NetSure 502 Integrated System Application Guide

SAG582136700
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Issue AV, February 21, 2014
Home
SYSTEM OVERVIEW
Description:
The NetSure™ 502NGFB DC Power System is a complete integrated power system
containing rectifiers, intelligent control, metering, monitoring, and distribution. This power
system consists of the following mounted in a 2RU high by 19” or 23” wide shelf.
•
Rectifier Modules
The 19” wide shelf accommodates two (2) Rectifier Modules. The 23” wide shelf
accommodates three (3) Rectifier Modules. The Rectifier Module R48-2000 comes
in 2000W power rating. The modules provide load power, battery float current, and
battery recharge current during normal operating conditions. The Rectifier Modules
are designed to provide constant power. They are designed with the latest patented
switch-mode technology using DSP (Digital Signal Processing) functionality for
efficient operation. This means that, within the normal operating ambient
temperature range and input voltage range, the maximum available output power is a
constant 2000W. Within these ranges, the Rectifier Modules operate in one of three
modes, depending upon load demands. Transition between modes is completely
automatic. If ambient temperature rises above or input voltage falls below acceptable
values, Rectifier Modules continue to operate but at derated output power levels.
1) Constant Voltage Mode: For any initial output voltage setting from 48 to 58
volts, output voltage remains constant regardless of load. This is the normal
operating condition, in which loads are being supplied and batteries are float
charged. Rectifier Modules operate in the Constant Voltage Mode unless load
increases to the point where the product of load current and output voltage is
approximately 2000W.
2) Constant Power Mode: As load increases above approximately 2000W (nonadjustable), output current continues to increase, but output voltage decreases
as required to maintain constant output power. Rectifier Modules operate in the
Constant Power Mode unless load continues to increase to the point where the
current limit setting is reached.
3) Constant Current Mode: If load increases above the current limit setting, output
voltage decreases linearly to maintain output current at current limit.
•
ACU+ (Advanced Control Unit Plus)
The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms as well as PCU control, data
acquisition, system alarm management, and advanced battery and energy
management. The ACU+ contains an LCD display and keypad for local access. It
provides connections for binary inputs, programmable relay outputs, and a charge
control function. The controller also supports rectifier temperature compensation if
the system is equipped with a temperature probe (or multiple temperature probes
connected via a Temperature
Concentrator (SM TEMP), and
ambient temperature monitoring
if equipped with a second
temperature probe. The ACU+
provides Ethernet connection
and supports software upgrade
via its USB port. It also comes
with a comprehensive web page
and SNMP capability for remote
system management.
Page 1 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
•
•
Home
SCU+ (Standard Control Unit Plus)
The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms. The SCU+ contains an LCD display
and keypad for local access. It provides connections for binary inputs, programmable
relay outputs, and a charge control function. The controller also supports rectifier
temperature compensation if the system is equipped with a temperature probe (or
multiple temperature probes connected via a Temperature Concentrator (SM TEMP),
and ambient temperature monitoring if equipped with a second temperature probe.
The SCU+ also provides Ethernet connection and SNMP capability.
Distribution Unit
Various Distribution Unit options are available, as described in this document. The
Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) contactor.
Family:
Spec. No.:
Model:
Input Voltage
Output Voltage:
Output Capacity:
Rectifier Module:
System:
Agency Approval:
Framework Type:
Mounting Width:
Mounting Depth:
Mounting Height:
Access:
Control:
Color:
Environment:
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
NetSure™
582136700
502NGFB
Nominal 120/208/240 volts AC, single phase, and 3-wire, 50/60 Hz, with
an operating range of 100 to 250 volts. Acceptable input frequency range
is 45 to 65 Hz.
-48 Volts DC
2000W (41.6A) @ 208/240VAC Input and +45°C (R48-2000) or +55°C
(R48-2000e)
1262W (26.3A) @ 120VAC Input and +45°C (R48-2000) or +55°C
(R48-2000e)
List 2 19” Version: 4000W (83A), maximum
List 6 23” Version: 6000W (125A), maximum
Note: 19” version is “Specification Compliant” up to 66 amperes
(2000W) at +65°C (+149°F).
23” version is “Specification Compliant” up to 100 amperes
(6000W) at +65°C (+149°F).
UL 60950 Recognized, CAN/CSA 22.2
Relay Rack Mounted
19” or 23”, nominal
12”
3.5” (2RU)
Front for Installation, Operation, and Maintenance
Microprocessor
Front Panels are Gray, Shelf is Galvaneal
Lists 2 and 6: -40°C (-40°F) to +65°C (+149°F),
with deratings (see SPECIFICATIONS section)
Page 2 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
582136700
Home
Rectifier Module (2000W)
or
Rectifier Module (2000W,
High Efficiency)
List 2 (19” Shelf)
SCU+
P/N 1M521BNA
or
ACU+
P/N 1M820BNA
List 6 (23” Shelf)
(shown)
List BA:
Side Molex AC Input Connectors
(P/O List 2 and 6) and AC Input
Cables/Line Cords
List LA:
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker
Load Positions
(2) Bullet-Nose Circuit Breaker
Battery Positions
Low Voltage Load Disconnect (LVLD)
List NA
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker
Load Positions
(2) Bullet-Nose Circuit Breaker
Battery Positions
NO Low Voltage Disconnect
List BC:
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points
List LC:
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points
DISTRIBUTION UNIT (continuation)
List NC:
(5) GMT Fuse Load Positions
(4) Bullet-Nose Circuit Breaker Load
Positions
NO Low Voltage Disconnect
(3) Battery Landing Points
List BF:
(13) GMT Fuse Load Positions
Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points
List LF:
(13) GMT Fuse Load Positions
Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points
List NF:
DISTRIBUTION UNIT
(5) GMT Fuse Load Positions
(2) Bullet-Nose Circuit Breaker
Load Positions
(2) Bullet-Nose Circuit Breaker
Battery Positions
Low Voltage Battery Disconnect
(LVBD)
(13) GMT Fuse Load Positions
NO Low Voltage Disconnect
(3) Battery Landing Points
Page 3 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
58213670002 with P/N 556851 (Vertical Flush Mount Kit)
Rectifier Module (2000W)
or
Rectifier Module (2000W,
High Efficiency)
Rear AC input Connectors (P/O
556851) and
AC Input Cables/Line Cords
SCU+
P/N 1M521BNA
or
ACU+
P/N 1M820BNA
Distribution Unit
Page 4 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Other List Options
List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions
(For use with Lists BC, LC, NC, BA, LA, and NA.)
List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions
(For use with Lists BF, LF, and NF.)
List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions
(For use with Lists BF, LF, and NF.)
List 65: Shelf Side Battery Cables
(For use with Lists BC, LC, NC, BF, LF, and NF)
List 66: Battery Side Battery Cables
(For use with Lists BC, LC, NC, BF, LF, and NF)
List 67: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 68: Shelf Side Battery Cables
(for use w/ Lists BC, LC, NC, BF, LF, and NF)
List 89: Relay Rack Earthquake Anchor Kit
List 90: Temperature Probe (12 ft. total)
List 91: Temperature Probe (33 ft. total)
List 93: Battery Tray (23”)
List 94: Batter Tray (19”)
List KG: GMT Fuse Distribution Panel
Accessory Options
Relay Racks
Rack Adapter Kit
Ring and Distribution Module
Battery Cabinets
SM TEMP Temperature Concentrator
Distribution Devices
AC Input Cables and Line Cords
Digital Input and Relay Output Cables
Optional Bullet-nose-type 6-position
GMT fuse board
Replacement Components
Wiring Notes
Wiring Illustrations
SEE ALSO
System Overview
Table of Contents
List Descriptions
Accessory Descriptions
Specifications
Physical Size Information
Related Documentation
Page 5 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
TABLE OF CONTENTS
System
Overview
Picture
List
Descriptions
Accessory
Descriptions
Specifications
Physical Size
Information
Related
Documentation
SYSTEM OVERVIEW................................................................................................................................................. 1
582136700 ............................................................................................................................................................. 3
58213670002 with P/N 556851 (Vertical Flush Mount Kit) ............................................................................... 4
TABLE OF CONTENTS ............................................................................................................................................. 6
LIST DESCRIPTIONS ................................................................................................................................................ 9
List 2: 19” Shelf ................................................................................................................................................ 9
List 6: 23” Shelf .............................................................................................................................................. 10
R48-2000 Rectifier Module ............................................................................................................................ 11
R48-2000e Rectifier Module, High Efficiency ................................................................................................ 11
ACU+ (Advanced Control Unit Plus), P/N 1M820BNA .................................................................................. 11
SCU+ (Standard Control Unit Plus), P/N 1M521BNA .................................................................................... 12
List 60: Load Lead Assemblies for GMT Fuses (for 10A positions) ............................................................... 12
List 61: Load Lead Assemblies for GMT Fuses (for 10A positions) ............................................................... 12
List 62: Load Lead Assemblies for GMT Fuses (for 15A positions) ............................................................... 13
List 65: Shelf Side Battery Cables, P/N 540814 ............................................................................................ 13
List 66: Battery Side Battery Cables, P/N 540954 ......................................................................................... 13
List 67: Battery Cable, P/N 545709 ................................................................................................................ 13
List 68: Shelf Side Battery Cables, P/N 557304 ............................................................................................ 14
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ......................................................................... 14
List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe
side half, 9 ft. long) ......................................................................................................................................... 14
List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe
side half, 30 ft. long) ....................................................................................................................................... 15
List 93: Battery Tray for 23” Relay Rack ........................................................................................................ 15
List 94: Battery Tray for 19” Relay Rack ........................................................................................................ 19
List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
Disconnect (LVBD) ......................................................................................................................................... 23
List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load
Disconnect (LVLD) ......................................................................................................................................... 24
List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Disconnect ...................................................................................................................................................... 25
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) ..................................................... 26
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................... 27
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and w/out Low Voltage Disconnect ............................................................................ 28
List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery
Disconnect (LVBD) ......................................................................................................................................... 29
List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load
Disconnect (LVLD) ......................................................................................................................................... 30
List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage
Disconnect ...................................................................................................................................................... 31
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ............................................... 32
Page 6 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
ACCESSORY DESCRIPTIONS ............................................................................................................................... 33
Relay Racks ....................................................................................................................................................... 33
Mounting and Adapter Kits .............................................................................................................................. 34
Optional Wall Mount Bracket Kit for Lists 2 and 6, P/N 553203 .................................................................... 34
Optional 19” to 23” Rack Adapter Kit, P/N 545728 ........................................................................................ 34
Optional Vertical Flush Mount Kit for List 2, P/N 556851 ............................................................................... 34
Distribution Devices .......................................................................................................................................... 35
GMT Load Distribution Fuses ........................................................................................................................ 35
Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load Distribution) ............................................ 36
Bulk Output Bus bar, P/N 535015 .................................................................................................................. 37
AC Input Cables and Line Cords ..................................................................................................................... 37
AC Input Cable Assembly, P/N 535232 ......................................................................................................... 37
AC Input Cable Assembly, P/N 553202 ......................................................................................................... 37
AC Input Line Cord, P/N 540946, 208/240VAC ............................................................................................. 38
AC Input Line Cord, P/N 545616, 208/240VAC ............................................................................................. 38
AC Input Line Cord, P/N 545252, 120VAC .................................................................................................... 38
AC Input Line Cord, P/N 545478, 120VAC .................................................................................................... 39
AC Input Line Cord, P/N 545479, 120VAC .................................................................................................... 39
AC Input Line Cord, P/N 545480, 208/240VAC ............................................................................................. 39
AC Input Line Cord, P/N 545481, 120VAC .................................................................................................... 40
AC Input Line Cord, P/N 545482, 208/240VAC ............................................................................................. 40
AC Input Line Cord, P/N 545553, 208/240VAC ............................................................................................. 40
AC Input Line Cord, P/N 547525, 120VAC .................................................................................................... 41
AC Input Line Cord, P/N 548457, 120VAC .................................................................................................... 41
AP6C57EA/EB Ring and Distribution Module ................................................................................................ 41
NetSure™ 211BC Battery Cabinet (Spec. No. 541434) ................................................................................... 43
NetSure™ 211BC Battery Cabinet (Spec. No. 545534) ................................................................................... 44
NetSure™ 211BC Battery Cabinet (Spec. No. 545506) ................................................................................... 45
NetSure™ 211BC Battery Cabinet (Spec. No. 554631) ................................................................................... 46
External Battery Disconnect Unit .................................................................................................................... 47
SM TEMP Temperature Concentrator (P/N 547490) ....................................................................................... 48
SM Module RS-485 Interface Cable P/N 547674 ............................................................................................. 48
Alarm Cables...................................................................................................................................................... 48
Optional Bullet-Nose-type 6-Position GMT Fuse Board (Part No. 545332) ................................................. 49
Replacement Components ............................................................................................................................... 50
Wiring Notes ...................................................................................................................................................... 51
AC Input Branch Circuit Protection and Wiring .............................................................................................. 51
External Alarm and Monitoring Wiring ........................................................................................................... 51
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF) ...................................................................... 51
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)................................................. 52
Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ................................... 52
Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) .......................................... 52
Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 53
CO Ground Wiring .......................................................................................................................................... 53
Input Battery Wiring (to battery bus bars) (Lists BF, LF, NF, BC, LC, and NC) ............................................. 55
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA and NA) ................................... 56
Wiring Illustrations ............................................................................................................................................ 57
AC Input Wiring (List 6 shown) ....................................................................................................................... 57
AC Input Wiring for List 2 with Rear AC Input Connectors ............................................................................ 58
External Alarm and Monitoring Wiring (List 6 shown) .................................................................................... 59
External Interface Connections (continuation) ............................................................................................... 60
External Interface Connections (continuation) ............................................................................................... 61
External Interface Connections (continuation) ............................................................................................... 62
External Interface Connections (continuation) ............................................................................................... 63
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF in List 6, as shown) ....................................... 64
Page 7 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in List 6, as
shown) ............................................................................................................................................................ 65
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................ 66
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground
Wiring (Lists BC, LC and NC, List 6 shown) .................................................................................................. 67
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground
Wiring (Lists BA, LA and NA, List 6 shown) ................................................................................................... 68
Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 69
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC in List 6, as shown) ............................................... 70
SPECIFICATIONS.................................................................................................................................................... 71
1. System ........................................................................................................................................................... 71
1.1 Environmental Ratings ............................................................................................................................. 71
1.2 Compliance Information ........................................................................................................................... 71
1.3 Standard Features .................................................................................................................................... 72
PHYSICAL SIZE INFORMATION ............................................................................................................................ 74
Overall Dimensions – List 2 ............................................................................................................................. 74
Overall Dimensions – List 6 ............................................................................................................................. 75
Additional Dimensions – Lists 2 and 6 with Wall Mounting Kit (P/N 553203) ............................................. 76
Additional Dimensions - List 2 and Vertical Flush Mounting Kit (P/N 556851) ........................................... 77
Overall Dimensions – List KG .......................................................................................................................... 78
Overall Dimensions – 19” Battery Tray ........................................................................................................... 79
Overall Dimensions – 23” Battery Tray ........................................................................................................... 80
BATTERY MANUFACTURER INFORMATION ...................................................................................................... 81
RELATED DOCUMENTATION ................................................................................................................................ 81
REVISION RECORD ................................................................................................................................................ 82
Page 8 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
LIST DESCRIPTIONS
List 2: 19” Shelf
Features
♦
Consists of a 2RU high by 19” wide shelf.
♦
Includes side AC input housing with Molex connectors.
♦
Houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
♦ Includes Relay Outputs Alarm Cable P/N 541308 (shelf side) factory connected in the shelf.
Restrictions
Each shelf holds up to two (2) Rectifier Modules.
Ordering Notes
1) Order List 2 as required.
Also order the following as required.
2) Order one (1) SCU+ (P/N 1M521BNA) or (1) ACU+ Controller (P/N 1M820BNA) per shelf. Also specify
appropriate configuration file for your site.
3) Order up to two (2) Rectifier Modules per shelf: P/N 1R482000e or 1R482000.
4) Order AC Input Cables or Line Cords as required. Note that each 19” Shelf requires two (2) AC Input
Cable Assemblies/Line Cords (each feeds one [1] rectifier).
5) Order one (1) Distribution Unit (List BF, LF, NF, BA, LA, NA, BC, LC, or NC) per shelf.
6) Order one (1) List 60 for each List BA, LA, NA, BC, LC, or NC ordered.
Each List 60 provides five (5) GMT fuse load lead assemblies (10A maximum).
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) GMT fuse load lead assemblies (10A maximum).
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) GMT fuse load lead assemblies (15A maximum).
7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.
8) Order Shelf Side or Battery Side Battery Cables (List 65 or List 68, and/or List 66) as required.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) (List 89) as required.
11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery
Charge Temperature Compensation feature, the other to monitor ambient temperature.
12) Order Battery Trays (List 94) as required.
13) Order Optional Vertical Flush Mount Kit, P/N 556851 as required.
14) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
15) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
16) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
17) Order Alarm Cables per ACCESSORY DESCRIPTIONS section.
18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 9 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
List 6: 23” Shelf
Features
♦
Consists of a 2RU high by 23” wide shelf.
♦
Includes side AC input housing with Molex connectors.
♦
Houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
♦ Includes Relay Outputs Alarm Cable P/N 541308 (shelf side) factory connected in the shelf.
Restrictions
Each shelf holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order List 6 as required.
Also order the following as required.
2) Order one (1) SCU+ (P/N 1M521BNA) or (1) ACU+ Controller (P/N 1M820BNA) per shelf. Also specify
appropriate configuration file for your site.
3) Order up to three (3) Rectifier Modules per shelf: P/N 1R482000e or 1R482000.
4) Order AC Input Cables or Line Cords as required. Note that each 23” Shelf requires two (2) AC Input
Cable Assemblies/Line Cords (one feeds one [1] rectifier, the other feeds two [2] rectifiers).
5) Order a Distribution Unit (List BF, LF, NF, BA, LA, NA, BC, LC, or NC) per shelf.
6) Order one (1) List 60 for each List BA, LA, NA, BC, LC, or NC ordered.
Each List 60 provides five (5) GMT fuse load lead assemblies (10A maximum).
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) GMT fuse load lead assemblies (10A maximum).
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) GMT fuse load lead assemblies (15A maximum).
7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.
8) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65 or List 68, and/or List 66) as
required.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) (List 89) as required.
11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery
Charge Temperature Compensation feature, the other to monitor ambient temperature.
12) Order Battery Trays (List 93) as required.
13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
16) Order Alarm Cables per ACCESSORY DESCRIPTIONS section.
17) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 10 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
R48-2000 Rectifier Module
Features
Provides one (1) Model R48-2000, Spec. No. 1R482000,
2000 watt / 48 volt Rectifier Module.
Restrictions
Each List 2 Shelf (19”) holds up to two (2) Rectifier Modules.
Each List 6 Shelf (23”) holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order by P/N 1R482000 as required.
♦
R48-2000e Rectifier Module, High Efficiency
Features
Provides one (1) Model R48-2000e, Spec. No. 1R482000e,
2000 watt / 48 volt High Efficiency Rectifier Module.
Restrictions
Each List 2 Shelf (19”) holds up to two (2) Rectifier Modules.
Each List 6 Shelf (23”) holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order by P/N 1R482000e as required.
♦
ACU+ (Advanced Control Unit Plus), P/N 1M820BNA
Features
♦
Provides the ACU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller.
Ordering Notes
1) Order one (1) ACU+ (P/N 1M820BMA) or one (1) SCU+ Controller (P/N
1M521BNA) or for each shelf.
For the ACU+ controller, specify also one of the following configurations.
a) List 5 and 6 with Low Voltage Disconnect: 550166.
b) List 5 and 6 without Low Voltage Disconnect: 550167.
