SAG582136600 System Application Guide Spec. No. 582136600 (Model 211NGFB) Issue W, January 12, 2015 Home SYSTEM OVERVIEW Description: The NetSure™ 211NGFB DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. This power system consists of the following mounted in a 1RU or 2RU high by 19” or 23” wide shelf. • 500W or 1000W Rectifier Modules The 1RU high by 19” wide shelf accommodates two (2) 500W or 1000W Rectifier Modules. The 1RU high by 23” wide shelf accommodates three (3) 500W or 1000W Rectifier Modules. The 2RU high by 19” wide shelf accommodates four (4) 500W or 1000W Rectifier Modules. The 2RU high by 23” wide shelf accommodates six (6) 500W or 1000W Rectifier Modules. The Rectifier Modules provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules are designed to provide constant power. They are designed with the latest patented switch-mode technology using DSP (Digital Signal Processing) functionality for efficient operation. This means that, within the normal operating ambient temperature range and input voltage range, the maximum available output power is a constant 500W or 1000W. Within these ranges, the Rectifier Modules operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. If ambient temperature rises above or input voltage falls below acceptable values, Rectifier Modules continue to operate but at derated output power levels. 1) Constant Voltage Mode: For any initial output voltage setting from 48 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 500W or 1000W. 2) Constant Power Mode: As load increases above approximately 500W or 1000W (non-adjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier List 1 (List 2 similar) Modules operate in the Constant Power Mode unless load continues to increase to the point where the current limit setting is reached. 3) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. List 5 (List 6 similar) Page 1 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 • • System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Controller The controller controls the operation of the rectifier modules. The controller also provides power system control, metering, monitoring, and alarm functions. NCU (NetSure Control Unit): The controller provides power system control (including optional low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a charge control function), metering functions, monitoring functions, local/remote alarm functions, and connections for binary inputs and programmable relay outputs. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe(s). Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains a color TFT display and keypad for local access. The controller provides an Ethernet port and comes with comprehensive webpages for remote access. The controller has SNMP V3 capability for remote system management. The controller supports software upgrade via its USB port. Refer to the NCU Controller Instructions (UM1M830BNA) for more information. ACU+ (Advanced Control Unit Plus): The controller provides power system control (including optional low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) control), rectifier control (including a charge control function), metering functions, monitoring functions, and local/remote alarm functions. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe(s). Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains an LCD display and keypad for local access. The controller provides an Ethernet port and comes with comprehensive webpages for remote access. The controller has SNMP capability for remote system management. The controller supports software upgrade via its USB port. Refer to the ACU+ Controller Instructions (UM1M820BNA) for more information. SCU+ (Standard Control Unit Plus): The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms. The SCU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via a Temperature Concentrator (SM TEMP), and ambient temperature monitoring if equipped with a second temperature probe. The SCU+ also provides Ethernet connection and SNMP capability. Distribution Unit Various Distribution Unit options are available, as described in this document. The Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) contactor. Page 2 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home General Specifications See detailed specifications starting on page 92. Family: Spec. No.: Model: Input Voltage Output Voltage: Output Capacity: Rectifier Module: NetSure™ 582136600 211NGFB Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an operating range of 100 to 250 volts. Acceptable input frequency range is 45 to 65 Hz. -48 Volts DC 500W @ Vout >48Vdc (10.5A @ -48Vdc) or 1000W @ Vout >48Vdc (20.9A @ -48Vdc) System: See the following table. System DC Output Capability 208/240VAC Input 120VAC Input +40°C (+104°F) +65°C (+149°F) +40°C (+104°F) +65°C (+149°F) 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 58213660001 20.8A 41.6A 12.6A 25A 20.8A 27.4A 12.6A 16.4A 58213660002 31.2A 62.4A 18.9A 37.5A 31.2A 41.1A 18.9A 24.6A 58213660005 41.6A 83.2A 25.2A 50A 41.6A 54.8A 25.2A 32.8A 58213660006 62.4A 124.8A 37.8A 75A 62.4A 82.2A 37.8A 49.2A Spec. No. Agency Approval: Framework Type: Mounting Width: Mounting Depth: Mounting Height: Access: Control: Color: Environment: UL 60950 Recognized, CAN/CSA 22.2 Relay Rack Mounted 19” or 23”, nominal 12” 1.75” (1RU) or 3.5” (2RU) Front for Installation, Operation, and Maintenance Microprocessor Front Panels are Gray; Shelf is Galvaneal -40°C (-40°F) to +65°C (+149°F), with deratings (see SPECIFICATIONS section) Page 3 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) TABLE OF CONTENTS SYSTEM OVERVIEW................................................................................................................................................. 1 MAIN COMPONENTS ILLUSTRATIONS .................................................................................................................. 8 58213660001......................................................................................................................................................... 8 58213660002......................................................................................................................................................... 8 58213660001 with P/N 555260 ............................................................................................................................ 9 58213660001 with P/N 556828 Kit ...................................................................................................................... 9 58213660002 with P/N 555261 .......................................................................................................................... 10 58213660005....................................................................................................................................................... 11 58213660006....................................................................................................................................................... 11 Other ................................................................................................................................................................... 12 LIST DESCRIPTIONS .............................................................................................................................................. 14 List Numbers...................................................................................................................................................... 14 List 1: 1RU High by 19” Wide Shelf............................................................................................................... 14 List 2: 1RU High by 23” Wide Shelf............................................................................................................... 15 List 5: 2RU High by 19” Wide Shelf............................................................................................................... 16 List 6: 2RU High by 23” Wide Shelf............................................................................................................... 17 List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ................................... 18 List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ................................. 18 List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions ................................... 18 List 65: Shelf Side Battery Cables, P/N 540814 ........................................................................................... 18 List 66: Battery Side Battery Cables, P/N 540954 ........................................................................................ 19 List 67: Battery Cable, P/N 545709 ................................................................................................................ 