RG25 Plug-in power relays 121 • • • • 35 mm DIN rail mounting, EN 50022 High switching capacity High inrush current Test button Contacts Contact number & arrangement Contact material Max. switching voltage Min. switching voltage Rated load Min. switching current Max. inrush current Rated current Max. breaking capacity Min. breaking capacity Resistance Max. operating frequency • at rated load AC/DC AC1 AC3 AC1 AC3 AC1 AC3 • no load 2NO AgCdO 400 V / 400 V 10 V 25 A / 380 V AC 15 A / 380 V AC 10 mA 40 A 25 A 9 500 VA 5 700 VA 1W ≤ 100 mΩ 600 cycles/hour 600 cycles/hour 3 600 cycles/hour Coil Rated voltage 50 Hz Must release voltage Operating range of supply voltage Rated power consumption AC DC AC DC 12-24-110-230-380 V 12-24-48-110-220 V ≥ 0,1 Un see Table 1, 2 3,0 VA 1,5 W Insulation Insulation category Insulation rated voltage Dielectric strength • coil - contact • contact - contact • pole - pole Contact - coil distance • clearance • creepage C400 400 V AC 5 000 V AC 1 500 V AC 5 000 V AC ≥ 6 mm ≥ 8 mm General data Operating time (typical value) Release time (typical value) Electrical life • resistive AC1 • cosφ Mechanical life (cycles) Dimensions (L x W x H) Weight Ambient temperature • storing • operating Cover protection category Shock resistance Vibration resistance Standard contact material marked with bolt type. www.relpol.com.pl 20 ms 20 ms ≥ 105 25 A, 380 V AC see Fig. 2 ≥ 106 26 x 49 x 72 mm 130 g -25...+85 oC -25...+85 oC IP 20 10 g 5 g 10...150 Hz RG25 Plug-in power relays 122 www.relpol.com.pl RG25 Plug-in power relays 123 Mounting Relays RG25 are designed for 35 mm DIN rail mounting, EN 50022. Operational position - contacts downwards. see Table 1, 2 page 122 www.relpol.com.pl