4 8 0 W S i n g l e O u t put Industrial DIN RAIL with PFC Function DRP480 series Built-in Passive PFC Function Compliance to EN61000-3-2 Protections:Short Circuit/Over Load/Over Voltage/ Over Temperature High Efficiency 89% and Low Dissipation Cooling by Free Air Convection Built-in Constant Current Limiting Circuit Can be Installed on DIN Rail TS-35/7.5 or 15 UL 508 (Industrial Control Equipment) Approved EN61000-6-2 (EN50082-2) Industrial Immunity Level AC Input Range Selectable by Switch (DRP480S) Model Number Input Volts Output Volts Output Amps Over Voltage Protection DRP480-24 DRP480-48 180-264VAC 180-264VAC 24 VDC 48VDC 0-20 Amps 0-10 Amps 30~36 Volts(DC) 54~60 Volts(DC) DRP480S-24 DRP480S-48 90-132/180-264VAC 24 VDC 90-132/180-264VAC 48VDC 0-20 Amps 0-10 Amps 30~36 Volts(DC) 59~66 Volts(DC) SINGLE OUTPUT All specifications are typical at nominal input, full load, and 25°C unless otherwise noted WWW.ASTRODYNE.COM Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications. ASTRODYNE USA: 1-800-823-8082 ASTRODYNE PACIFIC: 886-2-26983458 4 8 0 W S i n g l e O u t put Industrial DIN RAIL with PFC Function INPUT SPECIFICATIONS Input Voltage Range DRP480 180~ 264VAC DRP480S 90-132/180-264VAC by Switch Frequency Range 47-63 Hz Inrush Current, typ: (cold start) DRP480 40 Amps / 230VAC DRP480S 27A / 115VAC; 45A / 230VAC Input Current DRP480 4.0 Amps. @ 230VAC DRP480S 8A / 115VAC; 3.2A / 230VAC Leakage current < 3.5mAmps / 240VAC Power Factor @ FL PF ≥ 0.7 230VAC Only EMI Harmonic Current Efficiency Isolation EMS DRP480 series DRP480: EN55022B (CISPR22B) DRP480S:EN55011(CISPR11); EN55022 (CISPR22) EN61204-3 Class B Compliance to EN61000-3-2,-3 89% 4242VAC Input - Output 2121VAC Input - Ground 707VAC Output - Ground Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61204-3 (DRP480S only) EN61000-6-2 (EN50082-2) light Industry Level, Criteria A ENVIRONMENTAL SPECIFICATIONS OUTPUT SPECIFICATIONS Voltage and Current Line Regulation Load Regulation Voltage Tolerance (Note 2) Ripple/Noise (Note 1) Hold Up Time @ FL Setup, Rise Time @ FL Over Voltage Protection Over Current Protection Over Temperature Protection DC Voltage Adjust See Selection Chart ±0.5% ±1.0% ±1.0% 120mVpk-pk max. DRP480: 16mS; DRP480S: 23mS 1200ms, 40mS See Selection Chart Shut down o/p voltage,re-power 105 ~ 150% rated output power Constant current limiting, auto recover 100°C ±5°C (TSW: Detected on heatsink of power switch) Shut down o/p voltage, re-power after cool down 24~28Volts: 24Vout 48~53Volts: 48Vout (48-55V DRP480S) Oper. Temperature Storage Temperature Relative Humidity Temperature Coefficient MTBF Vibration MTBF (MIL-HDBK-217F) -20°C to +70°C (See Dreate Curve) DRP480: -20°C to +85°C, 10~95% RH DRP480S: 20°C to +85°C, 10~95% RH 20~90% RH non cond ±0.03% / °C (0-50°C) 180.9KHrs min,MIL-HDBK-217F(25°C) 10~500Hz, 2G10min./1cycle, period for 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6 DRP480: 180.9K Hrs. DRP480S: 187.9K Hrs. PHYSICAL SPECIFICATIONS Size Millimeters Inches Weight 227 x 125.2 x 100 8.94” x 4.93 ” x 3.94 ” DRP480: 5.29 lb (2400g) DRP480S: 7.73 lb (2600g) GENERAL SPECIFICATIONS Notes Safety Insulation Resistance 1. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 2. Tolerance : includes set up tolerance, line regulation and load regulation. UL508, UL60950-1, TUV EN60950-1 ≥ 100MΩ / 500Volts / 25°C / 70% RH WWW.ASTRODYNE.COM ASTRODYNE USA: 1-800-823-8082 ASTRODYNE PACIFIC: 886-2-26983458 4 8 0 W S i n g l e O u t put Industrial DIN RAIL with PFC Function DRP480 series DRP480S Only WWW.ASTRODYNE.COM ASTRODYNE USA: 1-800-823-8082 ASTRODYNE PACIFIC: 886-2-26983458