SAG582136700 System Application Guide Spec. No. 582136700 (Model 502NGFB) Issue AV, February 21, 2014 Home SYSTEM OVERVIEW Description: The NetSure™ 502NGFB DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. This power system consists of the following mounted in a 2RU high by 19” or 23” wide shelf. • Rectifier Modules The 19” wide shelf accommodates two (2) Rectifier Modules. The 23” wide shelf accommodates three (3) Rectifier Modules. The Rectifier Module R48-2000 comes in 2000W power rating. The modules provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules are designed to provide constant power. They are designed with the latest patented switch-mode technology using DSP (Digital Signal Processing) functionality for efficient operation. This means that, within the normal operating ambient temperature range and input voltage range, the maximum available output power is a constant 2000W. Within these ranges, the Rectifier Modules operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. If ambient temperature rises above or input voltage falls below acceptable values, Rectifier Modules continue to operate but at derated output power levels. 1) Constant Voltage Mode: For any initial output voltage setting from 48 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 2000W. 2) Constant Power Mode: As load increases above approximately 2000W (nonadjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier Modules operate in the Constant Power Mode unless load continues to increase to the point where the current limit setting is reached. 3) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. • ACU+ (Advanced Control Unit Plus) The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms as well as PCU control, data acquisition, system alarm management, and advanced battery and energy management. The ACU+ contains an LCD display and keypad for local access. It provides connections for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe. The ACU+ provides Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management. Page 1 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 • • Home SCU+ (Standard Control Unit Plus) The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms. The SCU+ contains an LCD display and keypad for local access. It provides connections for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe. The SCU+ also provides Ethernet connection and SNMP capability. Distribution Unit Various Distribution Unit options are available, as described in this document. The Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) contactor. Family: Spec. No.: Model: Input Voltage Output Voltage: Output Capacity: Rectifier Module: System: Agency Approval: Framework Type: Mounting Width: Mounting Depth: Mounting Height: Access: Control: Color: Environment: System Application Guide Spec. No. 582136700 (Model 502NGFB) NetSure™ 582136700 502NGFB Nominal 120/208/240 volts AC, single phase, and 3-wire, 50/60 Hz, with an operating range of 100 to 250 volts. Acceptable input frequency range is 45 to 65 Hz. -48 Volts DC 2000W (41.6A) @ 208/240VAC Input and +45°C (R48-2000) or +55°C (R48-2000e) 1262W (26.3A) @ 120VAC Input and +45°C (R48-2000) or +55°C (R48-2000e) List 2 19” Version: 4000W (83A), maximum List 6 23” Version: 6000W (125A), maximum Note: 19” version is “Specification Compliant” up to 66 amperes (2000W) at +65°C (+149°F). 23” version is “Specification Compliant” up to 100 amperes (6000W) at +65°C (+149°F). UL 60950 Recognized, CAN/CSA 22.2 Relay Rack Mounted 19” or 23”, nominal 12” 3.5” (2RU) Front for Installation, Operation, and Maintenance Microprocessor Front Panels are Gray, Shelf is Galvaneal Lists 2 and 6: -40°C (-40°F) to +65°C (+149°F), with deratings (see SPECIFICATIONS section) Page 2 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) 582136700 Home Rectifier Module (2000W) or Rectifier Module (2000W, High Efficiency) List 2 (19” Shelf) SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA List 6 (23” Shelf) (shown) List BA: Side Molex AC Input Connectors (P/O List 2 and 6) and AC Input Cables/Line Cords List LA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Positions Low Voltage Load Disconnect (LVLD) List NA (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Positions NO Low Voltage Disconnect List BC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points DISTRIBUTION UNIT (continuation) List NC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions NO Low Voltage Disconnect (3) Battery Landing Points List BF: (13) GMT Fuse Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LF: (13) GMT Fuse Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points List NF: DISTRIBUTION UNIT (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Positions Low Voltage Battery Disconnect (LVBD) (13) GMT Fuse Load Positions NO Low Voltage Disconnect (3) Battery Landing Points Page 3 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) 58213670002 with P/N 556851 (Vertical Flush Mount Kit) Rectifier Module (2000W) or Rectifier Module (2000W, High Efficiency) Rear AC input Connectors (P/O 556851) and AC Input Cables/Line Cords SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA Distribution Unit Page 4 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Other List Options List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions (For use with Lists BC, LC, NC, BA, LA, and NA.) List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions (For use with Lists BF, LF, and NF.) List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions (For use with Lists BF, LF, and NF.) List 65: Shelf Side Battery Cables (For use with Lists BC, LC, NC, BF, LF, and NF) List 66: Battery Side Battery Cables (For use with Lists BC, LC, NC, BF, LF, and NF) List 67: Battery Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 68: Shelf Side Battery Cables (for use w/ Lists BC, LC, NC, BF, LF, and NF) List 89: Relay Rack Earthquake Anchor Kit List 90: Temperature Probe (12 ft. total) List 91: Temperature Probe (33 ft. total) List 93: Battery Tray (23”) List 94: Batter Tray (19”) List KG: GMT Fuse Distribution Panel Accessory Options Relay Racks Rack Adapter Kit Ring and Distribution Module Battery Cabinets SM TEMP Temperature Concentrator Distribution Devices AC Input Cables and Line Cords Digital Input and Relay Output Cables Optional Bullet-nose-type 6-position GMT fuse board Replacement Components Wiring Notes Wiring Illustrations SEE ALSO System Overview Table of Contents List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation Page 5 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) TABLE OF CONTENTS System Overview Picture List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation SYSTEM OVERVIEW................................................................................................................................................. 1 582136700 ............................................................................................................................................................. 3 58213670002 with P/N 556851 (Vertical Flush Mount Kit) ............................................................................... 4 TABLE OF CONTENTS ............................................................................................................................................. 6 LIST DESCRIPTIONS ................................................................................................................................................ 9 List 2: 19” Shelf ................................................................................................................................................ 9 List 6: 23” Shelf .............................................................................................................................................. 10 R48-2000 Rectifier Module ............................................................................................................................ 11 R48-2000e Rectifier Module, High Efficiency ................................................................................................ 11 ACU+ (Advanced Control Unit Plus), P/N 1M820BNA .................................................................................. 11 SCU+ (Standard Control Unit Plus), P/N 1M521BNA .................................................................................... 12 List 60: Load Lead Assemblies for GMT Fuses (for 10A positions) ............................................................... 12 List 61: Load Lead Assemblies for GMT Fuses (for 10A positions) ............................................................... 12 List 62: Load Lead Assemblies for GMT Fuses (for 15A positions) ............................................................... 13 List 65: Shelf Side Battery Cables, P/N 540814 ............................................................................................ 13 List 66: Battery Side Battery Cables, P/N 540954 ......................................................................................... 13 List 67: Battery Cable, P/N 545709 ................................................................................................................ 13 List 68: Shelf Side Battery Cables, P/N 557304 ............................................................................................ 14 List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ......................................................................... 14 List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) ......................................................................................................................................... 14 List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) ....................................................................................................................................... 15 List 93: Battery Tray for 23” Relay Rack ........................................................................................................ 15 List 94: Battery Tray for 19” Relay Rack ........................................................................................................ 19 List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) ......................................................................................................................................... 