Note: For custom ACU+ configurations, contact Emerson.
Page 11 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
SCU+ (Standard Control Unit Plus), P/N 1M521BNA
Features
♦
Home
Provides the SCU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
Each shelf must contain one (1) SCU+ Controller.
Ordering Notes
1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N
1M820BMA) for each shelf.
For the SCU+ controller, specify also one of the following configurations.
a) List 2 and 6 with Low Voltage Disconnect: 545298.
b) List 2 and 6 without Low Voltage Disconnect: 545299.
Note: For custom SCU+ configurations, contact Emerson.
List 60: Load Lead Assemblies for GMT Fuses (for 10A positions)
Features
Provides 12’ long, 16 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution Unit,
and are left un-terminated at the remaining end for connection into customer
loads.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA only.
Ordering Notes
1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, and NA Distribution Unit. Each List 60 provides
five (5) GMT fuse load lead assemblies, P/N 535206.
♦
List 61: Load Lead Assemblies for GMT Fuses (for 10A positions)
Features
Provides 12’ long, 16 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads.
Restrictions
For use with Lists BF, LF, and NF only.
Ordering Notes
1) Order one (1) List 61 for each List BF, LF, and NF Distribution Unit. Each List
61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.
♦
Page 12 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List 62: Load Lead Assemblies for GMT Fuses (for 15A positions)
Features
Home
Provides 12’ long, 14 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 15A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads.
Restrictions
For use with Lists BF, LF, and NF only.
Ordering Notes
1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit. Each List
62 provides five (5) GMT fuse load lead assemblies, P/N 540988.
♦
List 65: Shelf Side Battery Cables, P/N 540814
Features
Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red
SB120 Anderson connector on the shelf side. Remaining end terminated in lugs
for connection to shelf.
Restrictions
For use with Lists BC, LC, NC, BF, LF, and NF only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery
strings.
♦
List 66: Battery Side Battery Cables, P/N 540954
Features
Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position
Red SB120 Anderson connector on the battery side. Remaining end unterminated for connection to batteries.
Restrictions
For use with Lists BC, LC, NC, BF, LF, and NF only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery
strings.
♦
List 67: Battery Cable, P/N 545709
Features
Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Red SB50
Anderson connector on the battery side. Remaining end terminated in lugs for
connection to shelf.
Restrictions
For use with Lists BC, LC, NC, BF, LF, and NF only.
For use with P/N 541434, P/N 545534, P/N 545506, or P/N 554631 battery cabinets only.
Ordering Notes
1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
2) Order one (1) for each battery cabinet feed required.
♦
Page 13 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
List 68: Shelf Side Battery Cables, P/N 557304
Features
Provides two (2) 3’ long, 6 AWG, battery cables terminated in a 2-position Red SB50 Anderson connector
on the shelf side. Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with Lists BC, LC, NC, BF, LF, and NF only.
For use with P/N 541434, P/N 545534, P/N 545506, or P/N 554631 battery cabinets
only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery strings.
♦
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
Features
♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor.
Ordering Notes
1) Order as required.
List 90: Optional Temperature Probe,
P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long)
Features
♦
Up to two (2) temperature probes can
be connected to the Customer Interface
(IB2) Board. Either or both probes can
be programmed to monitor ambient
temperature or battery temperature.
♦
A temperature probe set as a battery
probe can also be designated to be used for the battery charge temperature compensation feature. If the
system is equipped with the ACU+ Controller, the battery charge temperature compensation feature can
be programmed to use one probe or the average or highest value of all probes programmed to monitor
battery temperature. The battery charge temperature compensation feature allows the controller to
automatically increase or decrease the output voltage of the system to maintain battery float current as
battery temperature decreases or increases, respectively. Battery life can be extended when an optimum
charge voltage to the battery with respect to temperature is maintained.
♦
If the system is equipped with the ACU+ Controller, a temperature probe set as a battery probe can also
be used for controlling against battery thermal runaway (BTRM feature).
The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.
When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf. P/N 04118247 (9 feet long) is
shipped loose. Total length: 12 ft.
Restrictions
A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a
battery cell to sense battery temperature. A temperature probe used for battery charge temperature
compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side
of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a
convenient location, away from direct sources of heat or cold.
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247.
2) For a Temperature Probe with a longer cable see List 91.
♦
Page 14 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
3) Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple
probes are required, order (1) SM-TEMP Temperature Concentrator.
Home
List 91: Optional Temperature Probe,
P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long)
Features
♦
See above for description of Temperature Probes.
The Temperature Probe assembly consists of two pieces that plug together to make a complete probe.
When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is
shipped loose. Total length: 33 ft.
Restrictions
See above for restrictions.
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740.
2) For a Temperature Probe with a shorter cable see List 90.
3) Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple probes are
required, order (1) SM-TEMP Temperature Concentrator.
♦
List 93: Battery Tray for 23” Relay Rack
Features
♦
Provides one battery tray that mounts four (4) 12V front terminal
Valve Regulated Lead Acid (VRLA) batteries. Batteries are
configured as one (1) 48V string.
♦
Accepts various VRLA batteries. See Ordering Notes below.
♦
See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE
INFORMATION for battery tray dimensions and typical
arrangement. Note that two battery trays are available to
accommodate the various size batteries listed in the Ordering
Notes tables.
♦
Trays can be ordered with or without battery disconnect circuit
breakers. When circuit breakers are ordered, one is provided in
the -48V lead of each battery string (1 circuit breaker per tray).
Battery cables are available terminated at the power system end
in an Anderson connector. Battery lugs are available for the
remaining end.
Restrictions
For 23” relay racks only.
Maximum number of List 93’s per rack is three (3).
A single List 93 must mount at bottom of rack. Multiple List 93’s must
mount starting at bottom of rack and working upward.
Ordering Notes
1) Order multiples of List 93 for more than one (1) battery tray. See
Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s) as
required.
3) Order batteries separately. Tables A, B, and C list batteries
recommended for use with List 93.
♦
Page 15 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required
for battery clearance. See Tables A, B, and C.
5) Battery lugs are provided, as specified from Table D.
6) Specify with or without battery disconnect circuit breakers.
Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as
specified for the first tray ordered.
7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from Table E.
8) If ordering List 93 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or
remote mounting. Circuit breaker mounting kits shown in the Table E will be installed. Kit numbers are
provided for reference only
9) If ordering List 93 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the
alarm terminal of up to three (3) battery disconnect circuit breakers.
Page 16 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Battery Tray P/N 528496
Emerson
Network
Power
P/N
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
Manufacturer*
Model
GNB Marathon
M12V125FT
--
125
4.90 X 22.00 X 11.15
7U
105
GNB Marathon
M12V155FT
112795
155
4.90 X 22.00 X 11.15
7U
119
Northstar
NSB110FT
--
110
4.92 X 22.05 X 8.94
7U
91
Northstar
NSB170FT
--
167
4.92 X 22.05 X 12.60
8U
131
Deka Unigy I
12AVR-150ET
122018
150
4.90 X 22.00 X 11.75
8U
115
C&D
C&D
FA 12-150F
TEL12-210F
FA12150
554579
150
202
4.92 X 21.97 X 12.70
4.90 X 22.00 X 12.80
8U
8U
131
132
Douglas
DGS12-150F
125453
150
4.90 X 22.00 X 12.70
8U
137
Douglas
DSN12-170F
--
170.8
4.92 X 22.05 X 12.60
8U
130
* See Battery Manufacturer Information located at the end of this document.
Table A
Battery Tray P/N 540842
Manufacturer*
Model
Emerson
Network
Power
P/N
Northstar
NSB40FT**
--
38.1
3.80 X 9.80 X 8.20
6U
34
Northstar
NSB60FT**
--
57.9
4.20 X 11.30 X 10.40
7U
49
Douglas
DGS12-25F
--
25
3.94 X 10.80 X 7.60
6U
27
Douglas
DGS12-50F
--
50
3.94 X 10.80 X 11.60
8U
48
Enersys
12TD50F
--
48
4.2 X 10.9 X 8.7
6U
38
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.
Table B
Battery Tray P/N 557573
Manufacturer*
Model
Emerson
Network
Power
P/N
Enersys
12TD150F
--
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
143
4.3 X 21.7 X 11.3
8U
105
* See Battery Manufacturer Information located at the end of this document.
Table C
Page 17 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Battery
Specified
Battery Lug Kit Part Number
(Kit provides two lugs for one tray.)
GNB Marathon M12V125FT
GNB Marathon M12V155FT
Northstar NSB110FT
528234
Northstar NSB170FT
Deka Unigy I 12AVR-150ET
C&D FA 12-150F
C&D TEL12-210F
528236
Douglas DGS12-150F
Douglas DSN12-170F
Northstar NSB40FT
Northstar NSB60FT
528234
Douglas DGS12-25F
Douglas DGS12-50F
Enersys 12TD50F
Enersys 12TD150F
Table D
Ampere
Rating
Part No., Circuit Breaker,
1
Electrical/Mechanical Trip
(Black Handle)
1
256690300
3
256690700
5
256691100
10
256691500
15
256691900
20
256692300
25
256692700
30
256693100
35
256693500
40
256693900
50
256694300
60
256694700
70
256695100
75
256695500
100
256695900
Part No., Left-Side
Breaker Mtg. Kit
(For Reference Only)
Part No., Right-Side
Breaker Mtg. Kit
(For Reference Only)
528501
528500
1 Provides an alarm during an electrical or manual trip condition.
Table E
Page 18 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
List 94: Battery Tray for 19” Relay Rack
Features
♦
Provides one battery tray that mounts four (4) 12V front terminal
Valve Regulated Lead Acid (VRLA) batteries. Batteries are
configured as one (1) 48V string.
♦
Accepts various VRLA batteries. See Ordering Notes below.
♦
See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE
INFORMATION for battery tray dimensions and typical
arrangement. Note that three battery trays are available to
accommodate the various size batteries listed in the Ordering
Notes tables.
