FCTE 2013 - Digi-Key

FCTE
Pump Dry Running Sensor
cynergycomponents
The FCTE is a heat sensor, which is attached to the outlet pipe from a pump. This
device works by reacting to the temperature at the outlet of any centrifugal type pump,
which will rapidly rise past 45 ° if the inlet water level falls below the centre line of the
inlet. The unit will cut off the electrical supply to the pump, so protecting it from
damage. Manual resetting of this unit allows the pump to restart.
SPECIFICATION
Set Temperature
45°C 113°F
Switching voltage max.
250Vac
Switching current max. resistive
Pipe diameter range
16A
20-200mm
IP Rating
21
• Prevents dry-running
of pump
TE thermostat
• Prevents overheating
of seals
TE thermostat also
protects the seal
• High power switching
capacity
T E
Heat accumulation
zone due to vapour
formation
Level of
water when
TE cuts in
Dia.
m
in 20
max
Spring clip fixing sensor to pipe
400
Cynergy3 Components Ltd
7 Cobham Road
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
[email protected]
ISO 9001C E R T I F IED
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
FCTE 2013
FCTE
Pump Dry Running Sensor
cynergycomponents
INSTALLATION
Top View
72
46
reset button
heat sensor
T E
64
46
brass strip
00
ax 4
m
0
in 2
er. m
t
e
d ia m
indicator light
pipe
cable entry
spring clip fixing sensor to pipe
reset button
46
indicator light
cable entry
brass heat
conductor strip
heat sensor
50
20
Side View
A-A
three-phase motor pump protection
examples of positioning
pump
16 A 250V
thermic relay
TE thermostat
250V
single - phase motor pump protection
ISO 9001C E R T I F IED
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.