CLAMP ON SENSOR 9650

CLAMP ON SENSOR 9650 < Clamp Sensors < Products
Clamp Sensors (Current sensor -for the 3636-20 CLAMP
LOGGER, and 8205-10/8206-10 MICRO HiCORDER-)
CLAMP ON SENSOR 9650
CAT III 300 V
CLAMP LOGGER 3636-20
OVERVIEW
Clamp-on Sensors for the CLAMP LOGGER 3636-20, and MICRO HiCORDER 8205-10/8206-10
For input up to AC 500A, select our Model 9651, and for smaller currents of up to AC 100A, select Model 9650.
Both sensors are designed with a safety barrier to protect the user from being in direct contact with live
conductors and completely meet all CE marking requirements.
Basic specifications
Rated input current
100 A AC
Rated output current
100 mA AC
Accuracy (at 50/60 Hz)
Amplitude: ±1.5 % rdg. ±0.03 % f.s. , Full scale (f.s.) is the rated input current value
Frequency characteristics
40 Hz to 1 kHz (±8 % or less)
Max. allowable input
continuous 130 A rms (45 to 66 Hz)
Max. circuit voltage
300 V AC rms (insulated wire)
Core jaw dia.
Ø15 mm(0.59 in)
Dimensions, mass
46 mm(1.81 in)W × 135 mm(5.31 in)H × 21 mm(0.83 in)D, 200 g (7.1 oz), cord length: 3
m(9.84 ft)
OVERVIEW
Generated by www.PDFonFly.com
CLAMP ON SENSOR 9651 < Clamp Sensors < Products
Clamp Sensors (Current sensor -for the 3636-20 CLAMP
LOGGER, and 8205-10/8206-10 MICRO HiCORDER-)
CLAMP ON SENSOR 9651
CAT III 600 V
CLAMP LOGGER 3636-20
OVERVIEW
Clamp-on Sensors for the CLAMP LOGGER 3636-20, and MICRO HiCORDER 8205-10/8206-10
For input up to AC 500A, select our Model 9651, and for smaller currents of up to AC 100A, select Model 9650.
Both sensors are designed with a safety barrier to protect the user from being in direct contact with live
conductors and completely meet all CE marking requirements.
Basic specifications
Rated input current
500 A AC
Rated output current
500 mA AC
Accuracy (at 50/60 Hz)
Amplitude: ±1.5 % rdg. ±0.03 % f.s. , Full scale (f.s.) is the rated input current value
Frequency characteristics
40 Hz to 1 kHz (±3 % or less)
Max. allowable input
continuous 600 A rms (45 to 66 Hz)
Max. circuit voltage
600 V AC rms (insulated wire)
Core jaw dia.
Ø46 mm(1.81 in)
Dimensions, mass
77 mm(3.03 in)W × 151 mm(5.94 in)H × 42 mm(1.65 in)D, 340 g (12.0 oz), cord length: 3
m(9.84 ft)
OVERVIEW
Generated by www.PDFonFly.com
CLAMP ON SENSOR 9668 < Clamp Sensors < Products
Clamp Sensors (Current sensor -for the 3636-20 CLAMP
LOGGER, and 8205-10/8206-10 MICRO HiCORDER-)
CLAMP ON SENSOR 9668
CAT III 600 V
MICRO HiCORDER
8205-10, 8206-10
OVERVIEW
Clamp-on Sensors for MICRO HiCORDER 8205-10/8206-10
For input up to AC 1000A, select our Model 9668, This sensor is designed with a safety barrier to protect the
user from being in direct contact with live conductors and completely meet all CE marking requirements.
Basic specifications
Rated input current
1000 A AC
Rated output current
1000 mA AC
Accuracy (at 45 to 66 Hz)
Amplitude: ± 3.0 % rdg. ± 0.03 % f.s. , Full scale (f.s.) is the rated input current value
Frequency characteristics
40 Hz to 1 kHz (±3 % or less)
Max. allowable input
continuous 1000 A rms (45 to 66 Hz)
Max. circuit voltage
600 V AC rms (insulated wire)
Core jaw dia.
Ø55 mm(2.17 in), 80 mm (3.15 in) × 20 mm (0.79 in) busbar
Dimensions, mass
99.5 mm(3.92 in)W × 188 mm(7.40 in)H × 42 mm(1.65 in)D, 550 g (19.4 oz), cord length:
3 m(9.84 ft)
OVERVIEW