801-2, 3, 4) CE
n
Vibration IEC68-2-6
n
Hazardous locations UL 1604, CSA C22.2/213M1987, (Class I, Div 2, Groups A, B, C, D), EN50021
(zone 2)
n
Marine/offshore tested and/or verified to meet
various marine and maritime standards
ORDERING INFORMATION
RM-16DO2-H - Module with high density base
RM-16DO2-M - Replacement module only
All specifications are subject to change. Consult factory for latest info.
SIXNET Technology Park • 331 Ushers Road • Ballston Lake, NY 12019 USA
+1 518.877.5173 • Fax +1 518.877.8346 • [email protected]
SOLUTIONS FOR TODAY’S INDUSTRIAL NETWORKING CHALLENGES
2002 DATASHEET
RM-4DI2-4AI2 & RM-4DI2-4DO2 REV: 12/10
WWW.SIXNET.COM