23 List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load Disconnect (LVLD) ......................................................................................................................................... 24 List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect ...................................................................................................................................................... 25 List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) ..................................................... 26 List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................... 27 List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect ............................................................................ 28 List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD) ......................................................................................................................................... 29 List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................................................................................................... 30 List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect ...................................................................................................................................................... 31 List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ............................................... 32 Page 6 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) ACCESSORY DESCRIPTIONS ............................................................................................................................... 33 Relay Racks ....................................................................................................................................................... 33 Mounting and Adapter Kits .............................................................................................................................. 34 Optional Wall Mount Bracket Kit for Lists 2 and 6, P/N 553203 .................................................................... 34 Optional 19” to 23” Rack Adapter Kit, P/N 545728 ........................................................................................ 34 Optional Vertical Flush Mount Kit for List 2, P/N 556851 ............................................................................... 34 Distribution Devices .......................................................................................................................................... 35 GMT Load Distribution Fuses ........................................................................................................................ 35 Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load Distribution) ............................................ 36 Bulk Output Bus bar, P/N 535015 .................................................................................................................. 37 AC Input Cables and Line Cords ..................................................................................................................... 37 AC Input Cable Assembly, P/N 535232 ......................................................................................................... 37 AC Input Cable Assembly, P/N 553202 ......................................................................................................... 37 AC Input Line Cord, P/N 540946, 208/240VAC ............................................................................................. 38 AC Input Line Cord, P/N 545616, 208/240VAC ............................................................................................. 38 AC Input Line Cord, P/N 545252, 120VAC .................................................................................................... 38 AC Input Line Cord, P/N 545478, 120VAC .................................................................................................... 39 AC Input Line Cord, P/N 545479, 120VAC .................................................................................................... 39 AC Input Line Cord, P/N 545480, 208/240VAC ............................................................................................. 39 AC Input Line Cord, P/N 545481, 120VAC .................................................................................................... 40 AC Input Line Cord, P/N 545482, 208/240VAC ............................................................................................. 40 AC Input Line Cord, P/N 545553, 208/240VAC ............................................................................................. 40 AC Input Line Cord, P/N 547525, 120VAC .................................................................................................... 41 AC Input Line Cord, P/N 548457, 120VAC .................................................................................................... 41 AP6C57EA/EB Ring and Distribution Module ................................................................................................ 41 NetSure™ 211BC Battery Cabinet (Spec. No. 541434) ................................................................................... 43 NetSure™ 211BC Battery Cabinet (Spec. No. 545534) ................................................................................... 44 NetSure™ 211BC Battery Cabinet (Spec. No. 545506) ................................................................................... 45 NetSure™ 211BC Battery Cabinet (Spec. No. 554631) ................................................................................... 46 External Battery Disconnect Unit .................................................................................................................... 47 SM TEMP Temperature Concentrator (P/N 547490) ....................................................................................... 48 SM Module RS-485 Interface Cable P/N 547674 ............................................................................................. 48 Alarm Cables...................................................................................................................................................... 48 Optional Bullet-Nose-type 6-Position GMT Fuse Board (Part No. 545332) ................................................. 49 Replacement Components ............................................................................................................................... 50 Wiring Notes ...................................................................................................................................................... 51 AC Input Branch Circuit Protection and Wiring .............................................................................................. 51 External Alarm and Monitoring Wiring ........................................................................................................... 51 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF) ...................................................................... 51 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)................................................. 52 Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ................................... 52 Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) .......................................... 52 Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 53 CO Ground Wiring .......................................................................................................................................... 53 Input Battery Wiring (to battery bus bars) (Lists BF, LF, NF, BC, LC, and NC) ............................................. 55 Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA and NA) ................................... 56 Wiring Illustrations ............................................................................................................................................ 57 AC Input Wiring (List 6 shown) ....................................................................................................................... 57 AC Input Wiring for List 2 with Rear AC Input Connectors ............................................................................ 58 External Alarm and Monitoring Wiring (List 6 shown) .................................................................................... 59 External Interface Connections (continuation) ............................................................................................... 60 External Interface Connections (continuation) ............................................................................................... 61 External Interface Connections (continuation) ............................................................................................... 62 External Interface Connections (continuation) ............................................................................................... 63 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF in List 6, as shown) ....................................... 64 Page 7 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in List 6, as shown) ............................................................................................................................................................ 65 Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................ 66 Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BC, LC and NC, List 6 shown) .................................................................................................. 67 Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA and NA, List 6 shown) ................................................................................................... 68 Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 69 Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC in List 6, as shown) ............................................... 70 SPECIFICATIONS.................................................................................................................................................... 71 1. System ........................................................................................................................................................... 71 1.1 Environmental Ratings ............................................................................................................................. 71 1.2 Compliance Information ........................................................................................................................... 