NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay FEATURES/BENEFITS • Latest generation of High Voltage IGBT Technology • Innovative isolated driver ensures fast power transistor turn on and off and thus low power transient • Ultra low output leakage current • Low control current consumption • Triggered control input to avoid linear control risks • Low conducted and radiated disturbances Part Number Description MECHANICAL SPECIFICATION SI60DC100 100A, 600 Vdc Solid-State Relay 1.10 (28) SI120DC50 50A, 1200 Vdc Solid-State Relay 0.89 (22.8) Ø0.5 SI170DC25 25A, 1700 Vdc Solid-State Relay 1.10 (28) 0.77 (19.6) Ø4.7 M5 1 Line Voltage Switch Type2 Output Current – Amps NOTES 1) Line Voltage (peak): 60 = 600 Vdc; 120 = 1200 Vdc; 170 = 1700 Vdc; 2) Switch Type: DC = DC 1.01 (25.8) ELECTRICAL SPECIFICATIONS (+25°C ambient temperature unless otherwise specified) INPUT (CONTROL) SPECIFICATIONS Min Max Units Control Range 4.5 32 Vdc Input Current Range 25 42 mAdc Typical Turn-On Voltage 3.5 Must Turn-Off Voltage 2– 4– 3+ 0.20 (5.1) Series 1+ 1.87 (47.6) 100 DC 1.7 (43.2) 60 0.29 (7.5) SI 2.29 (58.2) Part Number Explanation 1.0 (25.4) 1.75 (44.5) M3 Tolerances: Ø0.3 Dimensions in inches (mm) Weight: 3.52 oz. (100g) Figure 1 Vdc 1 Vdc Reverse Voltage 32 Vdc Reverse Leakage Current 1 mA BLOCK DIAGRAM CONTROL CHARACTERISTIC Control Current (mAdc) 45 40 35 @25°C 30 Figure 3 25 20 15 10 5 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Control Voltage (V) Figure 2 © 2012 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com SI Page 1 SI\112012\Q4 NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay ELECTRICAL SPECIFICATIONS (+25°C ambient temperature unless otherwise specified) ELECTRICAL SPECIFICATIONS (Continued) (+25°C ambient temperature unless otherwise specified) OUTPUT (LOAD) SPECIFICATIONS OUTPUT (LOAD) SPECIFICATIONS Max Units Built-In Heat Sink Thermal Resistance (Vertically Mounted) 10 °C/W Vdc Heat Sink Thermal Time Constant 10 min Vdc Control Inputs/Power Outputs Insulation Voltage 4 kV 10 μs 600 μs SI60DC100 10 μs 50 μs Min Max Units SI60DC100 0 500 Vdc SI120DC50 0 1000 SI170DC25 0 1400 Operating Range Peak Voltage Min SI60DC100 600 Vpeak Turn-On Time SI120DC50 1200 Vpeak Turn-On Delay SI170DC25 1700 Vpeak Turn-Off Time Reverse Voltage (Internal Diode) SI60DC100 1.4 V SI120DC50 SI120DC50 1.4 V SI170DC25 50 μs SI170DC25 3.3 V Turn-Off Delay 100 μs On-Off Frequency Maximum Nominal Current (Resistive) SI60DC100 100 A SI60DC100 700 Hz SI120DC50 50 A SI120DC50 200 Hz SI170DC25 25 A SI170DC25 200 Hz Maximum Peak Current Rating (Non-Repetitive) (ON-State) SI60DC100 550 A SI120DC50 320 A SI170DC25 40 A TIME DIAGRAMS TURN-ON Leakage Current SI60DC100 1 mA SI120DC50 1 mA SI170DC25 1.5 mA Vc (control) t Max On-State Voltage Drop Vt (switch) t @25 °C @125 °C tdon SI60DC100 1.35 1.45 V SI120DC50 1.5 1.7 V SI170DC25 3.3 3.3 V SI60DC100 300 pF SI120DC50 300 pF SI170DC25 90 pF SI60DC100 .385 °C/W SI120DC50 .365 °C/W SI170DC25 1.25 °C/W Output Capacitance (Typical) TURN-OFF Junction-Case Thermal Resistance SI Page 2 ton Vc (control) t Vt (switch) t SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE tdoff toff Figure 4 © 2012 TELEDYNE RELAYS SI\112012\Q4 NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay GENERAL SPECIFICATIONS (+25°C ambient temperature unless otherwise specified) DC Control Power Supply ENVIRONMENTAL SPECIFICATIONS Min Max Units +90 °C –40 +100 °C Input-Output Isolation 4000 Vrms 1 GΩ <8 pF Insulation Capacitance Transient 175 °C (Red paths as short as possible.) D2 2– °C 3+ Ic 125 C1 D1 or Vt Vc Junction Temperature Steady State Ve Ie 1+ –40 Storage Temperature + DC Mains – +– 4– Operating Temperature Insulation Resistance HIGH SIDE WIRING DIAGRAM (Load Connected to “—”) On-Off control or or CONNECTIONS Screwdriver Power Control Phillips NR2 Phillips NR1 1.8 N.m 0.8 N.m M5 M3 Tightening Torque Insulated crimp terminals (Round Tabs, Eyelet Type) Load Figure 5 LOW SIDE WIRING DIAGRAM (Load Connected to “+”) + DC Mains DC Control Power Supply – +– MISCELLANEOUS Ie Ve C1 Mounting 2 screws (M4x12mm) Noise Level No audible noise D1 or D2 3+ UL94V0 Ic Vt Vc On-Off control or GENERAL Standards (Red paths as short as possible.) 