♦
Trays can be ordered with or without battery disconnect circuit
breakers. When circuit breakers are ordered, one is provided in
the -48V lead of each battery string (1 circuit breaker per tray).
Battery cables are available terminated at the power system end in
an Anderson connector. Battery lugs are available for the remaining
end.
Restrictions
For 19” relay racks only.
Maximum number of List 94’s per rack is three (3).
A single List 94 must mount at bottom of rack. Multiple List 94’s must
mount starting at bottom of rack and working upward.
Ordering Notes
1) Order multiples of List 94 for more than one (1) battery tray. See
Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.
3) Order batteries separately. Tables F, G, H and I list batteries
recommended for use with List 94.
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between
trays and above top tray as required for battery clearance. See
Tables F, G, H and I.
5) Battery lugs are provided, as specified from Table J.
♦
6) Specify with or without battery disconnect circuit breakers.
Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as
specified for the first tray ordered.
7) If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from Table K.
8) If ordering List 94 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or
remote mounting. Circuit breaker mounting kits shown in the Table K will be installed. Kit numbers are
provided for reference only
9) If ordering List 94 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the
alarm terminal of up to three (3) battery disconnect circuit breakers.
Page 19 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Battery Tray P/N 558047
Manufacturer*
Model
Emerson
Network
Power
P/N
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
Northstar
NSB90FT
--
90
4.25 X 15.59 X 10.04
7U
71
Northstar
NSB100FT
--
100
4.25 X 15.59 X 11.03
7U
78
GNB Marathon
M12V90FT
--
90
4.13 X 15.55 X 10.63
7U
70
Enersys
12TD100F4
--
96
4.3 X 15.5 X 11.3
8U
71
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
* See Battery Manufacturer Information located at the end of this document.
Table F
Battery Tray P/N 541034
Manufacturer*
Model
Emerson
Network
Power
P/N
GNB Marathon
M12V105FT
--
105
4.33 X 20.12 X 9.37
7U
79
Enersys
12TD100F6
--
97
4.3 X 20.0 X 9.4
7U
73
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
* See Battery Manufacturer Information located at the end of this document.
Table G
Battery Tray P/N 540841
Manufacturer*
Model
Emerson
Network
Power
P/N
Northstar
NSB40FT**
--
38.1
3.80 X 9.80 X 8.20
6U
34
Northstar
NSB60FT**
--
57.9
4.20 X 11.30 X 10.40
7U
49
Douglas
DGS12-25F
--
25
3.94 X 10.80 X 7.60
6U
27
Douglas
DGS12-50F
--
50
3.94 X 10.80 X 11.60
8U
48
Enersys
12TD50F
--
48
4.2 X 10.9 X 8.7
6U
38
Rated 8-Hr.
Capacity
(Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.
Table H
Page 20 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Battery Tray P/N 548213
Rated
8-Hr.
Capacit
y (Ah)
Dimension
WxLxH
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
Manufacturer*
Model
Emerson
Network
Power P/N
Enersys
12V125F
122009
125
4.10 X 22.10 X 12.40
8U
124
Enersys
12TD150F
--
143
4.3 X 21.7 X 11.3
8U
105
* See Battery Manufacturer Information located at the end of this document.
Table I
Battery
Specified
Battery Lug Kit Part Number
(Kit provides two lugs for one tray.)
Northstar NSB90FT
Northstar NSB100FT
GNB Marathon M12V90FT
GNB Marathon M12V105FT
Northstar NSB40FT
Northstar NSB60FT
528234
Douglas DGS12-25F
Douglas DGS12-50F
Enersys 12V125F
Enersys 12TD50F
Enersys 12TD100F4
Enersys 12TD100F6
Enersys 12TD150F
Table J
Page 21 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Ampere
Rating
Part No., Circuit Breaker,
1
Electrical/Mechanical Trip
(Black Handle)
1
256690300
3
256690700
5
256691100
10
256691500
15
256691900
20
256692300
25
256692700
30
256693100
35
256693500
40
256693900
50
256694300
60
256694700
70
256695100
75
256695500
100
256695900
Part No., Left-Side
Breaker Mtg. Kit
(For Reference Only)
Part No., Right-Side
Breaker Mtg. Kit
(For Reference Only)
528501
528500
1 Provides an alarm during an electrical or manual trip condition.
Table K
Page 22 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List BF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Battery Disconnect (LVBD)
Features
♦
Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, (3) battery connection
points, and thirteen (13) GMT fuse load distribution positions.
♦
Five (5) 0A to 15A GMT fuse load distribution positions.
Home
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at
+40°C (+104°F) and 59.5A at 65°C (+149°F).
Unless otherwise specified fuses are mounted from bottom to top,
starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of
any value.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses
of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be
separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
•
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a
fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, or NF) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 , List 67, and/or List 68)
as required. List 65, List 67 and List 68 are factory installed.
6) The controller remains powered when the LVBD contactor opens. Specify if you require List BF to be
factory configured for the controller not to be powered when the LVBD contactor opens.
•
Page 23 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List LF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Load Disconnect (LVLD)
Features
♦
Provides a Distribution Unit with Low Voltage Load Disconnect
(LVLD), a battery shunt, (3) battery connection points, and
thirteen (13) GMT fuse load distribution positions.
♦
Five (5) 0A to 15A GMT fuse load distribution positions.
Home
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at
+40°C (+104°F) and 59.5A at 65°C (+149°F).
Unless otherwise specified fuses are mounted from bottom to top,
starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of
any value.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses
of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be
separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
•
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a
fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, or NF) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68)
as required. List 65, List 67 and List 68 are factory installed.
•
Page 24 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List NF: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
♦
Provides a Distribution Unit w/out low voltage disconnect, a
battery shunt, (3) battery connection points, and thirteen (13)
GMT fuse load distribution positions.
♦
Five (5) 0A to 15A GMT fuse load distribution positions.
Home
♦ Eight (8) 0A to 10A GMT fuse load distribution positions.
Restrictions
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at
+40°C (+104°F) and 59.5A at 65°C (+149°F).
Unless otherwise specified fuses are mounted from bottom to top,
starting with the highest capacity and working to the lowest capacity.
In an ambient of 40°C (+104°F):
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of
any value.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses
of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be
separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
•
•
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a
fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, or NF) for each List shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68)
as required. List 65, List 67 and List 68 are factory installed.
•
Page 25 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)
Features
Home
Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, (3) battery connection
points, four (4) bullet nose-type circuit breaker load distribution
positions, five (5) GMT fuse load distribution positions (10A
maximum).
Restrictions
For use with Lists 2 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68)
as required. List 65, List 67 and List 68 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
6) The controller remains powered when the LVBD contactor opens. Specify if you require List BC to be
factory configured for the controller not to be powered when the LVBD contactor opens.
♦
Page 26 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD)
Features
Home
Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery connection
points, four (4) bullet nose-type circuit breaker load
distribution positions, five (5) GMT fuse load distribution
positions (10A maximum).
Restrictions
For use with Lists 2 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68)
as required. List 65, List 67 and List 68 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
♦
Page 27 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and w/out Low Voltage Disconnect
Features
Home
Provides a Distribution Unit w/out low voltage disconnect, a
battery shunt, (3) battery connection points, four (4) bullet
nose-type circuit breaker load distribution positions, five (5)
GMT fuse load distribution positions (10A maximum).
Restrictions
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @
+65°C (+149°F) maximum capacity. Maximum GMT fuse size is
10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68)
as required. List 65, List 67 and List 68 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
♦
Page 28 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List BA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Battery Disconnect (LVBD)
Features
Home
Provides a Distribution Unit with Low Voltage Battery Disconnect
(LVBD), a battery shunt, two (2) bullet nose-type circuit breaker
load distribution positions, two (2) bullet nose-type circuit breaker
battery disconnect positions, five (5) GMT fuse load distribution
positions (10A maximum).
Restrictions
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @
+65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required
between GMT fuses greater than 5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be
factory configured for the controller not to be powered when the LVBD contactor opens.
♦
Page 29 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List LA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Load Disconnect (LVLD)
Features
♦
Home
Provides a Distribution Unit with Low Voltage Load Disconnect
(LVLD), a battery shunt, two (2) bullet nose-type circuit breaker
load distribution positions, two (2) bullet nose-type circuit breaker
battery disconnect positions, five (5) GMT fuse load distribution
positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with Lists 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @
+40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 30 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List NA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and w/out Low Voltage Disconnect
Features
Home
Provides a Distribution Unit w/out low voltage disconnect, a
battery shunt, two (2) bullet nose-type circuit breaker load
distribution positions, two (2) bullet nose-type circuit breaker
battery disconnect positions, five (5) GMT fuse load distribution
positions (10A maximum).
Restrictions
For use with Lists 2 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
Maximum load distribution or battery circuit breaker size is 75A @
+65°C (+149°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers
(Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
2) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
3) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
♦
Page 31 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
Features
♦
Home
1U-high GMT fuse panel that provides Single Load
Distribution (-48V)
Provides twenty (20) 0A to 15A GMT fuse load
distribution positions.
Caution: At +40°C and +65°C ambient, a fuse with a
rating of greater than 10 amperes SHALL
HAVE an empty mounting position between
it and any other fuse.
♦
♦
Maximum Capacity: 80A @ +40°C and 80A @ +65°C
♦
Factory mounted and connected to List 2 or 6 shelf.
♦
If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG
loads are disconnected.
If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive
battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System
Controller fuse alarm
Restrictions
Mounts only immediately above List 2 or 6 shelf.
Maximum distribution current is 80A.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 2 or 6 shelf as required.
Also order the following as required.
2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.
♦
Page 32 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
ACCESSORY DESCRIPTIONS
Relay Racks
Features
♦ The following relay racks are available.
Restrictions
Customer must mount power/distribution shelf in relay rack. If battery trays are ordered, they are factory
mounted in the relay rack.
Ordering Notes
1) Order from relay racks listed in Table 1.
