ADF240C - ARCH Electronics Corp.

VER : A_3
update : 2015.09.03
AC-DC Din Rail Power Supply
ADF240C
240 Watts
KEY FEATURES
 Protections: Short Circuit / Overload / Over Voltage / Over Temperature
 With P.F.C. Function, PF>0.95
 Free Air Convection
 High Efficiency up to 91%
 Can be Connected in Parallel to Offer the Current Share Function
 Built-in DC OK Relay Contact
 3-Year Product Warranty
ELECTRICAL SPECIFICATIONS
All specifications valid at normal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Model No.
ADF240C-24S
Max Output Wattage (Free air Convection)
Voltage
Input
Output
Function
Isolation
Environment
Physical
Safety & EMC
90-264 VAC or 120-370 VDC
Frequency (Hz)
47-63 Hz
Current (Full load)
<3.0 A max. (115 VAC) / <1.5 A max. (230 VAC)
Inrush Current (<2ms)
<30 A max. (115 VAC) / <60 A max. (230 VAC)
Leakage Current
< 1.5 mA max.
Power Factor
PF>0.98 (115 VAC) / PF>0.94 (230 VAC) at Full Load
Voltage (V.DC.)
24V
Trim
±2% (Adjustable VR on the front panel)
Voltage Accuracy
±2%
Current (Free air Convection) (A) (max.)
10
Line Regulation
±0.5%
Load Regulation
±2%
Minimum Load
2%
Maximum Capacitive Load
6000 uF
Ripple & Noise (max.)
150mVp-p
Efficiency (typ.)
Protection
ADF240C-48S
240W
(W)
(at 230 VAC)
(Note 4)
48V
5
1200 uF
90%
91%
Hold-up Time
20 ms (115 VAC) / 20 ms (230 VAC) at Full Load
Over Power Protection
Auto recovery, Hiccup mode
Over Voltage Protection
27~31V (Latch Off)
Over Temperature Protection
Auto recovery
Short Circuit Protection
Auto recovery, Hiccup mode
52~56V (Latch Off)
DC OK Relay Contact Ratings (max.)
30Vdc/1A, 30Vac/0.5A Resistive Load
Input-Output (V.AC)
3000VAC or 4242VDC
Input-FG
(V.AC)
Output-FG (V.AC)
Operating Temperature
1500V
500V
-40°C…+70°C (with derating)
Storage Temperature
-40°C…+85°C
Temperature Coefficient
±0.05%/°C
Humidity
95% RH
MTB
>169K h @ 25°C (MIL-HDBK-217F)
Vibration
10~500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes.
Dimension (L x W x H)
2.56 x 4.96 x 4.25 Inches
Weigh
850 g
( 65.0 x 126.0 x 108.0 mm ) Tolerance 0.5 mm
Cooling Method
Free convection
Agency Approvals
CE(EN 60950-1)
Isolation Rsistance
EMI
(Conducted & Radiated Emission)
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25°C / 70% RH
EMS (Noise Immunity)
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
EN 55022 class B
EN61000-4-2,3,4,5,6,8,11, EN 55024, EN 61000-6-2, EN 61204-3,
Heavy Industry Level, Criteria A
-1-
VER : A_3
update : 2015.09.03
AC-DC Din Rail Power Supply
ADF240C
240 Watts
NOTE
1. Ripple & Noise are measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor.
2. The power supplies can connected in parallel to offer the current share function.
3. Derating may be needed under low input voltage. Please check the derating curve for more details.
4. After 30 minutes of burn-in
5. Parallel Operation with Remote Sensing:
(1). Parallel operation is available by connecting the units shown as below (+S,-S and CS are connected mutually in parallel)
(2). Difference in Vout among parallelled units should be less than +/-1%
(3). The total output current must not exceed the value determined by the following equation (Output current at parallel
operation)=(The rated current per unit) x (Number of unit) x 0.9.
(4). In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
(5). When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
(6). When in parallel operation, the minimum output load should be greater than 3% of total output load.(Min. load > 3% rated
current per unit x number of unit)
6. Please refer to our PDF file "AC-DC Application" on our website: www.archcorp.com.tw
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-2-
VER : A_3
update : 2015.09.03
AC-DC Din Rail Power Supply
ADF240C
240 Watts
DERATING
BLOCK DIAGRAM
MECHANICAL DIMENSION
( Top View )
P1
DC OK RELAY CONTACT
Contact Close
PSU Turns Off / DC Fail
Contact Open
PSU Turns On / DC Ok
Contact Ratings (max.)
PIN#
Single
1
+DC OK
2
CS
3
+S
4
-S
5
+DC OUT
6
+DC OUT
7
-DC OK & GND
8
GND
30V / 1A Resistive Load
P2
PIN#
Single
9
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
10
AC IN (N)
11
AC IN (L)
-3-
VER : A_3
update : 2015.09.03
AC-DC Din Rail Power Supply
ADF240C
240 Watts
EFFICIENCY VERSUS LOAD
ADF240C-24S
VIN
Input Voltage (V)
Efficiency (%)
VS
Efficiency
VS
Efficiency
90
115
180
230
264
Load (%)
10
20
30
40
50
86.21
87.63
89.91
90.57
90.80
115V (%)
78.36
84.91
86.93
87.58
88.20
230V (%)
77.68
83.98
87.27
88.85
86.60
Load (%)
60
70
80
90
100
115V (%)
88.34
88.30
88.38
88.19
87.73
230V (%)
90.03
90.35
90.50
90.59
90.52
92.00%
100.00%
91.00%
90.00%
90.00%
80.00%
70.00%
89.00%
60.00%
88.00%
EF F %
EFF%
LOAD
87.00%
50.00%
40.00%
86.00%
30.00%
85.00%
20.00%
10.00%
84.00%
0.00%
83.00%
90V
115V
180V
230V
0%
264V
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
LOAD
VIN
ADF240C-48S
VIN
Input Voltage (V)
Efficiency (%)
VS
Efficiency
LOAD
VS
Efficiency
90
115
180
230
264
Load (%)
10
20
30
40
50
87.49
89.73
91.24
91.84
92.15
115V (%)
80.72
84.05
86.67
88.01
88.55
230V (%)
77.16
82.91
86.97
88.96
90.05
Load (%)
60
70
80
90
100
115V (%)
89.15
89.46
89.84
89.68
89.87
230V (%)
90.51
91.05
91.21
91.55
91.84
93.00%
100.00%
92.00%
90.00%
80.00%
91.00%
70.00%
90.00%
EFF%
EFF%
60.00%
89.00%
88.00%
50.00%
40.00%
30.00%
87.00%
20.00%
86.00%
10.00%
0.00%
85.00%
90V
115V
180V
230V
VIN
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
264V
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
LOAD
-4-