71 1.3 Standard Features .................................................................................................................................... 72 PHYSICAL SIZE INFORMATION ............................................................................................................................ 74 Overall Dimensions – List 2 ............................................................................................................................. 74 Overall Dimensions – List 6 ............................................................................................................................. 75 Additional Dimensions – Lists 2 and 6 with Wall Mounting Kit (P/N 553203) ............................................. 76 Additional Dimensions - List 2 and Vertical Flush Mounting Kit (P/N 556851) ........................................... 77 Overall Dimensions – List KG .......................................................................................................................... 78 Overall Dimensions – 19” Battery Tray ........................................................................................................... 79 Overall Dimensions – 23” Battery Tray ........................................................................................................... 80 BATTERY MANUFACTURER INFORMATION ...................................................................................................... 81 RELATED DOCUMENTATION ................................................................................................................................ 81 REVISION RECORD ................................................................................................................................................ 82 Page 8 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home LIST DESCRIPTIONS List 2: 19” Shelf Features ♦ Consists of a 2RU high by 19” wide shelf. ♦ Includes side AC input housing with Molex connectors. ♦ Houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. ♦ Includes Relay Outputs Alarm Cable P/N 541308 (shelf side) factory connected in the shelf. Restrictions Each shelf holds up to two (2) Rectifier Modules. Ordering Notes 1) Order List 2 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or (1) ACU+ Controller (P/N 1M820BNA) per shelf. Also specify appropriate configuration file for your site. 3) Order up to two (2) Rectifier Modules per shelf: P/N 1R482000e or 1R482000. 4) Order AC Input Cables or Line Cords as required. Note that each 19” Shelf requires two (2) AC Input Cable Assemblies/Line Cords (each feeds one [1] rectifier). 5) Order one (1) Distribution Unit (List BF, LF, NF, BA, LA, NA, BC, LC, or NC) per shelf. 6) Order one (1) List 60 for each List BA, LA, NA, BC, LC, or NC ordered. Each List 60 provides five (5) GMT fuse load lead assemblies (10A maximum). Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) GMT fuse load lead assemblies (10A maximum). Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) GMT fuse load lead assemblies (15A maximum). 7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required. 8) Order Shelf Side or Battery Side Battery Cables (List 65 or List 68, and/or List 66) as required. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order Relay Rack Anchor Kit(s) (List 89) as required. 11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. 12) Order Battery Trays (List 94) as required. 13) Order Optional Vertical Flush Mount Kit, P/N 556851 as required. 14) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 15) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 16) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 17) Order Alarm Cables per ACCESSORY DESCRIPTIONS section. 18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 9 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home List 6: 23” Shelf Features ♦ Consists of a 2RU high by 23” wide shelf. ♦ Includes side AC input housing with Molex connectors. ♦ Houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. ♦ Includes Relay Outputs Alarm Cable P/N 541308 (shelf side) factory connected in the shelf. Restrictions Each shelf holds up to three (3) Rectifier Modules. Ordering Notes 1) Order List 6 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or (1) ACU+ Controller (P/N 1M820BNA) per shelf. Also specify appropriate configuration file for your site. 3) Order up to three (3) Rectifier Modules per shelf: P/N 1R482000e or 1R482000. 4) Order AC Input Cables or Line Cords as required. Note that each 23” Shelf requires two (2) AC Input Cable Assemblies/Line Cords (one feeds one [1] rectifier, the other feeds two [2] rectifiers). 5) Order a Distribution Unit (List BF, LF, NF, BA, LA, NA, BC, LC, or NC) per shelf. 6) Order one (1) List 60 for each List BA, LA, NA, BC, LC, or NC ordered. Each List 60 provides five (5) GMT fuse load lead assemblies (10A maximum). Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) GMT fuse load lead assemblies (10A maximum). Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) GMT fuse load lead assemblies (15A maximum). 7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required. 8) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65 or List 68, and/or List 66) as required. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order Relay Rack Anchor Kit(s) (List 89) as required. 11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. 12) Order Battery Trays (List 93) as required. 13) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 16) Order Alarm Cables per ACCESSORY DESCRIPTIONS section. 17) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 10 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home R48-2000 Rectifier Module Features Provides one (1) Model R48-2000, Spec. No. 1R482000, 2000 watt / 48 volt Rectifier Module. Restrictions Each List 2 Shelf (19”) holds up to two (2) Rectifier Modules. Each List 6 Shelf (23”) holds up to three (3) Rectifier Modules. Ordering Notes 1) Order by P/N 1R482000 as required. ♦ R48-2000e Rectifier Module, High Efficiency Features Provides one (1) Model R48-2000e, Spec. No. 1R482000e, 2000 watt / 48 volt High Efficiency Rectifier Module. Restrictions Each List 2 Shelf (19”) holds up to two (2) Rectifier Modules. Each List 6 Shelf (23”) holds up to three (3) Rectifier Modules. Ordering Notes 1) Order by P/N 1R482000e as required. ♦ ACU+ (Advanced Control Unit Plus), P/N 1M820BNA Features ♦ Provides the ACU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller. Ordering Notes 1) Order one (1) ACU+ (P/N 1M820BMA) or one (1) SCU+ Controller (P/N 1M521BNA) or for each shelf. For the ACU+ controller, specify also one of the following configurations. a) List 5 and 6 with Low Voltage Disconnect: 550166. b) List 5 and 6 without Low Voltage Disconnect: 550167. Note: For custom ACU+ configurations, contact Emerson. Page 11 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) SCU+ (Standard Control Unit Plus), P/N 1M521BNA Features ♦ Home Provides the SCU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions Each shelf must contain one (1) SCU+ Controller. Ordering Notes 1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N 1M820BMA) for each shelf. For the SCU+ controller, specify also one of the following configurations. a) List 2 and 6 with Low Voltage Disconnect: 545298. b) List 2 and 6 without Low Voltage Disconnect: 545299. Note: For custom SCU+ configurations, contact Emerson. List 60: Load Lead Assemblies for GMT Fuses (for 10A positions) Features Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA only. Ordering Notes 1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, and NA Distribution Unit. Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206. ♦ List 61: Load Lead Assemblies for GMT Fuses (for 10A positions) Features Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads. Restrictions For use with Lists BF, LF, and NF only. Ordering Notes 1) Order one (1) List 61 for each List BF, LF, and NF Distribution Unit. Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206. ♦ Page 12 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List 62: Load Lead Assemblies for GMT Fuses (for 15A positions) Features Home Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 15A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads. Restrictions For use with Lists BF, LF, and NF only. Ordering Notes 1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit. Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988. ♦ List 65: Shelf Side Battery Cables, P/N 540814 Features Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector on the shelf side. Remaining end terminated in lugs for connection to shelf. Restrictions For use with Lists BC, LC, NC, BF, LF, and NF only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. ♦ List 66: Battery Side Battery Cables, P/N 540954 Features Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector on the battery side. Remaining end unterminated for connection to batteries. Restrictions For use with Lists BC, LC, NC, BF, LF, and NF only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. ♦ List 67: Battery Cable, P/N 545709 Features Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Red SB50 Anderson connector on the battery side. Remaining end terminated in lugs for connection to shelf. Restrictions For use with Lists BC, LC, NC, BF, LF, and NF only. For use with P/N 541434, P/N 545534, P/N 545506, or P/N 554631 battery cabinets only. Ordering Notes 1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 2) Order one (1) for each battery cabinet feed required. ♦ Page 13 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home List 68: Shelf Side Battery Cables, P/N 557304 Features Provides two (2) 3’ long, 6 AWG, battery cables terminated in a 2-position Red SB50 Anderson connector on the shelf side. Remaining end terminated in lugs for connection to shelf. Restrictions For use with Lists BC, LC, NC, BF, LF, and NF only. For use with P/N 541434, P/N 545534, P/N 545506, or P/N 554631 battery cabinets only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. ♦ List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 Features ♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor. Ordering Notes 1) Order as required. List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) Features ♦ Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be programmed to monitor ambient temperature or battery temperature. ♦ A temperature probe set as a battery probe can also be designated to be used for the battery charge temperature compensation feature. If the system is equipped with the ACU+ Controller, the battery charge temperature compensation feature can be programmed to use one probe or the average or highest value of all probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. ♦ If the system is equipped with the ACU+ Controller, a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway (BTRM feature). The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf. P/N 04118247 (9 feet long) is shipped loose. Total length: 12 ft. Restrictions A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold. Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247. 2) For a Temperature Probe with a longer cable see List 91. ♦ Page 14 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) 3) Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple probes are required, order (1) SM-TEMP Temperature Concentrator. Home List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) Features ♦ See above for description of Temperature Probes. The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Total length: 33 ft. Restrictions See above for restrictions. Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740. 2) For a Temperature Probe with a shorter cable see List 90. 3) Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple probes are required, order (1) SM-TEMP Temperature Concentrator. ♦ List 93: Battery Tray for 23” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that two battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 23” relay racks only. Maximum number of List 93’s per rack is three (3). A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at bottom of rack and working upward. Ordering Notes 1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions above. 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. Tables A, B, and C list batteries recommended for use with List 93. ♦ Page 15 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables A, B, and C. 5) Battery lugs are provided, as specified from Table D. 6) Specify with or without battery disconnect circuit breakers. Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. 7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from Table E. 8) If ordering List 93 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table E will be installed. Kit numbers are provided for reference only 9) If ordering List 93 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Page 16 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Battery Tray P/N 528496 Emerson Network Power P/N Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) Manufacturer* Model GNB Marathon M12V125FT -- 125 4.90 X 22.00 X 11.15 7U 105 GNB Marathon M12V155FT 112795 155 4.90 X 22.00 X 11.15 7U 119 Northstar NSB110FT -- 110 4.92 X 22.05 X 8.94 7U 91 Northstar NSB170FT -- 167 4.92 X 22.05 X 12.60 8U 131 Deka Unigy I 12AVR-150ET 122018 150 4.90 X 22.00 X 11.75 8U 115 C&D C&D FA 12-150F TEL12-210F FA12150 554579 150 202 4.92 X 21.97 X 12.70 4.90 X 22.00 X 12.80 8U 8U 131 132 Douglas DGS12-150F 125453 150 4.90 X 22.00 X 12.70 8U 137 Douglas DSN12-170F -- 170.8 4.92 X 22.05 X 12.60 8U 130 * See Battery Manufacturer Information located at the end of this document. Table A Battery Tray P/N 540842 Manufacturer* Model Emerson Network Power P/N Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34 Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49 Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27 Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48 Enersys 12TD50F -- 48 4.2 X 10.9 X 8.7 6U 38 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. Table B Battery Tray P/N 557573 Manufacturer* Model Emerson Network Power P/N Enersys 12TD150F -- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 143 4.3 X 21.7 X 11.3 8U 105 * See Battery Manufacturer Information located at the end of this document. Table C Page 17 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Battery Specified Battery Lug Kit Part Number (Kit provides two lugs for one tray.) GNB Marathon M12V125FT GNB Marathon M12V155FT Northstar NSB110FT 528234 Northstar NSB170FT Deka Unigy I 12AVR-150ET C&D FA 12-150F C&D TEL12-210F 528236 Douglas DGS12-150F Douglas DSN12-170F Northstar NSB40FT Northstar NSB60FT 528234 Douglas DGS12-25F Douglas DGS12-50F Enersys 12TD50F Enersys 12TD150F Table D Ampere Rating Part No., Circuit Breaker, 1 Electrical/Mechanical Trip (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 35 256693500 40 256693900 50 256694300 60 256694700 70 256695100 75 256695500 100 256695900 Part No., Left-Side Breaker Mtg. Kit (For Reference Only) Part No., Right-Side Breaker Mtg. Kit (For Reference Only) 528501 528500 1 Provides an alarm during an electrical or manual trip condition. Table E Page 18 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home List 94: Battery Tray for 19” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that three battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 19” relay racks only. Maximum number of List 94’s per rack is three (3). A single List 94 must mount at bottom of rack. Multiple List 94’s must mount starting at bottom of rack and working upward. Ordering Notes 1) Order multiples of List 94 for more than one (1) battery tray. See Restrictions above. 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. Tables F, G, H and I list batteries recommended for use with List 94. 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables F, G, H and I. 5) Battery lugs are provided, as specified from Table J. ♦ 6) Specify with or without battery disconnect circuit breakers. Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. 7) If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from Table K. 8) If ordering List 94 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table K will be installed. Kit numbers are provided for reference only 9) If ordering List 94 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Page 19 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Battery Tray P/N 558047 Manufacturer* Model Emerson Network Power P/N Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) Northstar NSB90FT -- 90 4.25 X 15.59 X 10.04 7U 71 Northstar NSB100FT -- 100 4.25 X 15.59 X 11.03 7U 78 GNB Marathon M12V90FT -- 90 4.13 X 15.55 X 10.63 7U 70 Enersys 12TD100F4 -- 96 4.3 X 15.5 X 11.3 8U 71 Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. Table F Battery Tray P/N 541034 Manufacturer* Model Emerson Network Power P/N GNB Marathon M12V105FT -- 105 4.33 X 20.12 X 9.37 7U 79 Enersys 12TD100F6 -- 97 4.3 X 20.0 X 9.4 7U 73 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) * See Battery Manufacturer Information located at the end of this document. Table G Battery Tray P/N 540841 Manufacturer* Model Emerson Network Power P/N Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34 Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49 Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27 Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48 Enersys 12TD50F -- 48 4.2 X 10.9 X 8.7 6U 38 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. Table H Page 20 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Battery Tray P/N 548213 Rated 8-Hr. Capacit y (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) Manufacturer* Model Emerson Network Power P/N Enersys 12V125F 122009 125 4.10 X 22.10 X 12.40 8U 124 Enersys 12TD150F -- 143 4.3 X 21.7 X 11.3 8U 105 * See Battery Manufacturer Information located at the end of this document. Table I Battery Specified Battery Lug Kit Part Number (Kit provides two lugs for one tray.) Northstar NSB90FT Northstar NSB100FT GNB Marathon M12V90FT GNB Marathon M12V105FT Northstar NSB40FT Northstar NSB60FT 528234 Douglas DGS12-25F Douglas DGS12-50F Enersys 12V125F Enersys 12TD50F Enersys 12TD100F4 Enersys 12TD100F6 Enersys 12TD150F Table J Page 21 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Ampere Rating Part No., Circuit Breaker, 1 Electrical/Mechanical Trip (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 35 256693500 40 256693900 50 256694300 60 256694700 70 256695100 75 256695500 100 256695900 Part No., Left-Side Breaker Mtg. Kit (For Reference Only) Part No., Right-Side Breaker Mtg. Kit (For Reference Only) 528501 528500 1 Provides an alarm during an electrical or manual trip condition. Table K Page 22 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Home ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, or NF) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 , List 67, and/or List 68) as required. List 65, List 67 and List 68 are factory installed. 6) The controller remains powered when the LVBD contactor opens. Specify if you require List BF to be factory configured for the controller not to be powered when the LVBD contactor opens. • Page 23 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load Disconnect (LVLD) Features ♦ Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Home ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, or NF) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68) as required. List 65, List 67 and List 68 are factory installed. • Page 24 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Home ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, or NF) for each List shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68) as required. List 65, List 67 and List 68 are factory installed. • Page 25 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) Features Home Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions (10A maximum). Restrictions For use with Lists 2 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68) as required. List 65, List 67 and List 68 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. 6) The controller remains powered when the LVBD contactor opens. Specify if you require List BC to be factory configured for the controller not to be powered when the LVBD contactor opens. ♦ Page 26 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD) Features Home Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions (10A maximum). Restrictions For use with Lists 2 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68) as required. List 65, List 67 and List 68 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 27 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect Features Home Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions (10A maximum). Restrictions Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BC, LC, or NC) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66, List 67, and/or or List 68) as required. List 65, List 67 and List 68 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 28 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD) Features Home Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions (10A maximum). Restrictions Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. 