Part
Number
Available Mounting
Positions (1RU = 1-3/4”)
Size
Notes
23” Relay Racks
543156
51-3/8” H x 23” W
28RU
Welded
543161
6’0” H x 23” W
37RU
Welded
543160
7’0” H x 23” W
45RU
Seismic
(Note 1)
543162
7’0” H x 23” W
45RU
Welded
543163
7’6” H x 23” W
48RU
Welded
543164
8’0” H x 23” W
51RU
Welded
19” Relay Racks
525003
51-3/8” H x 19” W
28RU
Welded
534653
6’0" H x 19” W
37RU
Seismic
(Note 1)
524961
6’0” H x 19” W
37RU
Welded
534654
6’6” H x 19” W
41RU
Seismic
(Note 1)
534651
6’6” H x 19” W
41RU
Welded
528183
7’0” H x 19” W
45RU
Seismic
(Note 1)
524988
7’0” H x 19”W
45RU
Welded
524963
7’6” H x 19” W
48RU
Welded
534652
8’0" H x 19” W
51RU
Welded
Note 1: Complies with Bellcore Seismic Zone 4 Requirements
Table 1
Available Relay Racks
Page 33 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Mounting and Adapter Kits
Optional Wall Mount Bracket Kit for Lists 2 and 6, P/N 553203
Features
♦
Allows for vertical wall mounting.
♦ See Physical Size Information for mounting dimensions.
Restrictions
Customer must supply mounting fasteners for securing the Wall Mount Brackets to
the wall.
Ordering Notes
1) Order P/N 553203, which consists of two (2) wall brackets (P/N 553058 and 553059) and eight (8) 12-24
x ¾” screws with four (4) ground washers for attaching the brackets to the shelf.
Optional 19” to 23” Rack Adapter Kit, P/N 545728
Features
♦ Allows for 23” relay rack mounting
Ordering Notes
1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4)
12-24 x 1/”2 thread forming screws.
Optional Vertical Flush Mount Kit for List 2, P/N 556851
Features
♦
Allows for vertical flush mounting.
♦ This kit provides rear AC.
Restrictions
For List 2 only
For vertical mount only.
Ordering Notes
1) Order P/N 556851 as required.
Page 34 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Distribution Devices
GMT Load Distribution Fuses
Features
♦
Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)
0-10A GMT load distribution fuses.
♦
Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.
♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10A fuses, for which
load should not exceed 70% of device rating.
The 70% restriction for 10A GMT fuses also applies to 15A GMT fuses.
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA only) and Load
Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) under WIRING NOTES for additional wiring
restrictions.
Ordering Notes
1) Order GMT fuses per Table 2.
Ampere Rating
Part Number
Fuse Color
18/100 GMT-A
248610301
--
1/4
248610200
Violet
1/2
248610300
Red
3/4
248610500
Brown
1-1/3
248610700
White
2
248610800
Orange
3
248610900
Blue
5
248611000
Green
7-1/2
248611300
Black-White
10
248611200
Red-White
15
248611500
Red-Blue
Replacement
Dummy Fuse
248872600
--
Replacement Safety
Fuse Cover
102774
--
Table 2
GMT Fuses
Page 35 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load Distribution)
Features
♦
Home
Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit
breakers.
Each List BA and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit
breakers and up to two (2) bullet nose-type load distribution circuit breakers.
Restrictions
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (Circuit Breakers) and Input Battery Wiring (to Battery Disconnect Circuit
Breakers) under WIRING NOTES for additional wiring restrictions.
Ordering Notes
1) Order circuit breakers per Table 3.
♦
Part Number
Ampere
Rating
Number of
Poles (and
Mounting
Positions)
Electrical Trip
(White Handle)
Electrical/
2
Mechanical Trip
(Black Handle)
1
1
102272
101596
3
1
102273
101597
5
1
102274
101598
10
1
102275
101599
15
1
102276
101600
20
1
102277
101601
25
1
102278
101602
30
1
102279
101603
35
1
102280
101604
40
1
102281
101605
45
1
121998
121997
50
1
102282
101606
60
1
102283
101607
70
1
102284
101608
75
1
102285
101609
80
1
121996
121995
90
1
138887
138888
100
1
102286
101610
1
See Table 8 for recommended wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note: Electrical Trip only circuit breakers are not typically used for battery disconnect circuit
breakers.
Table 3
Bullet Nose-Type Circuit Breakers
Page 36 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Bulk Output Bus bar, P/N 535015
Features
♦
Provides replacement for circuit breakers shown in Table 3.
♦
Includes two (2) bullet terminals.
♦
Each List BC, LC, and NC Distribution Unit holds up to four (4) load bus bars.
Each List BA and NA Distribution Unit holds up to two (2) load bus bars and up
to two (2) battery bus bars.
Restrictions
Bulk Output Bus bars are ordered separately.
Maximum number of Bulk Output Bus bars per system is four (4).
Ordering Notes
1) Order by P/N 535015 as required.
♦
AC Input Cables and Line Cords
AC Input Cable Assembly, P/N 535232
Features
♦
Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and the remaining end un-terminated.
Restrictions
Rated for 30A.
Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6
ordered.
AC Input Cable Assembly, P/N 553202
Features
♦
Provides one (1) 12’ long, 8 AWG, AC Input Cable Assembly;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and the remaining end un-terminated.
Restrictions
Rated for 30A.
Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6
ordered.
Page 37 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
AC Input Line Cord, P/N 540946, 208/240VAC
Features
♦
Provides one (1) 14’ long, 8/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6
ordered.
AC Input Line Cord, P/N 545616, 208/240VAC
Features
♦
Provides one (1) 6’ long, 8/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6
ordered.
AC Input Line Cord, P/N 545252, 120VAC
Features
♦
Provides one (1) 14’ long, 8/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6
ordered.
Page 38 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
AC Input Line Cord, P/N 545478, 120VAC
Features
♦
Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
AC Input Line Cord, P/N 545479, 120VAC
Features
♦
Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-15P twist-lock plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
AC Input Line Cord, P/N 545480, 208/240VAC
Features
♦
Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-15P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 15A at 208/240VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
Page 39 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
AC Input Line Cord, P/N 545481, 120VAC
Features
♦
Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-20P twist-lock plug.
Restrictions
For 120 VAC only (rated for 20A at 120VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 6
ordered.
AC Input Line Cord, P/N 545482, 208/240VAC
Features
♦
Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 6-15P plug.
Restrictions
For 208/240 VAC only (rated for 15A at 208/240VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
AC Input Line Cord, P/N 545553, 208/240VAC
Features
♦
Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-20P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 20A at 208/240VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
Page 40 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
AC Input Line Cord, P/N 547525, 120VAC
Features
♦
Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616,
545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered.
AC Input Line Cord, P/N 548457, 120VAC
Features
♦
Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord;
♦
terminated on one end with a Molex plug which mates with AC input receptacle
on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P twist-lock plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232,
553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or
548457) for each List 2 ordered.
AP6C57EA/EB Ring and Distribution Module
Features
♦
When used with List 6, this module is designed to
supply a filtered and regulated –48 VDC source and a
continuous 20 Hz ringing supply source to imbedded
subscriber loop carrier telecommunication systems
(such as SLC-96 or SLC Series-5) requiring up to 45
A of load capacity.
♦
Designed to mount in a 23” relay rack, the module is
one rack unit high, with 5” front projection.
♦
Includes two (2) 50VA ringers with automatic transfer
capability (N+1 redundancy).
♦
Provides 35 DC distribution fuse positions, configured
in five groups of seven, feeding five channel banks. Includes 35 dummy fuses.
♦
Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution
fuses are included with each cable assembly ordered.
♦
An Order Wire Option provides a connection interface for an analog communication link over a metallic
pair, with surge protection.
♦
See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete
specifications.
Page 41 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Restrictions
Cannot be used with Distribution units List BF, LF, or NF.
Ordering Notes
1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626).
2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order
AP6C57EB (A7000796).
3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable
assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable
assemblies can be mixed.
ORDERING CODE
DESCRIPTION
P7000858
Cable assy for one SLC96 channel bank (8 ft.)
P7001139
Cable assy for one SLC96 channel bank (20 ft.)
P7000859
Cable assy for one SLC5 channel bank (8 ft.)
P7001136
Cable assy for one SLC5 channel bank (20 ft.)
P7000937*
Cable assy for one channel bank, generic applications (8 ft.)
*Note: Each channel bank position on the panel has a maximum capacity of 11A.
4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect
between a power shelf and the DC input terminals of one (1) Ring & Distribution Module.
5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table.
ORDERING
CODE
DESCRIPTION
547646
Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2
battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)
547647
Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for
2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)
6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the
following table.
ORDERING CODE
DESCRIPTION
A0885525
1.33A Alarm SAN-O Fuse
A0885530
3A Alarm SAN-O Fuse
A0885531
5A Alarm SAN-O Fuse
A0885532
10A Alarm SAN-O Fuse
A7000627 (AP8C55AA)
50VA Ring Generator
Page 42 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
NetSure™ 211BC Battery Cabinet (Spec. No. 541434)
Features
♦
The NetSure™ 211BC Battery Cabinet is rated at
30 amperes, and can be mounted in a 19” or 23”
nominal relay rack, or mounted to a suitable wall.
♦
The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦
Battery circuit breaker alarm leads are provided
to tie into the power system’s alarm circuit.
♦
The Battery Cabinet is equipped with a battery
cable terminated in an Anderson connector.
♦
Cables to connect the batteries (as specified in
the table under Order Notes) into the Battery
Cabinet provided.
Battery Cabinets can be paralleled to provide
greater reserve time. Battery cabinets contain a
second Anderson battery connector for plugging
one cabinet into another.
Ordering Notes
1) Order by Spec. No. 541434 as required.
2) Also order four (4) batteries per Battery Cabinet
per the following table.
♦
Battery
Manufacturer
Manufacturer
P/N
Emerson
P/N
Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
Hawker
SBS 15
139091
14
12.50
Fiamm
12SLA12
139092
12
12.35
EaglePicher
HE-12V7.7FR
139094
6.9
5.94
EaglePicher
HE-12V12.7FR
139093
11.6*
9.68
Enersys
NP18-12FR
139774
16 *
13.60
* 10Hr rate
3) When ordering 139774 batteries, also order 545427 Battery Connection kit.
4) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 43 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
NetSure™ 211BC Battery Cabinet (Spec. No. 545534)
Features
♦
The NetSure™ 211BC Battery Cabinet is rated at 30
amperes, and can be mounted in a 19” or 23” nominal
relay rack, or mounted to a suitable wall.
♦
The Battery Cabinet contains one (1) 40 ampere battery
disconnect circuit breaker.
♦
Battery circuit breaker alarm leads are provided to tie into
the power system’s alarm circuit.
♦
The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦
Cables to connect the batteries (as specified in the table
under Ordering Notes) into the Battery Cabinet provided.
Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into
another.
Ordering Notes
1) Order by Spec. No. 545534 as required.
2) Also order four (4) batteries per Battery Cabinet per the
following table.
♦
Battery
Manufacturer
Manufacturer
P/N
Emerson P/N
Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
Enersys
SBS B10
140553
38
28.20
C&D / Dynasty
TEL12-30
140455
30.5
26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 44 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
NetSure™ 211BC Battery Cabinet (Spec. No. 545506)
Features
♦
The NetSure™ 211BC Battery Cabinet is rated at 30
amperes, and can be mounted in a 23” nominal relay
rack, or mounted to a suitable wall.
♦
The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦
Battery circuit breaker alarm leads are provided to tie
into the power system’s alarm circuit.
♦
The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦
Cables to connect the batteries (as specified in the
table under Ordering Notes) into the Battery Cabinet
provided.
Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet
into another.
Ordering Notes
1) Order by Spec. No. 545506 as required.
2) Also order four (4) batteries per Battery Cabinet per
the following table.
♦
Battery
Manufacturer
Manufacturer
P/N
Emerson P/N
Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
Enersys
SBS B10
140553
38
28.20
Enersys
SBS 40
140581
38
28.00
C&D/ Dynasty
TEL12-30
140455
30.5
26.70
C&D/ Dynasty
TEL12-45
140454
46
26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 45 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
NetSure™ 211BC Battery Cabinet (Spec. No. 554631)
Features
♦
The NetSure™ 211BC Battery Cabinet is rated at 30
amperes, and can be mounted in a 19” or 23” nominal relay
rack, or mounted to a suitable wall.
♦
The Battery Cabinet contains one (1) 40 ampere battery
disconnect circuit breaker.
♦
Battery circuit breaker alarm leads are provided to tie into the
power system’s alarm circuit.
♦
The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦
Cables to connect the batteries (as specified in the table
under Ordering Notes) into the Battery Cabinet provided.
Battery Cabinets can be paralleled to provide greater reserve
time. Battery cabinets contain a second Anderson battery
connector for plugging one cabinet into another.
Ordering Notes
1) Order by Spec. No. 554631as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
♦
Battery
Manufacturer
Manufacturer
P/N
Emerson P/N
Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
GNB
M12V40F
241173815
40
39.00
Note: When wall mounted, a battery cabinet frame grounding landing point adapter, P/N 556872, is provided.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Frame Grounding Point
(1/4-20 Studs on 5/8” Centers)
Frame Ground Landing
Point Adapter P/N 556872
Attach Frame Ground Landing
Point Adapter to Cabinet
Page 46 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Battery Disconnect Unit
Features
♦
Battery Disconnect Unit with mounting tabs.
♦
Two 1/4-20 studs w/ hardware provided for installation of single hole
battery lugs.
♦ One (10’ long) alarm lead provided.
Restrictions
Circuit breakers are ordered separately.
Maximum number of Battery Disconnect Units per system is three (3).
Ordering Notes
1) Order by P/N 535282 as required.
2) Order a circuit breaker for each Battery Disconnect Unit from Table 4.
3) Also order two (2) P/N 245350815 lugs for each battery disconnect
circuit breaker ordered.
4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery
Disconnect Units are to be used (daisy-chains the alarm terminal of up
to three [3] Battery Disconnect Units). (Section of alarm lead between
Battery Disconnect Units is 30”, section of alarm lead between Battery
Disconnect Unit and system’s alarm terminal is 84”.)
Yellow Jumper/Alarm Lead (P/N 524384)
(for use when more than one Battery
Disconnect Units are ordered)
Ampere
Rating
P/N
Electrical/Mechanical
1
Trip
(Black Handle)
Ampere
Rating
P/N
Electrical/Mechanical
1
Trip
(Black Handle)
1
256690300
35
256693500
3
256690700
40
256693900
5
256691100
50
256694300
10
256691500
60
256694700
15
256691900
70
256695100
20
256692300
75
256695500
25
256692700
100
256695900
30
256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
Table 4
Battery Disconnect Unit Circuit Breakers
Page 47 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
SM TEMP Temperature Concentrator (P/N 547490)
Home
Features
♦
Allows for multiple temperature probes to be used for
temperature compensation. Compensation can be based on
highest probe temperature or average probe temperature.
♦
Provides (8) temperature probe inputs per SM TEMP.
♦
Can be cascaded up to (8) SM TEMP modules, connecting up to
64 temperature probes.
♦ Provides analog output for all controllers.
Restrictions
Concentrator needs to plug into analog temp input on IB2 board.
Ordering Notes
1) Order P/N 547490.
2) Order up to (8) 3-meter (P/N 547749) or 10-meter (P/N 547750) temperature probes for each
concentrator.
SM Module RS-485 Interface Cable P/N 547674
Features
♦
Provides 4’ cable for connecting SM supervisory modules to the system RS-485
interface connector.
♦ For interface with SM AC, SM BAT, SM BRC, or SM IO modules.
Restrictions
One (1) RS-485 connector is available in the system.
Ordering Notes
1) Order P/N 547674 as required.
Alarm Cables
Features
Two sets of Alarm Cables are available. One set for the Digital Inputs and another set for the Relay
Outputs. One half of the Relay Outputs Alarm Cable is provided and factory connected in the shelf. The
other half (includes mating connector on one end and un-terminated on the other end) must be ordered
separately. Both halves of the Digital Inputs Alarm Cable must be ordered separately. When ordered, one
half of the Digital Inputs Alarm Cable is factory connected in the shelf. The other half has a mating
connector on one end and is un-terminated on the other end.
Ordering Notes
1) For the Relay Outputs Alarm Cable, P/N 541308 (3 ft.) is provided and factory connected in the shelf. A
mating cable, P/N 541309 (10 ft.) or P/N 545644 (50 ft.), must be ordered separately.
2) For the Digital Inputs Cable, order P/N 541310 (shelf side, 3 ft.) and P/N 541311 (customer side, 10 ft.).
Note: A custom digital input cable (P/N 545591) and internal wiring kit (P/N 545594) is available. This
kit is factory installed only.
♦
Page 48 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Optional Bullet-Nose-type 6-Position GMT Fuse Board (Part No. 545332)
Home
Features
♦
Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit.
♦
Provides six (6) 0A to 15A GMT fuse load distribution positions.
♦
Screw clamp type load and load return terminals
provided.
Includes six (6) dummy fuses equipped with safety fuse
covers.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Terminal block wire size capacity: 24 to 14 AWG.
Requires two (2) bullet device mounting positions.
Fuse Module has a 30A @ +40°C (+104°F) and +65°C
(+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top
with highest value in the lowest position.
Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Factory installed only.
Ordering Notes
1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required.
2) Order GMT fuses as required per Table 2.
♦
Page 49 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Replacement Components
Ordering Notes
1) Refer to Table 6.
Item
Part Number
2000W Rectifier Module
1R482000
2000W High Efficiency Rectifier Module
1R482000e
Rectifier Module Fan
SCU+ (Standard Control Unit Plus)
32010096 for 1R482000
32010106 for 1R482000e
1M521BNA*
* Also specify the appropriate
SCU+ configuration file. Refer to the
configuration file label on your
existing SCU+ Controller.
ACU+ Controller Module
1M820BNA*
* Also specify the appropriate ACU+
configuration file. Refer to the
configuration file label on your
existing ACU+ Controller.
Temperature Probe
Order per List 90 (9 ft. long)
or List 91 (30 Ft. long)
(or if only one piece of the two piece
probe is needed, see the List 90 or 91
description for part numbers)
Table 5
Replacement Part Numbers
Page 50 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Wiring Notes
Refer also to the next section, Wiring Illustrations.
AC Input Branch Circuit Protection and Wiring
Features
♦
Each shelf contains side mounted plug-in Molex AC input connectors. Rear AC access if P/N 556851
ordered.
AC input branch circuits are connected via AC Input Cable Assemblies/Line Cords ordered with the
system.
Restrictions
For correct AC input wire size, order the appropriate Input Cable Assembly/Line Cord for each AC input
branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORIES DESRIPTIONS section of
this document.
Each shelf requires two AC input branch circuits.
In the 19” shelf, each feeds one rectifier. Recommended branch circuit protection is 15 amperes.
In the 23” shelf, one feeds one rectifier and the other feeds two rectifiers. Recommended branch circuit
protection is 30 amperes.
Branch circuit protective devices should be of the time-delay or high inrush type.
♦
External Alarm and Monitoring Wiring
Features
Alarm output and monitoring input leads are connected to screw-type terminal blocks located on the
Signal Interface Assembly located inside the shelf. These leads enter the right side (as viewed from the
front) of the shelf and are accessible from the front of the shelf. A wireway is provided to route the wires
to the Signal Interface Assembly.
Restrictions
Terminal block wire size capacity is 16 to 26 AWG.
Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
♦
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF)
Features
Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of
fuse amperage sizes, and that two different types of receptacles are provided.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
♦
Page 51 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Ordering Notes
1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end
with the appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse
connector, and are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco
350537-3 [reel].
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)
Features
Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated
at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
♦
Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module)
Features
Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse
Module.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 24 to 14 AWG.
♦
Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
Features
Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to
threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed
from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
♦
Page 52 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG
can be used, but the number of breaker positions will be reduced as follows;
• 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,
LC, and NC). Use 6 AWG for CO Ground.