19 List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493 .................................................................................................................................................... 19 List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery Strings, P/N 535124 ....................................................................................................................................... 20 List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 555050 .................................................................................................................................................... 20 List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ........................................................................ 20 List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) ......................................................................................................................................... 21 List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) ....................................................................................................................................... 21 List 93: Battery Tray for 23” Relay Rack ....................................................................................................... 22 List 94: Battery Tray for 19” Relay Rack ....................................................................................................... 25 Distribution Unit ................................................................................................................................................ 29 List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) ......................................................................................................................................... 29 List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load Disconnect (LVLD) ......................................................................................................................................... 30 List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect ...................................................................................................................................................... 31 List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) ..................................................... 32 List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................... 33 List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect ............................................................................ 34 List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD) ......................................................................................................................................... 35 Page 4 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) ......................................................................................................................................... 36 List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect ...................................................................................................................................................... 37 List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) ......................................................................................................................................... 38 List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect ...................................................................................................................................................... 39 List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ............................................... 40 ACCESSORY DESCRIPTIONS ............................................................................................................................... 41 Relay Racks ....................................................................................................................................................... 41 Rectifier .............................................................................................................................................................. 42 Rectifier Module (500W), P/N 1R48500 ......................................................................................................... 42 Rectifier Module (1000W), P/N 1R481000 ..................................................................................................... 42 Controller ........................................................................................................................................................... 43 NCU (NetSure Control Unit), P/N 1M830BNA ............................................................................................... 43 ACU+ (Advanced Control Unit Plus), P/N 1M820BNA .................................................................................. 43 SCU+ (Standard Control Unit Plus), P/N 1M521BNA .................................................................................... 43 Optional Temperature Probes .......................................................................................................................... 44 Mounting and Adapter Kits .............................................................................................................................. 45 Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 .................................................................... 45 Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203 ............................................................ 45 Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993 ................................................................................ 45 Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728 ................................................................................ 45 Optional 19” Rear Cover Kit, P/N 555260 ...................................................................................................... 46 Optional 3” Projection Mount Kit for List 1, P/N 556828 ................................................................................ 46 Optional 23” Rear Cover Kit, P/N 555261 ...................................................................................................... 46 Rear Battery Cable Exit Kit P/N 547645 ........................................................................................................ 46 Distribution Devices .......................................................................................................................................... 47 GMT Load Distribution Fuses ........................................................................................................................ 47 Bullet Nose-Type Circuit Breakers ................................................................................................................. 48 Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 ................................................................. 49 Optional Bulk Output Busbar, P/N 535015 .................................................................................................... 49 AC Input Cables and Line Cords ..................................................................................................................... 50 AC Input Cable Assembly, P/N 535232 ......................................................................................................... 50 AC Input Line Cord, 208/240VAC, P/N 540946 ............................................................................................. 50 AC Input Line Cord, 208/240VAC, P/N 559301 ............................................................................................. 51 AC Input Line Cord, 208/240VAC, P/N 545616 ............................................................................................. 51 AC Input Line Cord, 208/240VAC, P/N 559842 ............................................................................................. 52 AC Input Line Cord, 208/240VAC, P/N 559302 ............................................................................................. 52 AC Input Line Cord, 120VAC, P/N 545252 .................................................................................................... 53 AC Input Line Cord, 120VAC, P/N 545478 .................................................................................................... 53 AC Input Line Cord, 120VAC, P/N 545479 .................................................................................................... 53 AC Input Line Cord, 208/240VAC, P/N 545480 ............................................................................................. 