5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be factory configured for the controller not to be powered when the LVBD contactor opens. ♦ Page 29 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) Features ♦ Home Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with Lists 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 30 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect Features Home Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions (10A maximum). Restrictions For use with Lists 2 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load)” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BA, LA or NA) for each shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 2) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 3) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 31 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions Features ♦ Home 1U-high GMT fuse panel that provides Single Load Distribution (-48V) Provides twenty (20) 0A to 15A GMT fuse load distribution positions. Caution: At +40°C and +65°C ambient, a fuse with a rating of greater than 10 amperes SHALL HAVE an empty mounting position between it and any other fuse. ♦ ♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C ♦ Factory mounted and connected to List 2 or 6 shelf. ♦ If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG loads are disconnected. If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System Controller fuse alarm Restrictions Mounts only immediately above List 2 or 6 shelf. Maximum distribution current is 80A. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 2 or 6 shelf as required. Also order the following as required. 2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section. ♦ Page 32 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home ACCESSORY DESCRIPTIONS Relay Racks Features ♦ The following relay racks are available. Restrictions Customer must mount power/distribution shelf in relay rack. If battery trays are ordered, they are factory mounted in the relay rack. Ordering Notes 1) Order from relay racks listed in Table 1. Part Number Available Mounting Positions (1RU = 1-3/4”) Size Notes 23” Relay Racks 543156 51-3/8” H x 23” W 28RU Welded 543161 6’0” H x 23” W 37RU Welded 543160 7’0” H x 23” W 45RU Seismic (Note 1) 543162 7’0” H x 23” W 45RU Welded 543163 7’6” H x 23” W 48RU Welded 543164 8’0” H x 23” W 51RU Welded 19” Relay Racks 525003 51-3/8” H x 19” W 28RU Welded 534653 6’0" H x 19” W 37RU Seismic (Note 1) 524961 6’0” H x 19” W 37RU Welded 534654 6’6” H x 19” W 41RU Seismic (Note 1) 534651 6’6” H x 19” W 41RU Welded 528183 7’0” H x 19” W 45RU Seismic (Note 1) 524988 7’0” H x 19”W 45RU Welded 524963 7’6” H x 19” W 48RU Welded 534652 8’0" H x 19” W 51RU Welded Note 1: Complies with Bellcore Seismic Zone 4 Requirements Table 1 Available Relay Racks Page 33 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Mounting and Adapter Kits Optional Wall Mount Bracket Kit for Lists 2 and 6, P/N 553203 Features ♦ Allows for vertical wall mounting. ♦ See Physical Size Information for mounting dimensions. Restrictions Customer must supply mounting fasteners for securing the Wall Mount Brackets to the wall. Ordering Notes 1) Order P/N 553203, which consists of two (2) wall brackets (P/N 553058 and 553059) and eight (8) 12-24 x ¾” screws with four (4) ground washers for attaching the brackets to the shelf. Optional 19” to 23” Rack Adapter Kit, P/N 545728 Features ♦ Allows for 23” relay rack mounting Ordering Notes 1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread forming screws. Optional Vertical Flush Mount Kit for List 2, P/N 556851 Features ♦ Allows for vertical flush mounting. ♦ This kit provides rear AC. Restrictions For List 2 only For vertical mount only. Ordering Notes 1) Order P/N 556851 as required. Page 34 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Distribution Devices GMT Load Distribution Fuses Features ♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8) 0-10A GMT load distribution fuses. ♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses. ♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses. Restrictions When used for power distribution, load should not exceed 80% of device rating, except 10A fuses, for which load should not exceed 70% of device rating. The 70% restriction for 10A GMT fuses also applies to 15A GMT fuses. See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA only) and Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order GMT fuses per Table 2. Ampere Rating Part Number Fuse Color 18/100 GMT-A 248610301 -- 1/4 248610200 Violet 1/2 248610300 Red 3/4 248610500 Brown 1-1/3 248610700 White 2 248610800 Orange 3 248610900 Blue 5 248611000 Green 7-1/2 248611300 Black-White 10 248611200 Red-White 15 248611500 Red-Blue Replacement Dummy Fuse 248872600 -- Replacement Safety Fuse Cover 102774 -- Table 2 GMT Fuses Page 35 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Bullet Nose-Type Circuit Breakers (Battery Disconnect and Load Distribution) Features ♦ Home Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit breakers. Each List BA and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit breakers and up to two (2) bullet nose-type load distribution circuit breakers. Restrictions See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (Circuit Breakers) and Input Battery Wiring (to Battery Disconnect Circuit Breakers) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order circuit breakers per Table 3. ♦ Part Number Ampere Rating Number of Poles (and Mounting Positions) Electrical Trip (White Handle) Electrical/ 2 Mechanical Trip (Black Handle) 1 1 102272 101596 3 1 102273 101597 5 1 102274 101598 10 1 102275 101599 15 1 102276 101600 20 1 102277 101601 25 1 102278 101602 30 1 102279 101603 35 1 102280 101604 40 1 102281 101605 45 1 121998 121997 50 1 102282 101606 60 1 102283 101607 70 1 102284 101608 75 1 102285 101609 80 1 121996 121995 90 1 138887 138888 100 1 102286 101610 1 See Table 8 for recommended wire sizes and lugs. Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical trip condition only. 2 Provides an alarm during an electrical or manual trip condition. Note: Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers. Table 3 Bullet Nose-Type Circuit Breakers Page 36 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Bulk Output Bus bar, P/N 535015 Features ♦ Provides replacement for circuit breakers shown in Table 3. ♦ Includes two (2) bullet terminals. ♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) load bus bars. Each List BA and NA Distribution Unit holds up to two (2) load bus bars and up to two (2) battery bus bars. Restrictions Bulk Output Bus bars are ordered separately. Maximum number of Bulk Output Bus bars per system is four (4). Ordering Notes 1) Order by P/N 535015 as required. ♦ AC Input Cables and Line Cords AC Input Cable Assembly, P/N 535232 Features ♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and the remaining end un-terminated. Restrictions Rated for 30A. Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6 ordered. AC Input Cable Assembly, P/N 553202 Features ♦ Provides one (1) 12’ long, 8 AWG, AC Input Cable Assembly; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and the remaining end un-terminated. Restrictions Rated for 30A. Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6 ordered. Page 37 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home AC Input Line Cord, P/N 540946, 208/240VAC Features ♦ Provides one (1) 14’ long, 8/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6 ordered. AC Input Line Cord, P/N 545616, 208/240VAC Features ♦ Provides one (1) 6’ long, 8/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6 ordered. AC Input Line Cord, P/N 545252, 120VAC Features ♦ Provides one (1) 14’ long, 8/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). Each List 2 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 and 6 ordered. Page 38 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home AC Input Line Cord, P/N 545478, 120VAC Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. AC Input Line Cord, P/N 545479, 120VAC Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-15P twist-lock plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. AC Input Line Cord, P/N 545480, 208/240VAC Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-15P twist-lock plug. Restrictions For 208/240 VAC only (rated for 15A at 208/240VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. Page 39 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home AC Input Line Cord, P/N 545481, 120VAC Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-20P twist-lock plug. Restrictions For 120 VAC only (rated for 20A at 120VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 6 ordered. AC Input Line Cord, P/N 545482, 208/240VAC Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 6-15P plug. Restrictions For 208/240 VAC only (rated for 15A at 208/240VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. AC Input Line Cord, P/N 545553, 208/240VAC Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-20P twist-lock plug. Restrictions For 208/240 VAC only (rated for 20A at 208/240VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. Page 40 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home AC Input Line Cord, P/N 547525, 120VAC Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. AC Input Line Cord, P/N 548457, 120VAC Features ♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P twist-lock plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). Each List 2 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order two (2) AC Input Cable Assemblies/Line Cords as required (P/N 535232, 553202, 540946, 545616, 545252, 545478, 545479, 545480, 545481, 545482, 545553, 547525, or 548457) for each List 2 ordered. AP6C57EA/EB Ring and Distribution Module Features ♦ When used with List 6, this module is designed to supply a filtered and regulated –48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems (such as SLC-96 or SLC Series-5) requiring up to 45 A of load capacity. ♦ Designed to mount in a 23” relay rack, the module is one rack unit high, with 5” front projection. ♦ Includes two (2) 50VA ringers with automatic transfer capability (N+1 redundancy). ♦ Provides 35 DC distribution fuse positions, configured in five groups of seven, feeding five channel banks. Includes 35 dummy fuses. ♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution fuses are included with each cable assembly ordered. ♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic pair, with surge protection. ♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete specifications. Page 41 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Restrictions Cannot be used with Distribution units List BF, LF, or NF. Ordering Notes 1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626). 