• 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use
6 AWG for CO Ground.
For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on
the termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 7.
2) For other available lugs, refer to drawings 031110100 through 031110300.
Load Distribution Wiring (GMT Fuses) (List KG)
Features
Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front
of the assembly.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 26 to 14 AWG.
♦
CO Ground Wiring
Features
♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.
Restrictions
Recommended CO ground wire size is 6 AWG.
Recommended lug is 245346500 (2-hole, 10-32 clearance holes, and 5/8” centers).
Page 53 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Circuit
Breaker
Amperage
1, 3, 5,
10A
15A
20A
25A
30A
35A
40A
45A
50A
60A
70A
75A
80A
90A
100A
2-hole
Recm 90°C Wire Size
14 AWG
37
(3, 4, 5)
24
(3, 4)
---------
12 AWG
58
10 AWG
8 AWG
6 AWG
(2)
Loop Length (feet)
(3, 4, 5)
93
(3, 4, 5)
62
(3, 4, 5)
46
(3, 4,)
37
(3, 4)
31
------
39
(3, 4)
29
--------
(3, 4, 5)
(3, 4, 5)
148
(3, 4, 5)
236
(3, 4, 5)
99
(3, 4, 5)
74
(3, 4, 5)
59
(3, 4, 5)
49
(3, 4)
42
(3, 4)
37
(3, 4)
33
(3)
29
--
1
2
3
4
5
6
4 AWG
2 AWG
(3, 4, 5)
--
--
(3, 4, 5)
----(3, 4)
107
(3, 4)
94
(3, 4)
83
(3, 4)
75
(3, 4)
62
(3, 4)
53
(3, 4)
50
(3, 4)
47
(3)
41
--
---------
99
(3, 4)
85
(3, 4)
79
(3, 4)
74
(3, 4)
66
(3, 4)
59
245346800
245346900
157
(3, 4, 5)
118
(3, 4, 5)
94
(3, 4, 5)
78
(3, 4, 5)
67
(3, 4, 5)
59
(3, 4)
52
(3, 4,)
47
(3, 4)
39
(6)
245390100
(1)
Recommended Crimp Lug
245390100 245390100 245346600 245346500
(3, 4)
Wire sizes are based on recommendations of the American National Standards
Institute (ANSI) approved National Fire Protection Association's (NFPA)
National Electrical Code (NEC). Table 310-16 for wire rated at 90°C conductor
temperature operating in ambient temperatures of 40°C, 50°C, and 65°C was
used. For other operating ambient temperatures, refer to the NEC. For
operation in countries where the NEC is not recognized, follow applicable
codes.
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less
at listed branch current for the loop lengths shown. Loop length is the sum of
the lengths of the positive and negative leads.
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating
Temperature.
Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating
Temperature.
Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating
Temperature.
Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing
031110100 for lug crimping information.
Table 6
Recommended Battery and Load Distribution Wire Size and Lug Selection
(Bullet Nose-Type Circuit Breaker)
Page 54 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Input Battery Wiring (to battery bus bars) (Lists BF, LF, NF, BC, LC, and NC)
Features
Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the top of the shelf.
Restrictions
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width, 0.61 inches.
Ordering Notes
1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.
When making connections, observe correct polarity.
Refer to Table 8 for recommended wire sizes and lugs at rated maximum output capacity.
19” Version:
72A, maximum.
23” Version:
100A, maximum.
2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables. List 68
provides 6 AWG shelf side battery cables.
3) For other available lugs, refer to drawings 031110100 through 031110300.
♦
Maximum
Loop
Loop
Ambient
Recm 90°C
Current
Length (Ft)
Length (Ft)
Operating
Wire Size
(1)
(2)
(2)
(1)
(Amps) Temperature
1.0 Volt Drop
0.25 Volt Drop
(AWG)
72A
65°C
100A
40°C
Recommended
(3)
Crimp Lug
53.7
13.4
4
245346800
85.4
21.4
2
245346900
56.9
14.2
2
245346900
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire rated at 90°C conductor temperature operating in ambient temperature of
40°C and 65°C was used. For other operating ambient temperatures, refer to the NEC. For
operation in countries where the NEC is not recognized, follow applicable codes
2
Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column
heading, or less, at rated full load output current of the system for the loop lengths shown in this
column. Loop length is the sum of the lengths of the positive and negative leads.
3
Two-hole lug, 1/4-20 bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug
crimping information.
Table 7
Recommended Battery Wire Size and Lug Selection
Page 55 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA and NA)
Features
Home
Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be
used, but the number of breaker positions will be reduced as follows;
• 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC,
LC, and NC). Use 6 AWG for CO Ground.
• 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use
6 AWG for CO Ground.
For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on
the termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 8.
2) For other available lugs, refer to drawings 031110100 through 031110300.
♦
Page 56 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Wiring Illustrations
AC Input Wiring (List 6 shown)
Rectifiers are numbered left to
right as viewed from the front.
Front
AC Input connections are
made using the supplied
AC Input Cable Assemblies/
Line Cords connected here.
Front View
AC Input
Cable Assembly
L2-N
Ground
L1
AC Input
Line Cord
Blue*
White*
Green/Yellow*
Green*
Brown*
Black*
* Color of AC Input Cable
Assembly/Line Cord lead.
Nominal 120/208/240V
AC Input for Rectifier
Module #1
(In the 23” Shelf,
this input also connects
to Rectifier Module #3.)
Nominal 120/208/240V
AC Input for Rectifier
Module #2
* AC Input Cable Assembly / Line Cords
Part Number
Customer End
535232
553202
545252
540946
545616
545478
545479
545480
545481
545482
545553
547525
548457
unterminated
unterminated
L5-30P
L6-30P
L6-30P
5-15P
L5-15P
L6-15P
L5-20P
6-15P
L6-20P
L5-30P
5-15P
(List 2, 6)
(List 2, 6)
(List 2, 6)
(List 2, 6)
(List 2, 6)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
Page 57 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
AC Input Wiring for List 2 with Rear AC Input Connectors
Rear View
AC Input connections are
made using the supplied
AC Input Cable Assemblies/
Line Cords connected here.
Nominal 120/208/240V
AC Input for Rectifier
Module #1
Nominal 120/208/240V
AC Input for Rectifier
Module #2
AC Input
Cable Assembly
Brown*
Green/Yellow*
Blue*
* AC Input Cable Assembly / Line Cords
Part Number
535232
553202
545252
540946
545616
545478
545479
545480
545481
545482
545553
547525
548457
Customer End
Use In
unterminated
unterminated
L5-30P
L6-30P
L6-30P
5-15P
L5-15P
L6-15P
L5-20P
6-15P
L6-20P
L5-30P
5-15P
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
(List 2)
AC Input
Line Cord
Black*
L1
Green*
Ground
White*
L2-N
* Color of AC Input Cable
Assembly/Line Cord lead.
Page 58 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Alarm and Monitoring Wiring (List 6 shown)
Front
IB2 Board
RS-485 Connection
for SM AC, SM BAT,
SM BRC, or SM IO
Supervisory Modules.
See module data
sheets. (Functional
with ACU+ only.)
IB2 Customer
Interface Board
Relay
No.
J9
Relay Output Term. Blocks
J8
J7
J6
7
5
3
Digital Input Term. Blocks
J5
J4
J3
8 7 6 5 4 3 2 1
1*
NO C NC NO C NC NO C NC NO C NC
5 3 1
5 3 1
5 3 1 5 3 1
NO C NC NO C NC NO C NC NO C NC
Relay
No.
6
4
8
2
6
4
6
2
6
4
4
2
6
4
2
2
5
3
6
1
4
5
2
3
6
1
4
5
2
3
6
Input
No. (–)
1
4
2
8 7 6 5 4 3 2 1
Input
No. (+)
J12
J11
Temp. Probe #2
or
SM TEMP Module
Temp. Probe #1
or
SM TEMP Module
J2
J1
SW1
Switch sections must be set to this position
to interface with SCU+/ACU+ controller.
The relay assigned by the Controller to be the”Major Summary” (SCU+) or “Critical Summary” (ACU+) alarm (relay 1
* by
default) will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm
condition, opening the contacts between the C and NO terminals, and closing the contacts between the C and NC
terminals.
The remaining seven (7) alarm relays energize during an alarm condition, closing the contacts between the C and NO
terminals, and opening the contacts between the C and NC terminals.
A factory-connected jumper supplies +BAT (Battery Return) to the positive side of Digital Input # 2.
Page 59 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Interface Connections (continuation)
Yellow Alarm Lead
(P/N 535294)
(factory wired to
circuit breaker
alarm terminal)
Alarm Wiring to a Single
External Battery Disconnect Unit
Torque to 84 in-lbs
using supplied hardware
Procedure
1.
Connect YELLOW lead exiting top of
Battery Disconnect Unit per table below.
Remove quick connect terminal first.
The YELLOW lead is factory connected
to circuit breaker “C (Common)” alarm
terminal in the Battery Disconnect Unit.
2.
There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
3.
Connect loose end of Jumper factory
connected to bottom terminal on
circuit breaker to circuit breaker
“NC (Normally Closed)” alarm
terminal.
To
To
Power
System Battery
Connect to shelf
per table below.
Remove quick
connect terminal
first.
EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration
to show wiring details.)
541311 Alarm Cable
on shelf
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Pin 3 of J3 on Customer Interface BD
(negative side of Digital Input 2)
O-R Lead of 541311
Splice and heat shrink tubing included with 541311
Page 60 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Interface Connections (continuation)
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately
and supplied loose.
Must be wired
by the customer to
each circuit breaker
“C (Common)”
alarm terminal)
Yellow Alarm Lead
(P/N 535294)
(factory wired to
circuit breaker
alarm terminal)
* No terminal
on 524384
jumper
Connect to
shelf per
table below.
see
previous
page
REMOVE
COMPLETELY
FROM ALL BATTERY
DISCONNECT UNITS
AND DISCARD.
see
previous
page
see
previous
page
1st EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration
to show wiring details.)