54 AC Input Line Cord, 120VAC, P/N 545481 .................................................................................................... 54 AC Input Line Cord, 208/240VAC, P/N 545553 ............................................................................................. 55 AC Input Line Cord, 120VAC, P/N 547525 .................................................................................................... 55 AC Input Line Cord, 120VAC, P/N 548457 .................................................................................................... 55 AC Input Line Cord, 120/208/240VAC, P/N 548196 ...................................................................................... 56 Special Application Digital Input Cable Kit, P/N 554935................................................................................ 57 AP6C57EA/EB Ring & Distribution Module .................................................................................................... 57 External Battery Disconnect Unit, P/N 535282 ............................................................................................... 59 NetSure™ 211BC Battery Cabinet (Spec. No. 541434) ................................................................................... 60 Page 5 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) NetSure™ 211BC Battery Cabinet (Spec. No. 545534) ................................................................................... 61 NetSure™ 211BC Battery Cabinet (Spec. No. 545506) ................................................................................... 62 NetSure™ 211BC Battery Cabinet (Spec. No. 554631) ................................................................................... 63 SM TEMP Temperature Concentrator (P/N 547490) ....................................................................................... 64 SM Module RS-485 Interface Cable P/N 547674 ............................................................................................. 64 PCU Blank Filler Panel, P/N PSK4820R-1 ....................................................................................................... 64 Anderson Battery Connector ........................................................................................................................... 65 Digital Input and Relay Output Cables ............................................................................................................ 66 User Replaceable Components ....................................................................................................................... 67 Wiring Notes ...................................................................................................................................................... 68 Shelf Frame Grounding Stud ......................................................................................................................... 68 AC Input Branch Circuit Protection and Wiring .............................................................................................. 68 External Alarm and Monitoring Wiring ........................................................................................................... 68 Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) .................................................................... 69 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) .............................................................. 69 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)................................................. 70 Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ................................... 70 Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) .......................................... 70 Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 72 CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) ............................................................ 72 Input Battery Wiring (List BG and NG) ........................................................................................................... 72 Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) .................................. 72 Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) ............................................. 73 Wiring Illustrations ............................................................................................................................................ 74 Shelf Frame Grounding Stud (both 1U and 2U Panels, List 1 and 5 shown) ................................................ 74 AC Input Wiring (Lists 1 and 2) ...................................................................................................................... 75 AC Input Wiring (Lists 5 and 6) ...................................................................................................................... 76 External Alarm and Monitoring Wiring (Lists 1 and 2).................................................................................... 77 External Alarm and Monitoring Wiring (Lists 5 and 6).................................................................................... 78 Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) ................ 83 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) .......... 84 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6, List 5 shown) .................................................................................................................................................. 85 Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................ 86 Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown) ......................................................................................................................... 87 Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown) ............................................................ 88 Load Distribution Wiring (GMT Fuses) (List KG) ........................................................................................... 89 Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) ............................................. 90 Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) ......................................... 91 SPECIFICATIONS.................................................................................................................................................... 92 1. System ........................................................................................................................................................... 92 1.1 Environmental Ratings ............................................................................................................................. 92 1.2 Compliance Information ........................................................................................................................... 92 1.3 Standard Features .................................................................................................................................... 93 2. Rectifier .......................................................................................................................................................... 94 3. Controller ....................................................................................................................................................... 94 MECHANICAL SPECIFICATIONS .......................................................................................................................... 95 Overall Dimensions – List 1 ............................................................................................................................. 95 Additional Dimensions – List 1 with Wall Mounting Kit (P/N 541285) .......................................................... 96 Additional Dimensions – List 1 with Optional 19” Rear Cover Kit, P/N 555260 .......................................... 97 Additional Dimensions – List 1 with Optional 3” Projection Mount Kit, P/N 556828 .................................. 98 Overall Dimensions – List 2 ............................................................................................................................. 99 Page 6 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Additional Dimensions – List 2 with Wall Mounting Kit (P/N 541285) ........................................................ 100 Additional Dimensions – List 2 with Optional 23” Rear Cover Kit, P/N 555261 ........................................ 101 Overall Dimensions – List 5 ........................................................................................................................... 102 Overall Dimensions – List 6 ........................................................................................................................... 103 Additional Dimensions – Lists 1, 2, 5 and 6 with Wall Mounting Kit (P/N 553203) ................................... 