4– Housing 2– Green LED (ON) 1+ Display or IEC60947-1 Protection Level IP00 Protection Against Direct Touch None CE Marking Load Yes Figure 6 E.M.C. EMISSION Radiated & Conducted Disturbances NFEN55011 Figure 7 PROTECTIVE COVER AVAILABLE Contact Factory © 2012 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com SI Page 3 SI\112012\Q4 NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay OUTPUT RELAY CHARACTERISTIC CURVES FOR SI60DC100 140 200 Reverse Current (A) 100 80 Tj = 25°C 60 Tj = 125°C 40 Tj = 175°C 20 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 Tj=125°C 50 0 2 0 0.5 1 1.5 Voltage Drop (V) Reverse Voltage Drop (V) Figure 8a Figure 8b 0.18 0.16 0.14 0.12 0.1 D=50% 0.08 D=20% D=10% 0.06 D=5% 0.04 D=2% 0.02 D=1% Single pulse 0 0.0001 100 0.001 0.01 0.1 1 700 600 Non-repetitive D=1% (Tc=100°C, Tjm ax=175°C) 500 400 300 200 100 Repetitive D=50%(Tc=100°C, Tjmax=125°C) 0 0.0001 0.001 0.01 0.1 Pulse Duration (S) Pulse Duration (S) Figure 8c Figure 8d 1 160 110 2.2C/W 100 Load Current (A) 2 2.1C/W 1.2C/W 1.1C/W 0.9C/W 0.75C/W 0.55C/W 0.3C/W 0.2C/W 0.1C/W 145 90 131 80 116 70 102 60 87 50 72.5 40 58 30 43.5 20 29 Power Dissipation (W) Power Element Thermal Impedance (C/W) 0 150 ON-State Peak Overload Current (Apk) Load Current (A) 120 14.5 10 8C/W 0 0 4C/W 10 0 20 30 40 50 60 70 80 90 100 110 Ambient Temperature (°C) Figure 8e SI Page 4 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2012 TELEDYNE RELAYS SI\112012\Q4 NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay OUTPUT RELAY CHARACTERISTIC CURVES FOR SI120DC50 100 280 240 Reverse Current (A) 60 40 Tj = 25°c Tj = 175°c 20 200 160 120 Vf @175° 40 0 0 0.5 1 1.5 2 2.5 0.5 1 1.5 2 2.5 Voltage Drop (V) Reverse Voltage Drop (V) Figure 9a Figure 9b 1 0.1 Single pulse D=1% D=2% 0.01 D=5% D=10% D=20% D=50% 0.001 0.00001 0 3 0.0001 0.001 0.01 0.1 1 ON-State Peak Overload Current (Apk) 0 Power Element Thermal Impedance (C/W) Vf @25° 80 3.5 1000 100 10 Repetitive D=50% (Tc = 100°C, Tjmax = 125°C) No repetitive D=1% (Tc = 100°C, Tjmax = 175°C) 1 0.0001 0.001 0.01 0.1 Pulse Duration (S) Pulse Duration (S) Figure 9c Figure 9d 1 160 110 2.2C/W 100 Load Current (A) 3 2.1C/W 1.2C/W 1.1C/W 0.9C/W 0.75C/W 0.55C/W 0.3C/W 0.2C/W 0.1C/W 145 90 131 80 116 70 102 60 87 50 72.5 40 58 30 43.5 20 29 Power Dissipation (W) Load Current (A) 80 14.5 10 8C/W 0 0 4C/W 10 0 20 30 40 50 60 70 80 90 100 110 Ambient Temperature (°C) Figure 9e © 2012 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com SI Page 5 SI\112012\Q4 NEW Series SI Output to 100A, 1700 Vdc DC Solid-State Relay OUTPUT RELAY CHARACTERISTIC CURVES FOR SI170DC25 100 280 240 Reverse Current (A) 60 40 Tj = 25°c Tj = 175°c 20 200 160 120 Vf @175° 40 0 0 0.5 1 1.5 2 2.5 0.5 1 1.5 2 2.5 Voltage Drop (V) Reverse Voltage Drop (V) Figure 10a Figure 10b 1 0.1 Single pulse D=1% D=2% 0.01 D=5% D=10% D=20% D=50% 0.001 0.00001 0 3 0.0001 0.001 0.01 0.1 1 ON-State Peak Overload Current (Apk) 0 Power Element Thermal Impedance (C/W) Vf @25° 80 3.5 1000 100 10 Repetitive D=50% (Tc = 100°C, Tjmax = 125°C) No repetitive D=1% (Tc = 100°C, Tjmax = 175°C) 1 0.0001 0.001 0.01 0.1 Pulse Duration (S) Pulse Duration (S) Figure 10c Figure 10d 30 1 87 1.3C/W Load Current (A) 3 1.2C/W 1.1C/W 0.9C/W 0.75C/W 0.55C/W 0.3C/W 0.2C/W 0.1C/W 25 72.5 20 58 15 43.5 10 29 Power Dissipation (W) Load Current (A) 80 14.5 5 8C/W 4C/W 2.4C/W 2.2C/W 2.1C/W 1.95C/W 1.5C/W 0 0 0 10 20 30 40 50 60 70 80 90 100 110 Ambient Temperature (°C) NOTES 1. For additional/custom options, contact factory. SI Page 6 Figure 10e SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2012 TELEDYNE RELAYS SI\112012\Q4