INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS
TCL Series
Industrial Power Supply
Rated Input
Operational Input
Output
Voltage Range Voltage Range Power max.
Order Code *
TCL 024-105
20 Watt
TCL 024-112
Universal Input
TCL 024-124 (C)
TCL 060-112 (H) (C) (CH)
TCL 060-124 (H) (C) (CH)
TCL 060-148 (H) (C) (CH)
24 Watt
100 – 240Vac
50 / 60Hz
85 – 264Vac
47 - 63Hz
85 – 250Vdc
48 Watt
60 Watt
85 – 375Vdc
** Output Voltage Recommended
Adjustment Range Circuit Breaker
Output
5.0VDC / 4.0A
5.0 – 5.25VDC
12.0VDC / 2.0A
12.0 – 16.0VDC
24.0VDC / 1.0A
24.0 – 28.0VDC
12.0VDC / 4.0A
12.0 – 15.0VDC
24.0VDC / 2.5A
24.0 – 28.0VDC
48.0VDC / 1.25A
48.0 – 56.0VDC
TCL 120-112 (H) (C) (CH)
96 Watts
12.0VDC / 8.0A
12.0 – 15.0VDC
TCL 120-124 (H) (C) (CH)
120 Watt
24.0VDC / 5.0A
24.0 – 28.0VDC
240 Watt
24.0VDC / 10.0A
24.0 – 28.0VDC
100 - 115Vac /
220 - 240Vac
50 / 60Hz
Auto Selection
TCL 240-124
85 - 132Vac /
187 - 264Vac
47 - 63Hz
(Characteristic C)
5A
(Characteristic C)
10A
* EN 61000-3-2 (PFHC  Power Factor Harmonic Current) Class A will be meet with standard units
** Adjustable by potentiometer with a screwdriver.
Input current:
@ Vin = 115VAC
@ Vin = 230VAC
0.7A max
1.4A max
2.4A max
5.9A typ.
0.4A max
0.8A max
1.2A max
2.3A typ.
TCL 024
TCL 060
TCL 120
TCL 240
Power Consumption
@ Vin = 115VAC @ Vin = 230VAC
TCL 024
TCL 060
TCL 120
TCL 240
28 Watt typ.
71 Watt typ.
137 Watt typ.
274 Watt typ.
27 Watt typ.
68 Watt typ.
133 Watt typ.
272 Watt typ.
Output Signals:
Output Voltage nominal
Output Voltage threshold (DC is OK)
DC OK Signal Voltage
DC OK Signal Current
Load characteristic
12.0 / 15.0 VDC
9.0 … 11.0 V
11.0 V ±1.0V
60 mA
Resistive or Inductive
24.0 VDC
18.0 … 22.0 V
22.0 V ±2.0V
30 mA
Resistive or Inductive
48.0 VDC
36.0 … 44.0 V
44.0 V ±4.0V
15 mA
Resistive or Inductive
General:
Operating temperature range: -10°C – +70°C / 14°F – +158°F max (Natural Air Convection Cooling)
Output Power Derating:
Up to 30°C / 86°F at Input Above 30°C / 86°F at input Above 40°C / 104°F at input Above 50°C / 122°F at input
85..93VAC / 85..130VDC 85..93VAC / 85..130VDC 93..132VAC / 130..187VDC 187..264VAC / 265..375VDC
TCL 024-105
30%
30% + 1.3%/K
1.1%/K
3.8%/K
TCL 024-112
20%
20% + 1.3%/K
1.1%/K
1.7%/K
TCL 024-124 (C)
20%
20% + 1.3%/K
1.1%/K
1.7%/K
TCL 060-112 (H) (C) (CH)
15%
15% + 1.3%/K
1.1%/K
2.7%/K
TCL 060-124 (H) (C) (CH)
15%
15% + 1.3%/K
1.1%/K
2.4%/K
TCL 060-148 (H) (C) (CH)
15%
15% + 1.3%/K
1.1%/K
3.2%/K
TCL 120-112 (H) (C) (CH)
15%
15% + 1.3%/K
1.1%/K
1.7%/K
TCL 120-124 (H) (C) (CH)
15%
15% + 1.3%/K
1.3%/K
3%/K
At Input of 85…100VAC
TCL 240-124
At Input 100...132VAC At Input 187...264VAC
Up to 30°C / 86°F
Above 30°C / 86°F
Above 60°C / 140°F
Above 40°C / 104°F
Above 40°C / 104°F
16%
16% + 0.8%/K
40% + 3%/K
2%/K
1.7%/K
Storage temperature range:
-25°C – +85°C / -13°F – +185°F max
Parallel Operation:
Up to 5 power supplies possible (standard unit) except TCL 240-124  cannot be paralleled
Connections:
Screw type plug-in connector (standard).