104 Overall Dimensions – List KG ........................................................................................................................ 105 Overall Dimensions – 19” Battery Tray ......................................................................................................... 106 Overall Dimensions – 23” Battery Tray ......................................................................................................... 107 BATTERY MANUFACTURER INFORMATION .................................................................................................... 108 RELATED DOCUMENTATION .............................................................................................................................. 108 REVISION RECORD .............................................................................................................................................. 109 Page 7 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home MAIN COMPONENTS ILLUSTRATIONS 58213660001 Distribution Unit Side AC Input Connectors (P/O List 1) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or NCU P/N 1M830BNA 58213660002 Distribution Unit Side AC Input Connectors (P/O List 2) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or NCU P/N 1M830BNA Page 8 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 58213660001 with P/N 555260 Rear AC Input Connector (P/O P/N 555260) and AC Input Cables/Line Cords Distribution Unit Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or NCU P/N 1M830BNA 58213660001 with P/N 556828 Kit Rear AC Input Connector (P/O P/N 556828) and AC Input Cables/Line Cords Distribution Unit SCU+ P/N 1M521BNA or NCU P/N 1M830BNA Rectifier Module (500W) or Rectifier Module (1000W) Page 9 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 58213660002 with P/N 555261 Rear AC Input Connector (P/O P/N 555261) and AC Input Cables/Line Cords Distribution Unit Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or NCU P/N 1M830BNA Page 10 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 58213660005 Distribution Unit Side AC Input Connectors (P/O List 5) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA or NCU P/N 1M830BNA 58213660006 Distribution Unit Side AC Input Connectors (P/O List 6) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA or NCU P/N 1M830BNA Page 11 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 Other System Application Guide Spec. No. 582136600 (Model 211NGFB) Home DISTRIBUTION UNIT (Lists 1 and 2) List BG: (10) GMT Fuse Load Positions Low Voltage Battery Disconnect (LVBD) (1) Set Battery Cables List NG: (10) GMT Fuse Load Positions NO Low Voltage Disconnect (1) Set Battery Cables DISTRIBUTION UNIT (Lists 5 and 6) List BF: (13) GMT Fuse Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LF: (13) GMT Fuse Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points List NF: (13) GMT Fuse Load Positions NO Low Voltage Disconnect (3) Battery Landing Points List BC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points List NC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions NO Low Voltage Disconnect (3) Battery Landing Points List BA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions Low Voltage Battery Disconnect (LVBD) List LA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions Low Voltage Load Disconnect (LVLD) List NA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions NO Low Voltage Disconnect Page 12 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Other List Options List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions (for use w/ Lists BC, LC, NC, BA, LA, and NA) List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions (for use w/ Lists BF, LF, and NF) List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions (for use w/ Lists BF, LF, and NF) List 65: Shelf Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 66: Battery Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 67: Battery Side Battery Cables (For use with Lists BC, LC, NC, BF, LF, and NF) List 71: Optional External Battery Cables (8 AWG) with Anderson Connector for (1) Battery String (for use w/ Lists BG and NG) List 72: Optional External Battery Cables with Anderson Connector for (2) Battery Strings (for use w/ Lists BG and NG) List 73: Optional External Battery Cables (6 AWG) with Anderson Connector for (1) Battery String (for use w/ Lists BG and NG) List 89: Relay Rack Earthquake Anchor Kit List 90: Temperature Probe (12 ft. total) List 91: Temperature Probe (33 ft. total) List 93: Battery Tray (23”) List 94: Battery Tray (19”) List KG: GMT Fuse Load Distribution Panel Home Page 13 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home LIST DESCRIPTIONS List Numbers List 1: 1RU High by 19” Wide Shelf Features ♦ Consists of a 1RU high by 19” wide shelf. ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed. ♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf. A mating half is available. ♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 1 shelf holds up to two (2) Rectifier Modules. Ordering Notes 1) Order List 1 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or NCU (P/N 1M830BNA) controller per shelf. Also specify the appropriate configuration file for your site. 3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 1 shelf requires one (1) AC Input Cable or Line Cord. 5) Order one (1) Distribution Unit (List BG or NG) per shelf. 6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71, 72 or 73. 7) Order Relay Rack Anchor Kit(s) (List 89) as required. 8) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. 9) Order Battery Trays (List 94) as required. 10) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. 16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section. Page 14 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 2: 1RU High by 23” Wide Shelf Features ♦ Consists of a 1RU high by 23” wide shelf. ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed. ♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf. A mating half is available. ♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 2 shelf holds up to three (3) Rectifier Modules. Ordering Notes 1) Order List 2 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or NCU (P/N 1M830BNA) controller per shelf. Also specify the appropriate configuration file for your site. 3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 2 shelf requires one (1) AC Input Cable or Line Cord. 5) Order one (1) Distribution Unit (List BG or NG) per shelf. 6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71, 72 or 73. 7) Order Relay Rack Anchor Kit(s) (List 89) as required. 8) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. 9) Order Battery Trays (List 93) as required. 10) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. 16) Order Special Application Digital Input Cable Kit per ACCESSORY DESCRIPTIONS section. Page 15 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 5: 2RU High by 19” Wide Shelf Features ♦ Consists of a 2RU high by 19” wide shelf. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds. ♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs. ♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available. ♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 5 shelf holds up to four (4) Rectifier Modules. Ordering Notes 1) Order List 5 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or ACU+ (P/N 1M820BNA) or NCU (P/N 1M830BNA) Controller per shelf. Also specify the appropriate configuration file for your site. 3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 5 shelf requires two (2) AC Input Cables or Line Cords. 5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf. 6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered. Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions. 7) Order one (1) List KG Distribution Fuse Panel per shelf, as required. 8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66) for each List BC, LC, NC, BF, LF, or NF ordered. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order Relay Rack Anchor Kit(s) (List 89) as required. 11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. 12) Order Battery Trays (List 94) as required. 13) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 16 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 6: 2RU High by 23” Wide Shelf Features ♦ Consists of a 2RU high by 23” wide shelf. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds. ♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs. ♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available. ♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 6 shelf holds up to six (6) Rectifier Modules. Ordering Notes 1) Order List 6 as required. Also order the following as required. 