2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order AP6C57EB (A7000796). 3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable assemblies can be mixed. ORDERING CODE DESCRIPTION P7000858 Cable assy for one SLC96 channel bank (8 ft.) P7001139 Cable assy for one SLC96 channel bank (20 ft.) P7000859 Cable assy for one SLC5 channel bank (8 ft.) P7001136 Cable assy for one SLC5 channel bank (20 ft.) P7000937* Cable assy for one channel bank, generic applications (8 ft.) *Note: Each channel bank position on the panel has a maximum capacity of 11A. 4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect between a power shelf and the DC input terminals of one (1) Ring & Distribution Module. 5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table. ORDERING CODE DESCRIPTION 547646 Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) 547647 Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) 6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the following table. ORDERING CODE DESCRIPTION A0885525 1.33A Alarm SAN-O Fuse A0885530 3A Alarm SAN-O Fuse A0885531 5A Alarm SAN-O Fuse A0885532 10A Alarm SAN-O Fuse A7000627 (AP8C55AA) 50VA Ring Generator Page 42 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) NetSure™ 211BC Battery Cabinet (Spec. No. 541434) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Order Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 541434 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Hawker SBS 15 139091 14 12.50 Fiamm 12SLA12 139092 12 12.35 EaglePicher HE-12V7.7FR 139094 6.9 5.94 EaglePicher HE-12V12.7FR 139093 11.6* 9.68 Enersys NP18-12FR 139774 16 * 13.60 * 10Hr rate 3) When ordering 139774 batteries, also order 545427 Battery Connection kit. 4) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 43 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 545534) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545534 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys SBS B10 140553 38 28.20 C&D / Dynasty TEL12-30 140455 30.5 26.70 3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 44 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 545506) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545506 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys SBS B10 140553 38 28.20 Enersys SBS 40 140581 38 28.00 C&D/ Dynasty TEL12-30 140455 30.5 26.70 C&D/ Dynasty TEL12-45 140454 46 26.70 3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 45 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 554631) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 554631as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery GNB M12V40F 241173815 40 39.00 Note: When wall mounted, a battery cabinet frame grounding landing point adapter, P/N 556872, is provided. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 46 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Battery Disconnect Unit Features ♦ Battery Disconnect Unit with mounting tabs. ♦ Two 1/4-20 studs w/ hardware provided for installation of single hole battery lugs. ♦ One (10’ long) alarm lead provided. Restrictions Circuit breakers are ordered separately. Maximum number of Battery Disconnect Units per system is three (3). Ordering Notes 1) Order by P/N 535282 as required. 2) Order a circuit breaker for each Battery Disconnect Unit from Table 4. 3) Also order two (2) P/N 245350815 lugs for each battery disconnect circuit breaker ordered. 4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery Disconnect Units are to be used (daisy-chains the alarm terminal of up to three [3] Battery Disconnect Units). (Section of alarm lead between Battery Disconnect Units is 30”, section of alarm lead between Battery Disconnect Unit and system’s alarm terminal is 84”.) Yellow Jumper/Alarm Lead (P/N 524384) (for use when more than one Battery Disconnect Units are ordered) Ampere Rating P/N Electrical/Mechanical 1 Trip (Black Handle) Ampere Rating P/N Electrical/Mechanical 1 Trip (Black Handle) 1 256690300 35 256693500 3 256690700 40 256693900 5 256691100 50 256694300 10 256691500 60 256694700 15 256691900 70 256695100 20 256692300 75 256695500 25 256692700 100 256695900 30 256693100 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. Table 4 Battery Disconnect Unit Circuit Breakers Page 47 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) SM TEMP Temperature Concentrator (P/N 547490) Home Features ♦ Allows for multiple temperature probes to be used for temperature compensation. Compensation can be based on highest probe temperature or average probe temperature. ♦ Provides (8) temperature probe inputs per SM TEMP. ♦ Can be cascaded up to (8) SM TEMP modules, connecting up to 64 temperature probes. ♦ Provides analog output for all controllers. Restrictions Concentrator needs to plug into analog temp input on IB2 board. Ordering Notes 1) Order P/N 547490. 2) Order up to (8) 3-meter (P/N 547749) or 10-meter (P/N 547750) temperature probes for each concentrator. SM Module RS-485 Interface Cable P/N 547674 Features ♦ Provides 4’ cable for connecting SM supervisory modules to the system RS-485 interface connector. ♦ For interface with SM AC, SM BAT, SM BRC, or SM IO modules. Restrictions One (1) RS-485 connector is available in the system. Ordering Notes 1) Order P/N 547674 as required. Alarm Cables Features Two sets of Alarm Cables are available. One set for the Digital Inputs and another set for the Relay Outputs. One half of the Relay Outputs Alarm Cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Both halves of the Digital Inputs Alarm Cable must be ordered separately. When ordered, one half of the Digital Inputs Alarm Cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end. Ordering Notes 1) For the Relay Outputs Alarm Cable, P/N 541308 (3 ft.) is provided and factory connected in the shelf. A mating cable, P/N 541309 (10 ft.) or P/N 545644 (50 ft.), must be ordered separately. 2) For the Digital Inputs Cable, order P/N 541310 (shelf side, 3 ft.) and P/N 541311 (customer side, 10 ft.). Note: A custom digital input cable (P/N 545591) and internal wiring kit (P/N 545594) is available. This kit is factory installed only. ♦ Page 48 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Optional Bullet-Nose-type 6-Position GMT Fuse Board (Part No. 545332) Home Features ♦ Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit. ♦ Provides six (6) 0A to 15A GMT fuse load distribution positions. ♦ Screw clamp type load and load return terminals provided. Includes six (6) dummy fuses equipped with safety fuse covers. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA. Terminal block wire size capacity: 24 to 14 AWG. Requires two (2) bullet device mounting positions. Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position. Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Factory installed only. Ordering Notes 1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required. 2) Order GMT fuses as required per Table 2. ♦ Page 49 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Replacement Components Ordering Notes 1) Refer to Table 6. Item Part Number 2000W Rectifier Module 1R482000 2000W High Efficiency Rectifier Module 1R482000e Rectifier Module Fan SCU+ (Standard Control Unit Plus) 32010096 for 1R482000 32010106 for 1R482000e 1M521BNA* * Also specify the appropriate SCU+ configuration file. Refer to the configuration file label on your existing SCU+ Controller. ACU+ Controller Module 1M820BNA* * Also specify the appropriate ACU+ configuration file. Refer to the configuration file label on your existing ACU+ Controller. Temperature Probe Order per List 90 (9 ft. long) or List 91 (30 Ft. long) (or if only one piece of the two piece probe is needed, see the List 90 or 91 description for part numbers) Table 5 Replacement Part Numbers Page 50 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Wiring Notes Refer also to the next section, Wiring Illustrations. AC Input Branch Circuit Protection and Wiring Features ♦ Each shelf contains side mounted plug-in Molex AC input connectors. Rear AC access if P/N 556851 ordered. AC input branch circuits are connected via AC Input Cable Assemblies/Line Cords ordered with the system. Restrictions For correct AC input wire size, order the appropriate Input Cable Assembly/Line Cord for each AC input branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORIES DESRIPTIONS section of this document. Each shelf requires two AC input branch circuits. In the 19” shelf, each feeds one rectifier. Recommended branch circuit protection is 15 amperes. In the 23” shelf, one feeds one rectifier and the other feeds two rectifiers. Recommended branch circuit protection is 30 amperes. Branch circuit protective devices should be of the time-delay or high inrush type. ♦ External Alarm and Monitoring Wiring Features Alarm output and monitoring input leads are connected to screw-type terminal blocks located on the Signal Interface Assembly located inside the shelf. These leads enter the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. A wireway is provided to route the wires to the Signal Interface Assembly. Restrictions Terminal block wire size capacity is 16 to 26 AWG. Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft. 18-20 AWG for Loop Lengths Over 200 ft. ♦ Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF) Features Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of fuse amperage sizes, and that two different types of receptacles are provided. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. ♦ Page 51 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Ordering Notes 1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111 [reel]. 2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco 350537-3 [reel]. Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA) Features Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Ordering Notes 1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111 [reel]. ♦ Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) Features Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse Module. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Terminal block wire size capacity is 24 to 14 AWG. ♦ Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) Features Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. ♦ Page 52 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows; • 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC, LC, and NC). Use 6 AWG for CO Ground. • 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use 6 AWG for CO Ground. For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination. Ordering Notes 1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 7. 2) For other available lugs, refer to drawings 031110100 through 031110300. Load Distribution Wiring (GMT Fuses) (List KG) Features Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front of the assembly. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Terminal block wire size capacity is 26 to 14 AWG. ♦ CO Ground Wiring Features ♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring. Restrictions Recommended CO ground wire size is 6 AWG. Recommended lug is 245346500 (2-hole, 10-32 clearance holes, and 5/8” centers). Page 53 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Circuit Breaker Amperage 1, 3, 5, 10A 15A 20A 25A 30A 35A 40A 45A 50A 60A 70A 75A 80A 90A 100A 2-hole Recm 90°C Wire Size 14 AWG 37 (3, 4, 5) 24 (3, 4) --------- 12 AWG 58 10 AWG 8 AWG 6 AWG (2) Loop Length (feet) (3, 4, 5) 93 (3, 4, 5) 62 (3, 4, 5) 46 (3, 4,) 37 (3, 4) 31 ------ 39 (3, 4) 29 -------- (3, 4, 5) (3, 4, 5) 148 (3, 4, 5) 236 (3, 4, 5) 99 (3, 4, 5) 74 (3, 4, 5) 59 (3, 4, 5) 49 (3, 4) 42 (3, 4) 37 (3, 4) 33 (3) 29 -- 1 2 3 4 5 6 4 AWG 2 AWG (3, 4, 5) -- -- (3, 4, 5) ----(3, 4) 107 (3, 4) 94 (3, 4) 83 (3, 4) 75 (3, 4) 62 (3, 4) 53 (3, 4) 50 (3, 4) 47 (3) 41 -- --------- 99 (3, 4) 85 (3, 4) 79 (3, 4) 74 (3, 4) 66 (3, 4) 59 245346800 245346900 157 (3, 4, 5) 118 (3, 4, 5) 94 (3, 4, 5) 78 (3, 4, 5) 67 (3, 4, 5) 59 (3, 4) 52 (3, 4,) 47 (3, 4) 39 (6) 245390100 (1) Recommended Crimp Lug 245390100 245390100 245346600 245346500 (3, 4) Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and 65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads. Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature. Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature. Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature. Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping information. Table 6 Recommended Battery and Load Distribution Wire Size and Lug Selection (Bullet Nose-Type Circuit Breaker) Page 54 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Input Battery Wiring (to battery bus bars) (Lists BF, LF, NF, BC, LC, and NC) Features Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the top of the shelf. Restrictions All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. Maximum size of wire to be connected to a single lug position is 2 AWG. Maximum lug width, 0.61 inches. Ordering Notes 1) Battery wire size varies depending on load, therefore no specific information is provided for wire size. When making connections, observe correct polarity. Refer to Table 8 for recommended wire sizes and lugs at rated maximum output capacity. 19” Version: 72A, maximum. 23” Version: 100A, maximum. 2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables. List 68 provides 6 AWG shelf side battery cables. 3) For other available lugs, refer to drawings 031110100 through 031110300. ♦ Maximum Loop Loop Ambient Recm 90°C Current Length (Ft) Length (Ft) Operating Wire Size (1) (2) (2) (1) (Amps) Temperature 1.0 Volt Drop 0.25 Volt Drop (AWG) 72A 65°C 100A 40°C Recommended (3) Crimp Lug 53.7 13.4 4 245346800 85.4 21.4 2 245346900 56.9 14.2 2 245346900 1 Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire rated at 90°C conductor temperature operating in ambient temperature of 40°C and 65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes 2 Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or less, at rated full load output current of the system for the loop lengths shown in this column. Loop length is the sum of the lengths of the positive and negative leads. 3 Two-hole lug, 1/4-20 bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information. Table 7 Recommended Battery Wire Size and Lug Selection Page 55 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA and NA) Features Home Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. Maximum wire size is 6 AWG when all four (4) circuit breaker positions are used. 4 AWG or 2 AWG can be used, but the number of breaker positions will be reduced as follows; • 4 AWG: 3 breakers max. (2 load/1 battery or 1 load/2 battery on lists BA, LA, and NA; 3 load on lists BC, LC, and NC). Use 6 AWG for CO Ground. • 2 AWG: 2 breakers max. (1 load/1 battery on lists BA, LA, and NA; 2 load on lists BC, LC, and NC). Use 6 AWG for CO Ground. For 4 AWG and 2 AWG wire, install a customer supplied flat washer between the lug and the nut supplied on the termination. Ordering Notes 1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 8. 2) For other available lugs, refer to drawings 031110100 through 031110300. ♦ Page 56 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Wiring Illustrations AC Input Wiring (List 6 shown) Rectifiers are numbered left to right as viewed from the front. Front AC Input connections are made using the supplied AC Input Cable Assemblies/ Line Cords connected here. Front View AC Input Cable Assembly L2-N Ground L1 AC Input Line Cord Blue* White* Green/Yellow* Green* Brown* Black* * Color of AC Input Cable Assembly/Line Cord lead. Nominal 120/208/240V AC Input for Rectifier Module #1 (In the 23” Shelf, this input also connects to Rectifier Module #3.) Nominal 120/208/240V AC Input for Rectifier Module #2 * AC Input Cable Assembly / Line Cords Part Number Customer End 535232 553202 545252 540946 545616 545478 545479 545480 545481 545482 545553 547525 548457 unterminated unterminated L5-30P L6-30P L6-30P 5-15P L5-15P L6-15P L5-20P 6-15P L6-20P L5-30P 5-15P (List 2, 6) (List 2, 6) (List 2, 6) (List 2, 6) (List 2, 6) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) Page 57 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home AC Input Wiring for List 2 with Rear AC Input Connectors Rear View AC Input connections are made using the supplied AC Input Cable Assemblies/ Line Cords connected here. Nominal 120/208/240V AC Input for Rectifier Module #1 Nominal 120/208/240V AC Input for Rectifier Module #2 AC Input Cable Assembly Brown* Green/Yellow* Blue* * AC Input Cable Assembly / Line Cords Part Number 535232 553202 545252 540946 545616 545478 545479 545480 545481 545482 545553 547525 548457 Customer End Use In unterminated unterminated L5-30P L6-30P L6-30P 5-15P L5-15P L6-15P L5-20P 6-15P L6-20P L5-30P 5-15P (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) (List 2) AC Input Line Cord Black* L1 Green* Ground White* L2-N * Color of AC Input Cable Assembly/Line Cord lead. Page 58 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Alarm and Monitoring Wiring (List 6 shown) Front IB2 Board RS-485 Connection for SM AC, SM BAT, SM BRC, or SM IO Supervisory Modules. See module data sheets. (Functional with ACU+ only.) IB2 Customer Interface Board Relay No. J9 Relay Output Term. Blocks J8 J7 J6 7 5 3 Digital Input Term. Blocks J5 J4 J3 8 7 6 5 4 3 2 1 1* NO C NC NO C NC NO C NC NO C NC 5 3 1 5 3 1 5 3 1 5 3 1 NO C NC NO C NC NO C NC NO C NC Relay No. 6 4 8 2 6 4 6 2 6 4 4 2 6 4 2 2 5 3 6 1 4 5 2 3 6 1 4 5 2 3 6 Input No. (–) 1 4 2 8 7 6 5 4 3 2 1 Input No. (+) J12 J11 Temp. Probe #2 or SM TEMP Module Temp. Probe #1 or SM TEMP Module J2 J1 SW1 Switch sections must be set to this position to interface with SCU+/ACU+ controller. The relay assigned by the Controller to be the”Major Summary” (SCU+) or “Critical Summary” (ACU+) alarm (relay 1 * by default) will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C and NO terminals, and closing the contacts between the C and NC terminals. The remaining seven (7) alarm relays energize during an alarm condition, closing the contacts between the C and NO terminals, and opening the contacts between the C and NC terminals. A factory-connected jumper supplies +BAT (Battery Return) to the positive side of Digital Input # 2. Page 59 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Interface Connections (continuation) Yellow Alarm Lead (P/N 535294) (factory wired to circuit breaker alarm terminal) Alarm Wiring to a Single External Battery Disconnect Unit Torque to 84 in-lbs using supplied hardware Procedure 1. Connect YELLOW lead exiting top of Battery Disconnect Unit per table below. Remove quick connect terminal first. The YELLOW lead is factory connected to circuit breaker “C (Common)” alarm terminal in the Battery Disconnect Unit. 2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 3. Connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker “NC (Normally Closed)” alarm terminal. To To Power System Battery Connect to shelf per table below. Remove quick connect terminal first. EXTERNAL BATTERY DISCONNECT UNIT (Side cover removed in illustration to show wiring details.) 541311 Alarm Cable on shelf NO YES BREAKER ALARM CONNECTION CONNECT YELLOW WIRE TO: Pin 3 of J3 on Customer Interface BD (negative side of Digital Input 2) O-R Lead of 541311 Splice and heat shrink tubing included with 541311 Page 60 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Interface Connections (continuation) Yellow Jumper/Alarm Lead (P/N 524384) (Ordered separately and supplied loose. Must be wired by the customer to each circuit breaker “C (Common)” alarm terminal) Yellow Alarm Lead (P/N 535294) (factory wired to circuit breaker alarm terminal) * No terminal on 524384 jumper Connect to shelf per table below. see previous page REMOVE COMPLETELY FROM ALL BATTERY DISCONNECT UNITS AND DISCARD. see previous page see previous page 1st EXTERNAL BATTERY DISCONNECT UNIT (Side cover removed in illustration to show wiring details.) 