Recommended tightening torque 0.5 to 0.7Nm (4.5 to 6.2lb.in.)
Spring-clamp connector (option C)
Wiring:
Screw-type connector  0.75mm2 - 3.16mm2 (AWG 18 - AWG 12)
Spring-clamp connector  0.75mm2 - 3.16mm2 (AWG 18 - AWG 12)
Case material:
Grey plastic  FR2010-110C (PC-ABS V0)
http://www.tracopower.com
Rev: 01/12
Safety Instructions:
Before installation read these instructions carefully and
completely. This installation instruction cannot account for
every possible condition of installation, operation or
maintenance. Further information can be obtained from
your local distributor’s office or from the product datasheet,
which can be downloaded, from the Internet at
http://tracopower.com/products/tcl.pdf.
The mains supply voltage connection, must be in
accordance to IEC 62103, EN 50178 and IEC 60364, VDE
100.
Before any installation, maintenance or modification work
ensure that the main switch is switched off and prevented
from being switched on again. Non-observance, touching
of any live components or improper handling of this power
supply can result in death, severe personal injury or
substantial property damage. Proper and safe operation is
dependent on proper storage, handling, installation and
operation.
Compliance with the relevant national regulations (in the
USA, Europe and other countries) must be ensured.
Before operation is started the following conditions must
be ensured:
Connection to mains supply in compliance with national
regulations (VDE0100 and EN50178).
By use of stranded wires, all strands must be fastened
in the terminal blocks.
Power supply and mains cables must be sufficiently
fused.
Degree of protection I to IEC536. The non-fused
protective earth connection must be connected to the
FG terminal (Protection Class I).
All output wires must be rated for the power supply
output current and must be connected with the correct
polarity.
Sufficient cooling must be ensured.
Installation Instructions:
This power supply is designed for professional indoor
systems. In operation the power supply must not be
accessible. It may be installed and put into service by
qualified personnel only.
Do not operate without PE connection! To comply with
EMC and safety standards (CE mark, approvals) the
power supply must be operated only if PE terminal is
connected to the non-fused earth conductor.
The correct mounting position for optimal cooling
performance must be observed. Do not cover any
ventilation holes. Leave a free space of minimum 50mm
(2in.) above and below the power supply. Observe power
derating.
The internal fuse is not accessible, as it may not be
replaced by the user. If this internal fuse has blown, the
power supply has an internal defect and, for safety
reasons, must be shipped to the local distributor. In case
this internal fuse has to be replaced in the field, replace
only with same type and rating of fuse for continued protection against risk of fire.
Recycling: The unit contains elements that are suitable for
recycling, and components that need special disposal. You
are therefore requested to make sure that the power
supply will be recycled at the end of its service life.
Never work on the power supply if power is supplied!
Risk of electric arcs and electrical shock, which can cause
death, severe personal injury or substantial property
damage.
Warning: Hazardous voltages and components storing a
very substantial amount of energy are present in this
power supply during normal operating conditions. However,
these are inaccessible. Improper handling may result in an
electric shock or serious burns! Do not open the power
supply until at least 5 minutes after it has been disconnected from the mains on all poles.
Only trained personnel may open the power supply.
Do not introduce any objects into the power supply.
The output voltage adjustment potentiometer may only
be actuated using an insulated screwdriver.
Keep away from fire and water