SERIES B

ITALIANA
RELE
SERIES B
Power Industrial Relays
All-or-Nothing relays designed to meet high
power switching applications, having up to
three changeover contacts, rated 4000 or
7500VA AC1. They are ideally suited for
arduous duties where safety and reliability
are at premium, being even capable to
replace small contactors when switching
DIELECTRIC STRENGTH
Coil spring set to contacts :
Between adjacent contacts :
Between open contacts :
Ground / live parts :
type B1-B3
2500 V RMS
2500 V RMS
2500 V RMS
2000 V RMS
resistive loads. The 3mm contact gap
version is very popular, meeting the
strictest safety standards. Meeting IECCEI-VDE standards, this design includes a
dust cover, 0.25 Faston terminals (6.3x0.8
mm) and flame resistant terminal block
material.
type B2-B4
2500 V RMS
2500 V RMS
2000 V RMS
2000 V RMS
OPERATING TIMES (At Rated Voltage)
Operate (excluding bounces) : max 15
milliseconds
Release (excluding bounces) : max 12
milliseconds
max 10
Bounces :
milliseconds
SPECIFICATION
Min. insulation resistance
Insulation group (VDE 110)
Enclosure classification
Type of duty
Mechanical life expectancy
Max ops./hour @ no load
Max ops./hour @ rated load
Temperature range
Type B4-3 with AC coils
Storage temperature
Vibration
Impulse voltage class
Operating class (CEI 41-1)
2x104 ΜΩ @ 500 VDC (all circuits)
1° Gr. C 250 VAC
IP 40 (IEC 144)
continuous
106 operations
10000 (AC / DC)
1200 (AC / DC)
-10 to +55° C
-10 to +45° C
-25 to +80° C
4 g (N / O contacts)
1 g (N / C contacts)
0
C
AVAILABLE TYPES
B1-1 1 pole normally open - 16A-250V AC
B3-1 1 pole normally open - 30A-250V AC
Distance between open contacts: 3 mm
Weight: 135 grams
B1-2 2 pole normally open - 16A-250V AC
B3-2 2 pole normally open - 30A-250V AC
Distance between open contacts: 3 mm
Weight: 145 grams
B1-3 3 pole normally open - 16A-250V AC
B3-3 3 pole normally open - 30A-250V AC
Distance between open contacts: 3 mm
Weight: 155 grams
B2-1 1 pole changeover - 16A-250V AC
B4-1 1 pole changeover - 30A-250V AC
Distance between open contacts: 1 mm
Weight: 135 grams
B2-2 2 pole changeover - 16A-250V AC
B4-2 2 pole changeover - 30A-250V AC
Distance between open contacts: 1 mm
Weight: 145 grams
B2-3 3 pole changeover - 16A-250V AC
B4-3 3 pole changeover - 30A-250V AC
Distance between open contacts: 1 mm
Weight: 155 grams
APPROVALS (16A Types only)
All dimensions in mm
Willow Technologies Ltd. Shawlands Court, Newchapel Road, Lingfield, Surrey, RH7 6BL, United Kingdom
Tel (+44) 01342 835234 - Fax (+44) 01342 834306 - E-mail: [email protected] - Web: http://www.willow.co.uk
COIL CHARACTERISTICS
DC
Rated
Voltage V
Rated Current
mA
Resistance R
Ω
Rated Current
mA
AC
Resistance R
Ω
6
270
22
650
2
9
12
135
88
320
8
37
24
68
350
160
32
150
48
34
1400
80
130
600
110
15
7500
35
670
3100
230
-
-
17
2900
13500
Resistance values at 20°C ambient temp.
Impedance Z
Ω
Tolerance on R and Z: + 10%
CTEISTICSCOCHARACTERISTICS
Power supply voltages:
6-12-24-48-110-230-400 VAC
6-12-24-48-60-110 VDC
Rated power:
2W (DC) ; 3.9 VA (AC)
Operating range:
- 20% to + 10% of nominal
Minimum hold voltage:
80% of nominal (AC)
50% of nominal (DC)
Must release voltage:
15% of nominal (AC)
5% of nominal (DC)
Thermic insulation class of winding
(IEC 317): F (155°C)
CONTACT CHARACTERISTICS
Power rating (AC1) : 4000VA (Type B1-B2)
7500VA (Type B3-B4)
Rated current :
16A (Type B1-B2)
30A (Type B3-B4)
Rated voltage:
250V AC
Max. instantaneous current(1) :
30A (Type B1-B2)
35A (Type B3-B4)
(1)
Make & maintaining only - max. 0.5 sec.
Max switched voltage : 400 VAC
Max. single-phase motor load :
½ HP (B1-B2) – 1 HP (B3-B4)
Switching power (DC1) : see diagram
Initial contact resistance (2): max. 30 mΩ
standard 5 mΩ
Contact material: Ag90% - Ni10%
(2)
Category of application (EN 60255) : 3
ORDERING INFORMATION
B2 - 3 - 230 AC - FS
1 2
3
4
5
1 – Relay Series: B
2 – Contact type:
1 = Normally Open 16A
2 = Changeover 16A
3 = Normally Open 30A
4 = Changeover 30A
3 – Number of poles: 1 - 2 - 3
4 – Coil supply voltage: AC or DC
5 – Fixing options:
FS = Fixing tabs on cover (standard)
FA = screw mounting on base (M4x8)
AD = DIN-rail flange on cover
Willow Technologies Ltd. Shawlands Court, Newchapel Road, Lingfield, Surrey, RH7 6BL, United Kingdom
Tel. (+44) 01342 835234 - Fax. (+44) 01342 834306 - E-mail: [email protected] - Web: http://www.willow.co.uk