2nd EXTERNAL BATTERY DISCONNECT UNIT Alarm Wiring to (2) to (3) External Battery Disconnect Units 3rd EXTERNAL BATTERY DISCONNECT UNIT Procedure 1. Completely remove YELLOW lead exiting top of ALL Battery Disconnect Units and discard. 2. Connect separately ordered YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals in ALL Battery Disconnect Units. Connect remaining end per table below. 541311 Alarm Cable on shelf NO YES 3. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 4. In ALL Battery Disconnect Units, connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker “NC (Normally Closed)” alarm terminal. BREAKER ALARM CONNECTION CONNECT YELLOW WIRE TO: Pin 3 of J3 on Customer Interface BD (negative side of Digital Input 2) O-R Lead of 541311 Splice and heat shrink tubing included with 541311 Page 61 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Interface Connections (continuation) Yellow Jumper/Alarm Lead (P/N 524384) (Ordered separately and supplied loose. Must be wired by the customer to each circuit breaker “C (Common)” alarm terminal) * No terminal on 524384 jumper Connect to shelf per table below. see previous page see previous page see previous page 1st BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (Side cover removed in illustration to show wiring details.) 2nd BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (if furnished) Alarm Wiring to Battery Disconnect Circuit Breakers when (1) to (3) Battery Trays are Used 3rd BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (if furnished) Procedure 1. Connect kit-supplied YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals on ALL Battery Disconnect Circuit Breakers. Connect remaining per table below. 2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 541311 Alarm Cable on shelf 3. On ALL Battery Disconnect circuit breakers, there should be a factory connected Jumper connected from the bottom terminal on the circuit breaker to the circuit breaker “NC (Normally Closed)” alarm terminal. BREAKER ALARM CONNECTION CONNECT YELLOW WIRE TO: NO Pin 3 of J3 on Customer Interface BD (negative side of Digital Input 2) YES O-R Lead of 541311 Splice and heat shrink tubing included with 541311 Page 62 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home External Interface Connections (continuation) Yellow Jumper/Alarm Lead (P/O Cabinet) Orange wire on 541434 not used Connect to shelf per table below. alarm wire alarm wire 1st BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER alarm wire 2nd BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER 3rd BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER Alarm Wiring to Battery Cabinets Procedure 1. Remove quick connect terminal from YELLOW battery cabinet alarm lead and wire per table below. 541311 Alarm Cable on shelf BREAKER ALARM CONNECTION CONNECT YELLOW WIRE TO: NO Pin 3 of J3 on Customer Interface BD (negative side of Digital Input 2) YES O-R Lead of 541311 Splice and heat shrink tubing included with 541311 Page 63 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF in List 6, as shown) Front Load Distribution Leads Enter Here GMT Fuse Positions (Max. 15A) GMT Fuse Load Distribution Leads Connect Here Mating Connectors and 12 ’ Leads provided with List 62. -48V on Left (Black Lead), Return on Right (White Lead) GMT Fuse Positions (Max. 10A) GMT Fuse Load Distribution Leads Connect Here Mating Connectors and 12 ’ Leads provided with List 61. -48V on Left (Black Lead), Return on Right (White Lead) Page 64 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in List 6, as shown) Home GMT Fuse Load Distribution Leads Connect Here GMT Fuses and Safety Covers Max. 10A Front Mating Connectors and 12 ’ Leads provided with List 60 -48V on Left (Black Lead), Return on Right (White Lead) as viewed from side with door closed Page 65 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) -48V Distribution Leads Home Load Return Leads Page 66 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BC, LC and NC, List 6 shown) Home Front Load Distribution Circuit Breakers Circuit Breaker Load Distribution and CO Ground Leads Enter Here Front Portion shelf removed in illustration for clarity. Leads are brought into side of shelf, and tools to secure lugs from front of shelf. -48V Load Distribution Leads Load Return Leads CO Ground Lead 10-32 studs (w/ hardware) on 5/8” centers for installation of customer provided two-hole lugs. Page 67 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA and NA, List 6 shown) Home Front Load Distribution Circuit Breakers CO Ground, Circuit Breaker Load Distribution, and Circuit Breaker Battery Leads Enter Here Battery Disconnect Circuit Breakers Front Portion of shelf removed in illustration for clarity. Leads are brought into side of shelf, and tools to secure lugs from front of shelf. -48V Load Distribution Leads -48V Battery Leads OBSERVE PROPER POLARITY WHEN MAKING BATTERY CONNECTIONS Battery Return Leads Load Return Leads CO Ground Lead 10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs. Page 68 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home “B” Side Loads #6 - #10 Connections are made to screw compression terminal blocks. Wire size range is 26 to 14 AWG. “B” Side Returns Inputs for Side “A” and Side “B” are strapped in this system. “B” Side Loads #1 - #5 “A” Side Loads #6 - #10 “A” Side Returns “A” Side Loads #1 - #5 Load Distribution Wiring (GMT Fuses) (List KG) Page 69 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC in List 6, as shown) List NC Distribution Unit shown. List BC, LC, NC, BF, LF and NF similar. Front List 65 provides 3’ long, 2AWG battery cables terminated on one end with lugs to connect to the input battery landings and on the other end with an Anderson connector. List 66 provides 12’ long, 2AWG battery cables terminated on one end an Anderson connector and left unterminated at the remaining end for connection of battery lugs. Distribution Unit Battery, Battery Return and CO Leads Enter Here List BC, LC, and NC Distribution Unit Battery: 1/4-20 studs (w/ hardware) on 5/8” centers for installation on customer provided two-hole lugs. CO Ground: 10-32 studs (w/ hardware) on 5/8” centers for installation on customer provided two-hole lugs. CO Ground Lead Right Side Battery Return Leads -48 Battery Leads List BF, LF, and NF Distribution Unit OBSERVE PROPER POLARITY WHEN MAKING BATTERY CONNECTIONS CO Ground Lead Right Side Battery Return Leads -48 Battery Leads Page 70 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) Home SPECIFICATIONS Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R482000e) supplied with your Power System. For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B) supplied with your Power System. For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (Cdrawing) supplied with your Power System. 1. SYSTEM 1.1 Environmental Ratings 1.1.1 Lists 2 and 6 Operating Ambient Temperature Range (Specification Compliant): (A) -40°C (-40°F) to +65°C (+149°F) with derating output. (B) -40°C (-40°F) to +40°C (+104°F) with full power performance. 1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +80°C (+176°F). 1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of 0% to 95%, non-condensing. 1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m). 1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-combustible surface. This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally controlled electronic equipment enclosure). This product is intended to be connected to the common bonding network in a Network Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure). Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4” multiple drilling). Mounting angles are positioned for a 5-inch front projection mounting only. 1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient Temperature Range stated above. 1.2 Compliance Information 1.2.1 Surge Protection: Refer to Paragraphs 2.3.5. Note: This level of protection is a widely used standard for telecommunications power equipment. As with all such equipment, it is the end user's responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes/categories stated for the equipment. 1.2.2 Safety Compliance: (A) This unit meets the requirements of UL 60950, Standard for Information Technology Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data Processing, or Information Processing Equipment. (B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified by UL ("c UR") as a Component Type Power Supply. Page 71 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 1.2.3 System Application Guide Spec. No. 582136700 (Model 502NGFB) EMC and Safety: (A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and Immunity requirements as specified in GR-1089-Core Issue 4. Home EMC Emissions EN 55022: 1998 CFR 47 – Part 15 GR-1089 Issue 4 Test Level Conducted Class B Radiated Class B Immunity GR-1089 Issue 4 EN 61000-4-2 Electrostatic Discharge 8kV / 15kV EN 61000-4-4 Electric Fast Transients 0.25kV / 0.5kV Radiated Immunity 8.5V/m Conducted Immunity 89dBuA Surge IEEE C62.41 2kV / 6kV SAFETY EN 60950-1: 2001 1.2.4 Safety of Information Technology Equipment, including Electrical Business Equipment NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports. For NETSURE™ 502NGFB to remain compliant during a fan failure condition, the backup battery connection must be utilized to provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50% output power. If no backup battery connection is used, the system must operate with a redundant module installed. 1.3 Standard Features 1.3.1 AC Input Connections: AC input leads are connected to Molex connectors located on the side of the shelf. Each shelf requires two (2) AC input branch circuits. In the 19” shelf, each feeds one rectifier. In the 23” shelf, one feeds one rectifier and the other feeds two rectifiers. 1.3.2 Battery Connections: Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. 1.3.3 Load Connections: Load distribution (circuit breakers, if furnished) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. 1.3.4 Alarm and Monitoring Connections: Alarm output and monitoring input leads are connected to screw-type terminal blocks located on the Signal Interface Assembly located inside the shelf. These leads enter the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf Page 72 of 82 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136700 Issue AV, February 21, 2014 System Application Guide Spec. No. 582136700 (Model 502NGFB) 1.3.5 1.3.6 Dimensions (A)