2) Order one (1) SCU+ (P/N 1M521BNA) or ACU+ (P/N 1M820BNA) or NCU (P/N 1M830BNA) Controller per shelf. Also specify the appropriate configuration file for your site. 3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 6 shelf requires two (2) AC Input Cables or Line Cords. 5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf. 6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered. Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions. 7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required. 8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66) for each List BC, LC, NC, BF, LF, or NF ordered. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order Relay Rack Anchor Kit(s) (List 89) as required. 11) Order up to two (2) Temperature Probes (List 90 or 91) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient temperature. See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. 12) Order Battery Trays (List 93) as required. 13) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 17 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions Features Home Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads. Restrictions For use with List BC, LC, NC, BA, LA, and NA Distribution units only. Ordering Notes 1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit. Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206. ♦ List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions Features Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads. Restrictions For use with List BF, LF, and NF Distribution units only. Ordering Notes 1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit. Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206. ♦ List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions Features Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 15A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads. Restrictions For use with List BF, LF, and NF Distribution units only. Ordering Notes 1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit. Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988. ♦ List 65: Shelf Side Battery Cables, P/N 540814 Features Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 66). Remaining end terminated in lugs for connection to shelf. Restrictions For use with List BF, LF, NF, BC, LC, and NC Distribution units only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. ♦ Page 18 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List 66: Battery Side Battery Cables, P/N 540954 Features Home Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 65). Remaining end un-terminated for connection to batteries. Restrictions For use with List BF, LF, NF, BC, LC, and NC only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. ♦ List 67: Battery Cable, P/N 545709 Features Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson connector on the battery side. Remaining end terminated in lugs for connection to shelf. Restrictions For use with P/N 541434, P/N 545534, P/N 545506, or P/N 554631 battery cabinets only. For use with List BF, LF, NF, BC, LC, and NC Distribution units only. Ordering Notes 1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 2) Order one (1) for each battery cabinet feed required. ♦ List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493 Features ♦ Provides two (2) 6’ long, 8 AWG, battery cables terminated in a Red SB50 Anderson connector for connecting one (1) battery string to the system. One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string. Restrictions For use with List BG and NG only. Ordering Notes 1) Order if required. 2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. ♦ Page 19 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List 72: Optional External Battery Cable Assembly Home with Anderson Connector for (2) Battery Strings, P/N 535124 Features ♦ Provides four (4) 6’ long, 10 AWG, battery cables terminated in a Red SB50 Anderson connector for connecting two (2) battery strings to the system. One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains four (4) unterminated cables for connection into customer battery strings. Restrictions For use with List BG and NG Distribution units only. Ordering Notes 1) Order if required. 2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. ♦ List 73: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 555050 Features ♦ Provides two (2) 6’ long, 6 AWG, battery cables terminated in a Red SB50 Anderson connector for connecting one (1) battery string to the system. One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string. Restrictions For use with List BG and NG only. Ordering Notes 1) Order if required. 2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. ♦ List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 Features ♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor. Ordering Notes 1) Order as required. Page 20 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) Features Home ♦ Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be programmed to monitor ambient temperature or battery temperature. ♦ A temperature probe set as a battery probe can also be designated to be used for the battery charge temperature compensation feature. If the system is equipped with the ACU+ or NCU Controller, the battery charge temperature compensation feature can be programmed to use one probe or the average or highest value of all probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. ♦ If the system is equipped with the ACU+ or NCU Controller, a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway (BTRM feature). The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04118247 (9 feet long) is shipped loose. Total length: 12 ft. Restrictions A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold. Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247. 2) For a Temperature Probe with a longer cable see List 91. 3) See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. ♦ List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) Features ♦ See above for description of Temperature Probes. The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Total Length: 33 ft. Restrictions See above for restrictions. Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740. 2) For a Temperature Probe with a shorter cable see List 90. 3) See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. ♦ Page 21 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 93: Battery Tray for 23” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that two battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 23” relay racks only. Maximum number of List 93’s per rack is three (3). A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at bottom of rack and working upward. Ordering Notes 1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions above. 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. Tables A, B, and C list the batteries recommended for use with List 93. ♦ 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables A, B, and C. 5) Battery lugs are provided, as specified from Table D. 6) Specify with or without battery disconnect circuit breakers. Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. 7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from Table E. 8) If ordering List 93 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table E will be installed. Kit numbers are provided for reference only 9) If ordering List 93 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Page 22 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Battery Tray P/N 528496 Emerson Network Power P/N Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) Manufacturer* Model GNB Marathon M12V125FT -- 125 4.90 X 22.00 X 11.15 7U 105 GNB Marathon M12V155FT 112795 155 4.90 X 22.00 X 11.15 7U 119 Northstar NSB110FT -- 110 4.92 X 22.05 X 8.94 7U 91 Northstar NSB170FT -- 167 4.92 X 22.05 X 12.60 8U 131 Deka Unigy I 12AVR-150ET 122018 150 4.90 X 22.00 X 11.75 8U 115 C&D TEL12-210F 554579 202 4.90 X 22.00 X 12.80 8U 132 Douglas DGS12-150F 125453 150 4.90 X 22.00 X 12.70 8U 137 Douglas DSN12-170F -- 170.8 4.92 X 22.05 X 12.60 8U 130 * See Battery Manufacturer Information located at the end of this document. Table A Battery Tray P/N 540842 Manufacturer* Model Emerson Network Power P/N Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34 Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49 Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27 Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48 Enersys 12TD50F -- 48 4.2 X 10.9 X 8.7 6U 38 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. Table B Battery Tray P/N 557573 Manufacturer* Model Emerson Network Power P/N Enersys 12TD150F -- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 143 4.3 X 21.7 X 11.3 8U 105 * See Battery Manufacturer Information located at the end of this document. Table C Page 23 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Battery Lug Kit Part Number (Kit