INSTALLATION INSTRUCTIONS TPC Series Industrial and

INSTALLATION INSTRUCTIONS
TPC Series Industrial and Residential Power Supply
Table of Models and Rated Values
Order Code
Rated AC-Input
Voltage Range
Operational Input Rated Output
Voltage Range
Power max.
Rated Output
* Output Voltage
Adjustment
Range
TPC 030-105
TPC 030-112
20 Watt
26,4 Watt
5.0Vdc / 4.0A
12.0Vdc / 2.2A
5.0 – 6.0Vdc
12.0 – 15.0Vdc
TPC 030-124
TPC 030-148
TPC 055-112
TPC 055-124
TPC 055-148
TPC 080-112
TPC 080-124
30 Watt
30 Watt
42 Watt
55 Watt
55 Watt
72 Watt
80 Watt
24.0Vdc / 1.25A
48.0Vdc / 0.6A
12.0Vdc / 3.5A
24.0Vdc / 2.3A
48.0Vdc / 1.15A
12.0Vdc / 6.0A
24.0Vdc / 3.3A
24.0 – 28.8Vdc
48.0 – 56.0Vdc
12.0 – 15.0Vdc
24.0 – 28.8Vdc
48.0 – 56.0Vdc
12.0 – 15.0Vdc
24.0 – 28.8Vdc
TPC 080-148
80 Watt
48.0Vdc / 1.7A
48.0 – 56.0Vdc
TPC 120-112
96 Watt
12.0Vdc / 8.0A
12.0 – 15.0Vdc
TPC 120-124
120 Watt
24.0Vdc / 5.0A
24.0 – 28.8Vdc
TPC 120-148
120 Watt
48.0Vdc / 2.5A
48.0 – 56.0Vdc
Nominal
85Vac – 264Vac
110Vac – 240Vac
47 – 63Hz
50 – 60Hz
130Vdc - 300Vdc
90Vdc - 375Vdc
recommended
Circuit breaker
(Characteristic C)
6A
* Adjustable by potentiometer with a screwdriver.
Connection and Ambient Conditions
Operating temperature range:
Natural Air Convection Cooling
Output Power Derating:
-25°C – +70°C max, above +50°C see derating below
-13°F – +158°F max at nominal load, above +122°F see derating below
above +50°C  2.5%/°C up to +70°C
%
above 122°F  1.4 /°F up to +158°F
<100Vac input voltage output power has to be derated by 2.5%/V for continuous operation
%
<130Vdc input voltage output power has to be derated by 1 /V for continuous operation
Storage temperature range:
-25°C – +85°C max
-13°F – +185°F max
Wire recommendation:
Input wire:
Output wire:
0.5 – 2.5mm2
2
0.5 – 2.5mm
AWG: 20 – 14
AWG: 20 – 14
Use:
Strand / solid copper wire
Wire temperature specification: 70°C minimum (>70°C)
Wire material:
Copper
Connections:
Screw type terminal COMBICON.
Recommended tightening torque 0.5 to 0.7Nm (6.0lb.in.)
Case material:
Grey Plastic
Please follow safety instruction overleaf.
http://www.tracopower.com
Rev: 1.0 / 1116
Safety Instructions
 Before installation read these instructions carefully and

completely. This installation instruction cannot account for
every possible condition of installation, operation or
maintenance. Further information can be obtained from
your local distributor’s office or from the product datasheet,
which can be downloaded, from the Internet at
http://tracopower.com/products/tpc.pdf. You will find
additional information in our Instruction Manual, which can
also be downloaded from the Internet at:
http://www.tracopower.com/products/tpc_manual.pdf.
 The mains supply voltage connection, must be in
accordance to IEC 62103, EN50178 and IEC 60364,
VDE100.
 Before any installation, maintenance or modification work
ensure that the main switch is switched off and prevented
from being switched on again. Non-observance, touching
of any live components or improper handling of this power
supply can result in death, severe personal injury or
substantial property damage. Proper and safe operation is
dependent on proper storage, handling, installation and
operation.
 Compliance with the relevant national regulations (in the
USA, Europe and other countries) must be ensured.
Before operation is started the following conditions must
be ensured:
 Connection to mains supply in compliance with national
regulations (VDE100 and EN50178).
 By use of stranded wires, all strands must be fastened
in the terminal blocks. (Potential danger of contact with
the case)
 On the Output ALL four power terminals must be used.
 Power supply and mains cables must be sufficiently
fused.
 Degree of protection I to IEC536. (Protection Class I).
 All output wires must be rated for the power supply
output current and must be connected with the correct
polarity.
 Sufficient cooling must be ensured.

Warning: Hazardous voltages and components storing a
very substantial amount of energy are present in this
power supply during normal operating conditions.
However, these are inaccessible. Improper handling may
result in an electric shock or serious burns! Do not open
the power supply until at least 5 minutes after it has
been disconnected from the mains on all poles.
 Only trained personnel may open the power supply.
 Do not introduce any objects into the power supply.
The output voltage adjustment potentiometer may only
be actuated using an insulated screwdriver.
 Keep away from fire and water
Installation Instructions:
 This power supply is designed for professional indoor
systems. The unit shall be mounted in an enclosure
without openings in the end application. In operation the
power supply must not be accessible. It may be installed
and put into service by qualified personnel only.

The correct mounting position for optimal cooling
performance must be observed. Do not cover any
ventilation holes. Leave a free space of minimum 50mm
(2in.) above and below the power supply, if possible both
sides should be clear for airflow and observe power
derating.
 The internal fuse is not accessible, as it may not be
replaced by the user. If this internal fuse has blown, the
power supply has an internal defect and, for safety
reasons, must be shipped to the local distributor. In case
this internal fuse has to be replaced in the field, replace
only with same type and rating of fuse for continued
protection against risk of fire.

Recycling: The unit contains elements that are suitable for
recycling, and components that need special disposal. You
are therefore requested to make sure that the power
supply will be recycled at the end of its service life.
Never work on the power supply if power is supplied!
Risk of electric arcs and electrical shock, which can cause
death, severe personal injury or substantial property
damage.
 CAUTION: “FOR USE IN A CONTROLLED ENVIRONMENT”
http://www.tracopower.com
Rev: 1.0 / 1116