2nd EXTERNAL BATTERY
DISCONNECT UNIT
Alarm Wiring to (2) to (3)
External Battery Disconnect Units
3rd EXTERNAL BATTERY
DISCONNECT UNIT
Procedure
1.
Completely remove YELLOW lead exiting top of
ALL Battery Disconnect Units and discard.
2.
Connect separately ordered YELLOW jumper/alarm
lead (P/N 524384) to circuit breaker “C (Common)”
alarm terminals in ALL Battery Disconnect Units.
Connect remaining end per table below.
541311 Alarm Cable
on shelf
NO
YES
3.
There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
4.
In ALL Battery Disconnect Units,
connect loose end of Jumper factory
connected to bottom terminal on
circuit breaker to circuit breaker
“NC (Normally Closed)”
alarm terminal.
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Pin 3 of J3 on Customer Interface BD
(negative side of Digital Input 2)
O-R Lead of 541311
Splice and heat shrink tubing included with 541311
Page 61 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Interface Connections (continuation)
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately
and supplied loose.
Must be wired
by the customer to
each circuit breaker
“C (Common)”
alarm terminal)
* No terminal
on 524384
jumper
Connect to
shelf per
table below.
see
previous
page
see
previous
page
see
previous
page
1st BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(Side cover removed in illustration
to show wiring details.)
2nd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
Alarm Wiring to Battery Disconnect Circuit
Breakers when (1) to (3) Battery Trays are Used
3rd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
Procedure
1.
Connect kit-supplied YELLOW jumper/alarm lead
(P/N 524384) to circuit breaker “C (Common)”
alarm terminals on ALL Battery Disconnect Circuit
Breakers. Connect remaining per table below.
2.
There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
541311 Alarm Cable
on shelf
3.
On ALL Battery Disconnect circuit
breakers, there should be a factory
connected Jumper connected from
the bottom terminal on the circuit
breaker to the circuit breaker “NC
(Normally Closed)” alarm terminal.
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
NO
Pin 3 of J3 on Customer Interface BD
(negative side of Digital Input 2)
YES
O-R Lead of 541311
Splice and heat shrink tubing included with 541311
Page 62 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
External Interface Connections (continuation)
Yellow Jumper/Alarm
Lead (P/O Cabinet)
Orange wire on
541434 not used
Connect to
shelf per
table below.
alarm
wire
alarm
wire
1st BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
alarm
wire
2nd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
3rd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Cabinets
Procedure
1.
Remove quick connect terminal from YELLOW battery
cabinet alarm lead and wire per table below.
541311 Alarm Cable
on shelf
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
NO
Pin 3 of J3 on Customer Interface BD
(negative side of Digital Input 2)
YES
O-R Lead of 541311
Splice and heat shrink tubing included with 541311
Page 63 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF in List 6, as shown)
Front
Load Distribution
Leads Enter Here
GMT Fuse
Positions
(Max. 15A)
GMT Fuse Load
Distribution Leads
Connect Here
Mating Connectors and 12 ’
Leads provided with List 62.
-48V on Left (Black Lead),
Return on Right (White Lead)
GMT Fuse
Positions
(Max. 10A)
GMT Fuse Load
Distribution Leads
Connect Here
Mating Connectors and 12 ’
Leads provided with List 61.
-48V on Left (Black Lead),
Return on Right (White Lead)
Page 64 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in List 6, as
shown)
Home
GMT Fuse Load
Distribution Leads
Connect Here
GMT Fuses
and Safety Covers
Max. 10A
Front
Mating Connectors and 12 ’
Leads provided with List 60
-48V on Left (Black Lead),
Return on Right (White Lead)
as viewed from side with door
closed
Page 65 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)
-48V Distribution
Leads
Home
Load Return
Leads
Page 66 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers),
and CO Ground Wiring (Lists BC, LC and NC, List 6 shown)
Home
Front
Load Distribution
Circuit Breakers
Circuit Breaker Load
Distribution and
CO Ground Leads
Enter Here
Front
Portion shelf removed
in illustration for clarity.
Leads are brought into
side of shelf, and tools
to secure lugs from
front of shelf.
-48V Load
Distribution
Leads
Load Return Leads
CO Ground Lead
10-32 studs (w/ hardware)
on 5/8” centers for installation
of customer provided two-hole lugs.
Page 67 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers),
and CO Ground Wiring (Lists BA, LA and NA, List 6 shown)
Home
Front
Load Distribution
Circuit Breakers
CO Ground, Circuit Breaker
Load Distribution, and Circuit
Breaker Battery Leads
Enter Here
Battery Disconnect
Circuit Breakers
Front
Portion of shelf removed
in illustration for clarity.
Leads are brought into
side of shelf, and tools
to secure lugs from
front of shelf.
-48V Load
Distribution
Leads
-48V Battery
Leads
OBSERVE PROPER
POLARITY WHEN
MAKING BATTERY
CONNECTIONS
Battery Return Leads
Load Return Leads
CO Ground Lead
10-32 studs (w/ hardware)
on 5/8" centers for installation
of customer provided two hole lugs.
Page 68 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
“B” Side Loads #6 - #10
Connections are made to
screw compression terminal blocks.
Wire size range is 26 to 14 AWG.
“B” Side Returns
Inputs for Side “A” and Side “B”
are strapped in this system.
“B” Side Loads #1 - #5
“A” Side Loads #6 - #10
“A” Side Returns
“A” Side Loads #1 - #5
Load Distribution Wiring (GMT Fuses) (List KG)
Page 69 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC in List 6, as shown)
List NC Distribution
Unit shown. List
BC, LC, NC,
BF, LF and NF
similar.
Front
List 65 provides 3’ long, 2AWG battery
cables terminated on one end with lugs
to connect to the input battery landings
and on the other end with an Anderson
connector.
List 66 provides 12’ long, 2AWG battery
cables terminated on one end an
Anderson connector and left unterminated
at the remaining end for connection
of battery lugs.
Distribution
Unit
Battery, Battery Return
and CO Leads
Enter Here
List BC, LC, and NC
Distribution Unit
Battery: 1/4-20 studs (w/ hardware)
on 5/8” centers for installation
on customer provided two-hole lugs.
CO Ground: 10-32 studs (w/ hardware)
on 5/8” centers for installation
on customer provided two-hole lugs.
CO Ground
Lead
Right Side
Battery Return
Leads
-48 Battery
Leads
List BF, LF, and NF
Distribution Unit
OBSERVE PROPER
POLARITY WHEN
MAKING BATTERY
CONNECTIONS
CO Ground
Lead
Right Side
Battery Return
Leads
-48 Battery
Leads
Page 70 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
Home
SPECIFICATIONS
Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R482000e) supplied
with your Power System.
For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B)
supplied with your Power System.
For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (Cdrawing) supplied with your Power System.
1. SYSTEM
1.1 Environmental Ratings
1.1.1 Lists 2 and 6 Operating Ambient Temperature Range (Specification Compliant):
(A) -40°C (-40°F) to +65°C (+149°F) with derating output.
(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +80°C (+176°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 95%, non-condensing.
1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut,
or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4”
multiple drilling).
Mounting angles are positioned for a 5-inch front projection mounting only.
1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be
blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient
Temperature Range stated above.
1.2 Compliance Information
1.2.1 Surge Protection: Refer to Paragraphs 2.3.5.
Note: This level of protection is a widely used standard for telecommunications power
equipment. As with all such equipment, it is the end user's responsibility to provide an
adequately sized Surge Suppression Device at the commercial power service entrance of
the building that reduces all incoming surges to levels below the classes/categories
stated for the equipment.
1.2.2 Safety Compliance:
(A) This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data
Processing, or Information Processing Equipment.
(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and
Certified by UL ("c UR") as a Component Type Power Supply.
Page 71 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
1.2.3
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
EMC and Safety:
(A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and
Immunity requirements as specified in GR-1089-Core Issue 4.
Home
EMC
Emissions
EN 55022: 1998
CFR 47 – Part 15
GR-1089 Issue 4
Test Level
Conducted
Class B
Radiated
Class B
Immunity
GR-1089 Issue 4
EN 61000-4-2 Electrostatic Discharge
8kV / 15kV
EN 61000-4-4 Electric Fast Transients
0.25kV / 0.5kV
Radiated Immunity
8.5V/m
Conducted Immunity
89dBuA
Surge IEEE C62.41
2kV / 6kV
SAFETY
EN 60950-1: 2001
1.2.4
Safety of Information Technology Equipment, including
Electrical Business Equipment
NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL)
per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance
reports.
For NETSURE™ 502NGFB to remain compliant during a fan failure condition, the backup battery
connection must be utilized to provide sufficient power to the loads for up to eight (8) hours when
the system is operated at greater than 50% output power. If no backup battery connection is
used, the system must operate with a redundant module installed.
1.3
Standard Features
1.3.1 AC Input Connections: AC input leads are connected to Molex connectors located on the side
of the shelf. Each shelf requires two (2) AC input branch circuits. In the 19” shelf, each feeds one
rectifier. In the 23” shelf, one feeds one rectifier and the other feeds two rectifiers.
1.3.2 Battery Connections: Battery and battery return leads terminated in two-hole lugs are
connected to threaded studs located inside the Distribution Unit. Battery leads are brought into
the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf.
1.3.3 Load Connections: Load distribution (circuit breakers, if furnished) and load return leads
terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit.
Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf.
Load distribution (GMT fuses) and load return leads are connected to receptacles located inside
the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
1.3.4 Alarm and Monitoring Connections: Alarm output and monitoring input leads are connected to
screw-type terminal blocks located on the Signal Interface Assembly located inside the shelf.
These leads enter the right side (as viewed from the front) of the shelf and are accessible from
the front of the shelf
Page 72 of 82
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136700
Issue AV, February 21, 2014
System Application Guide
Spec. No. 582136700 (Model 502NGFB)
1.3.5
1.3.6
Dimensions
(A)