provides two lugs for one tray.) Battery Specified Lists 5 and 6 Lists 1 and 2 GNB Marathon M12V125FT GNB Marathon M12V155FT Northstar NSB110FT 528234 Northstar NSB170FT 540989 (for use with 10 AWG wire and List 72) Deka Unigy I 12AVR-150ET C&D TEL12-210F Douglas DGS12-150F 528236 545581 (for use with 8 AWG wire and List 71) Douglas DSN12-170F Northstar NSB40FT 555069 (for use with 6 AWG wire and List 73) Northstar NSB60FT Douglas DGS12-25F 528234 Douglas DGS12-50F Enersys 12TD50F Enersys 12TD150F Table D Ampere Rating Part No., Circuit Breaker, 1 Electrical/Mechanical Trip (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 35 256693500 40 256693900 50 256694300 60 256694700 70 256695100 75 256695500 100 256695900 Part No., Left-Side Breaker Mtg. Kit (For Reference Only) Part No., Right-Side Breaker Mtg. Kit (For Reference Only) 528501 528500 1 Provides an alarm during an electrical or manual trip condition. Table E Page 24 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 94: Battery Tray for 19” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that three battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 19” relay racks only. Maximum number of List 94’s per rack is three (3). A single List 94 must mount at bottom of rack. Multiple List 94’s must mount starting at bottom of rack and working upward. Ordering Notes 1) Order multiples of List 94 for more than one (1) battery tray. See Restrictions above. 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. Tables F, G, H and I list batteries recommended for use with List 94. 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See Tables F, G, H and I. 5) Battery lugs are provided, as specified from Table J. ♦ 6) Specify with or without battery disconnect circuit breakers. Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. 7) If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from Table K. 8) If ordering List 94 with circuit breakers, specify breaker mounting on left side of tray, right side of tray, or remote mounting. Circuit breaker mounting kits shown in the Table K will be installed. Kit numbers are provided for reference only. 9) If ordering List 94 with circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Page 25 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Battery Tray P/N 558047 Model Emerson Network Power P/N Northstar NSB90FT -- 90 4.25 X 15.59 X 10.04 7U 71 Northstar NSB100FT -- 100 4.25 X 15.59 X 11.03 7U 78 GNB Marathon M12V90FT -- 90 4.13 X 15.55 X 10.63 7U 70 Enersys 12TD100F4 -- 96 4.3 X 15.5 X 11.3 8U 71 Manufacturer* Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. Table F Battery Tray P/N 541034 Manufacturer* Model Emerson Network Power P/N GNB Marathon M12V105FT -- 105 4.33 X 20.12 X 9.37 7U 79 Enersys 12TD100F6 -- 97 4.3 X 20.0 X 9.4 7U 73 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. Table G Battery Tray P/N 540841 Manufacturer* Model Emerson Network Power P/N Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34 Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49 Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27 Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48 Enersys 12TD50F -- 48 4.2 X 10.9 X 8.7 6U 38 Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. Table H Page 26 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Battery Tray P/N 548213 Rated 8-Hr. Capacit y (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) Manufacturer* Model Emerson Network Power P/N Enersys 12V125F 122009 125 4.10 X 22.10 X 12.40 8U 124 Enersys 12TD150F -- 143 4.3 X 21.7 X 11.3 8U 105 * See Battery Manufacturer Information located at the end of this document. Table I Battery Specified Battery Lug Kit Part Number (Kit provides two lugs for one tray.) Lists 5 and 6 Lists 1 and 2 Northstar NSB90FT Northstar NSB100FT GNB Marathon M12V90FT GNB Marathon M12V105FT 540989 (for use with 10 AWG wire and List 72) Northstar NSB40FT Northstar NSB60FT Douglas DGS12-25F 545581 (for use with 8 AWG wire and List 71) 528234 Douglas DGS12-50F Enersys 12V125F 555069 (for use with 6 AWG wire and List 73) Enersys 12TD50F Enersys 12TD100F4 Enersys 12TD100F6 Enersys 12TD150F Table J Page 27 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Ampere Rating Part No., Circuit Breaker, 1 Electrical/Mechanical Trip (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 35 256693500 40 256693900 50 256694300 60 256694700 70 256695100 75 256695500 100 256695900 Part No., Left-Side Breaker Mtg. Kit (For Reference Only) Part No., Right-Side Breaker Mtg. Kit (For Reference Only) 528501 528500 1 Provides an alarm during an electrical or manual trip condition. Table K Page 28 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Distribution Unit List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): ♦ • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 6) The controller remains powered when the LVBD contactor opens. Specify if you require List BF to be factory configured for the controller not to be powered when the LVBD contactor opens. • Page 29 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List LF: Distribution Unit with GMT Fuse Load Distribution Positions Home and with Low Voltage Load Disconnect (LVLD) Features ♦ Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): ♦ • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. • Page 30 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List NF: Distribution Unit with GMT Fuse Load Distribution Positions Home and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and working to the lowest capacity. In an ambient of 40°C (+104°F): ♦ • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of any value. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be separated by a smaller fuse or a space. In an ambient of 65°C (+149°F): • • Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses. 10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. • Page 31 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) Features ♦ Home Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. 6) The controller remains powered when the LVBD contactor opens. Specify if you require List BC to be factory configured for the controller not to be powered when the LVBD contactor opens. ♦ Page 32 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD) Features ♦ Home Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List LC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 33 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect Features ♦ Home Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 34 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD) Features ♦ Home Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. 5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be factory configured for the controller not to be powered when the LVBD contactor opens. Page 35 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) Features ♦ Home Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 36 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect Features ♦ Home Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. ♦ Page 37 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), battery cables, and ten (10) GMT fuse load distribution positions (15A maximum). ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. Home ♦ Ten (10) 0A to 15A GMT fuse load distribution positions. Restrictions For use with List 1 and 2 only. The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71, 72 or 73. 4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 38 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, battery cables, and ten (10) GMT fuse load distribution positions (15A maximum). ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. Home ♦ Ten (10) 0A to 15A GMT fuse load distribution positions. Restrictions For use with List 1 and 2 only. The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71, 72 or 73. 4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 39 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions Features ♦ Home 1U-high GMT fuse panel that provides Single Load Distribution (-48V) Provides twenty (20) 0A to 15A GMT fuse load distribution positions. Caution: At +40°C and +65°C ambient, a fuse with a rating of greater than 10 amperes SHALL HAVE an empty mounting position between it and any other fuse. ♦ ♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C ♦ Factory mounted and connected to List 5 or 6 shelf. ♦ If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG loads are disconnected. If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System Controller fuse alarm Restrictions For use with List 5 and 6 only. Mounts only immediately above List 5 or 6 shelf. Maximum distribution current is 80A. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required. Also order the following as required. 2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section. ♦ Page 40 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home ACCESSORY DESCRIPTIONS Relay Racks Features ♦ The following relay racks are available. Restrictions Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory mounted in the relay rack. Ordering Notes 1) Order from relay racks listed in Table 1. Part Number Available Mounting Positions (1RU = 1-3/4”) Size Notes 23” Relay Racks 543156 51-3/8” H x 23” W 28RU Welded 543161 6’0” H x 23” W 37RU Welded 543160 7’0” H x 23” W 45RU Seismic (Note 1) 543162 7’0” H x 23” W 45RU Welded 543163 7’6” H x 23” W 48RU Welded 543164 8’0” H x 23” W 51RU Welded 19” Relay Racks 525003 51-3/8” H x 19” W 28RU Welded 534653 6’0" H x 19” W 37RU Seismic (Note 1) 524961 6’0” H x 19” W 37RU Welded 534654 6’6” H x 19” W 41RU Seismic (Note 1) 534651 6’6” H x 19” W 41RU Welded 528183 7’0” H x 19” W 45RU Seismic (Note 1) 524988 7’0” H x 19”W 45RU Welded 524963 7’6” H x 19” W 48RU Welded 534652 8’0" H x 19” W 51RU Welded Note 1: Complies with Bellcore Seismic Zone 4 requirements. Table 1 Available Relay Racks Page 41 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Rectifier Rectifier Module (500W), P/N 1R48500 Features Provides one (1) Model R48-500, Spec. No. 1R48500, 500 watt / 48 volt Rectifier Module. Restrictions Each List 1 Shelf holds up to two (2) Rectifier Modules. Each List 2 Shelf holds up to three (3) Rectifier Modules. Each List 5 Shelf holds up to four (4) Rectifier Modules. Each List 6 Shelf holds up to six (6) Rectifier Modules. DO NOT install different wattage Rectifier Modules in same shelf. Ordering Notes 1) Order by P/N (1R48500) as required. ♦ Rectifier Module (1000W), P/N 1R481000 Features Provides one (1) Model R48-1000, Spec. No. 1R481000, 1000 watt / 48 volt Rectifier Module. Restrictions Each List 1 Shelf holds up to two (2) Rectifier Modules. Each List 2 Shelf holds up to three (3) Rectifier Modules. Each List 5 Shelf holds up to four (4) Rectifier Modules. Each List 6 Shelf holds up to six (6) Rectifier Modules. DO NOT install different wattage Rectifier Modules in same shelf. Ordering Notes 1) Order by P/N (1R481000) as required. ♦ Page 42 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Controller NCU (NetSure Control Unit), P/N 1M830BNA Features ♦ Provides the NCU Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions Each shelf must contain one (1) controller. Ordering Notes 1) Order one (1) controller for each shelf. Note: The controller is provided with the factory default configuration unless otherwise specified. ACU+ (Advanced Control Unit Plus), P/N 1M820BNA Features ♦ Provides the ACU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions ACU+ is not available in List 1 or List 2 shelves. Each shelf must contain one (1) controller. Ordering Notes 1) Order one (1) controller for each shelf. Note: The controller is provided with the factory default configuration unless otherwise specified. SCU+ (Standard Control Unit Plus), P/N 1M521BNA Features ♦ Provides the SCU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions Each shelf must contain one controller. Ordering Notes 1) Order one (1) controller for each shelf. Note: The controller is provided with the factory default configuration unless otherwise specified. Page 43 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Optional Temperature Probes Features ♦ Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be programmed to monitor ambient temperature or battery temperature. ♦ A temperature probe set as a battery probe can also be designated to be used for the battery charge temperature compensation feature. If the system is equipped with the ACU+ or NCU Controller, the battery charge temperature compensation feature can be programmed to use one probe or the average or highest value of all probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. ♦ If the system is equipped with the ACU+ or NCU Controller, a temperature probe set as a battery probe can also be used for controlling against battery thermal runaway (BTRM feature). ♦ The temperature sensor end of the probe contains a tab with a 5/16” clearance hole for mounting. ♦ The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. Restrictions A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold. Ordering Notes 1) Order temperature probes as required. Note that each temperature probe consists of two pieces which plug together to make a complete probe (see the following illustration). For a complete temperature probe, order one (1) P/N 552992 (10.3 meters) or one (1) P/N 556155 (3.3 meters). 2) See “List 90” on page 21 and “List 91” on page 21 for additional temperature probe options. Page 44 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Mounting and Adapter Kits Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 Features ♦ Allows for horizontal or vertical wall mounting. ♦ See Physical Size Information for mounting dimensions. Restrictions For use with List 1 or 2 only. Customer must supply mounting fasteners for securing the Wall Mount Bracket to the wall. This Kit will not support wall-mounting when the 58213660001 and 58213660002 shelves are flush mounted. Ordering Notes 1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2) P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to the shelf. Optional Wall Mount Bracket Kit for Lists 1, 2, 5 and 6, P/N 553203 Features ♦ Allows for vertical wall mounting. ♦ See Physical Size Information for mounting dimensions. Restrictions Customer must supply mounting fasteners for securing the Wall Mount Brackets to the wall. Ordering Notes 1) Order P/N 553203, which consists of two (2) wall brackets (P/N 553058 and 553059) and eight (8) 12-24 x ¾” screws with four (4) ground washers for attaching the brackets to the shelf. Optional 19” to 23” 1RU Rack Adapter Kit, P/N 540993 Features ♦ Allows for 23” 1RU relay rack mounting Restrictions For use with List 1 only. Ordering Notes 1) Order P/N 540993, which consists of two (2) P/N 540994 adapters and four (4) 12-24 x 1/”2 thread forming screws. Optional 19” to 23” 2RU Rack Adapter Kit, P/N 545728 Features ♦ Allows for 23” 2RU relay rack mounting Restrictions For use with List 5 only. Ordering Notes 1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread forming screws. Page 45 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Optional 19” Rear Cover Kit, P/N 555260 Features ♦ Allows for 19” 1RU flush rack mount configuration ♦ AC input unit is moved to the rear panel Restrictions For use with List 1 only. Ordering Notes 1) Order P/N 555260, which consists of one (1) P/N 553271 19” rear cover assembly, one (1) P/N 29041838 caution label and one (1) P/N PSK04118562 AC input jumper. Optional 3” Projection Mount Kit for List 1, P/N 556828 Features Allows for 19" 1RU 3" projection rack mount configuration Restrictions For use with List 1 only. Ordering Notes 1) Order by P/N 556828 as required. ♦ Optional 23” Rear Cover Kit, P/N 555261 Features ♦ Allows for 23” 1RU flush rack mount configuration ♦ AC input unit is moved to the rear panel Restrictions For use with List 2 only. Ordering Notes 1) Order P/N 555261, which consists of one (1) P/N 555113 23” rear cover assembly, one (1) P/N 29041838 caution label and one (1) P/N PSK04118555 AC input jumper. Rear Battery Cable Exit Kit P/N 547645 Features ♦ Provides 12” battery cables exiting rear of shelf Restrictions For use with List 5 only. Ordering Notes 1) For use with Battery Cabinets only. Page 46 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Distribution Devices GMT Load Distribution Fuses Features ♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8) 0-10A GMT load distribution fuses. ♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses. ♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses. ♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses. Restrictions When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere fuses, for which load should not exceed 70% of device rating. See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only), Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only), and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order GMT fuses per Table 2. Ampere Rating P/N Fuse Color 18/100 GMT-A 248610301 -- 1/4 248610200 Violet 1/2 248610300 Red 3/4 248610500 Brown 1-1/3 248610700 White 2 248610800 Orange 3 248610900 Blue 5 248611000 Green 7-1/2 248611300 Black-White 10 248611200 Red-White 15 248611500 Red-Blue Replacement Dummy Fuse 248872600 --- Replacement Safety Fuse Cover Lists BF, LF, NF, BC, LC, NC, BA, LA, NA and KG 102774 Lists BG and NG 248898700 -- Table 2 GMT Fuses Page 47 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Bullet Nose-Type Circuit Breakers Features ♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit breakers. Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit breakers and up to two (2) bullet nose-type load distribution circuit breakers. Restrictions See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) and Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order circuit breakers per Table 3. ♦ P/N Ampere Rating Electrical Trip (White Handle) Electrical/ 2 Mechanical Trip (Black Handle) 1 102272 101596 3 102273 101597 5 102274 101598 10 102275 101599 15 102276 101600 20 102277 101601 25 102278 101602 30 102279 101603 35 102280 101604 40 102281 101605 45 121998 121997 50 102282 101606 60 102283 101607 70 102284 101608 75 102285 101609 80 121996 121995 90 138887 138888 102286 101610 100 1 See Table 6 for recommended wire sizes and lugs. Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical trip condition only. 2 Provides an alarm during an electrical or manual trip condition. Note that Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers. Table 3 Bullet Nose-Type Circuit Breakers Page 48 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 Features ♦ Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit. ♦ Provides six (6) 0A to 15A GMT fuse load distribution positions. ♦ Screw clamp type load and load return terminals provided. Home Includes six (6) dummy fuses equipped with safety fuse covers. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA. Terminal block wire size capacity: 24 to 14 AWG. Requires two (2) bullet device mounting positions. Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position. Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Factory installed only. Ordering Notes 1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required. 2) Order GMT fuses as required per Table 2. ♦ Optional Bulk Output Busbar, P/N 535015 Features Each Bulk Output Busbar installs in a single circuit breaker position in a List BC, LC, NC, BA, LA, and NA Distribution Unit. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA. Ordering Notes 1) Order by P/N 535015 as required. ♦ Page 49 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Cables and Line Cords AC Input Cable Assembly, P/N 535232 Features ♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and the remaining end un-terminated. Restrictions Rated for 30A. For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 208/240VAC, P/N 540946 Features ♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 50 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 559301 Features ♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug at a 90 degree angle bend which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 208/240VAC, P/N 545616 Features ♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 51 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 559842 Features ♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug (wires molded 180° from plug orientation) which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 208/240VAC, P/N 559302 Features ♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug at a 90 degree angle bend which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 52 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 120VAC, P/N 545252 Features ♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 120VAC, P/N 545478 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 equipped with R48-500 Rectifier Modules. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. AC Input Line Cord, 120VAC, P/N 545479 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-15P twist-lock plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 equipped with R48-500 Rectifier Modules. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 53 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 545480 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-15P twist-lock plug. Restrictions For 240 VAC only (rated for 15A at 208/240VAC). For use with List 1 and 5. For use with List 2 and 6 with R48-500 Rectifiers. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. AC Input Line Cord, 120VAC, P/N 545481 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-20P twist-lock plug. Restrictions For 120 VAC only (rated for 20A at 120VAC). For use with List 1 and 5. For use with List 2 and 6 with R48-500 Rectifiers. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 54 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 545553 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-20P twist-lock plug. Restrictions For 240 VAC only (rated for 20A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 120VAC, P/N 547525 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 120VAC, P/N 548457 Features ♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 with R48-500 Rectifiers. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 55 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) AC Input Line Cord, 120/208/240VAC, P/N 548196 Features ♦ Home Provides one (1) 6’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with an IEC320 C20 plug. Restrictions For 120/208/240 VAC (rated for 20A at 120/208/240VAC). For 208/240V use with List 1, 2, 5, and 6 and all Rectifier Modules. For 120V use with List 1 and 5 and all Rectifier Modules. For 120V use with List 2 and 6 with 500W Rectifier Module only. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Per UL 60950-1, 2nd Edition, when this cord is used with this power system, the following restrictions apply: • The power system must be used “in a location having equipotential bonding (such as a telecommunications centre, a dedicated computer room or a restricted access location). • “The building installation shall provide a means for connection to protective earth; and • “The equipment is to be connected to that means; and “A service person shall check whether or not the socket-outlet from which the equipment is to be powered provides a connection to the building protective earth. If not, the service person shall arrange for the installation of a protective earthing conductor from the separated protective earthing terminal to the protective earth wire in the building.” Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. • Page 56 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Special Application Digital Input Cable Kit, P/N 554935 Home Features ♦ Provides an alarm cable kit to add -48VDC to digital input #2. The kit consists of two pieces that plug together to make a complete connection. One part is pre-wired to the shelf and the other part is shipped loose. Restrictions For use with List 1 and 2. Ordering Notes 1) Order one (1) Special Application Digital Input Cable Kit as required for each List 1 and 2 ordered. ♦ AP6C57EA/EB Ring & Distribution Module Features ♦ When used with List 6, this module is designed to supply a filtered and regulated –48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems (such as SLC-96 or SLC Series-5) requiring up to 45 A of load capacity. ♦ Designed to mount in a 23” relay rack, the module is one rack unit high, with 5” front projection. ♦ Includes two (2) 50VA ringers with automatic transfer capability (N+1 redundancy). ♦ Provides 35 DC distribution fuse positions, configured in five groups of seven, feeding five channel banks. Includes 35 dummy fuses. ♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution fuses are included with each cable assembly ordered. ♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic pair, with surge protection. See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete specifications. Restrictions Cannot be used with Distribution units List BF, LF, or NF. Ordering Notes 1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626). 2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order AP6C57EB (A7000796). 3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable assemblies can be mixed. ♦ Page 57 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home ORDERING CODE DESCRIPTION P7000858 Cable assy for one SLC96 channel bank (8 ft.) P7001139 Cable assy for one SLC96 channel bank (20 ft.) P7000859 Cable assy for one SLC5 channel bank (8 ft.) P7001136 Cable assy for one SLC5 channel bank (20 ft.) P7000937* Cable assy for one channel bank, generic applications (8 ft.) *Note: Each channel bank position on the panel has a maximum capacity of 11A. 4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect between a power shelf and the DC input terminals of one (1) Ring & Distribution Module. 5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table. ORDERING CODE DESCRIPTION 547646 Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) 547647 Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) 6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the following table. ORDERING CODE DESCRIPTION A0885525 1.33A Alarm SAN-O Fuse A0885530 3A Alarm SAN-O Fuse A0885531 5A Alarm SAN-O Fuse A0885532 A7000627 (AP8C55AA) 10A Alarm SAN-O Fuse 50VA Ring Generator Page 58 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home External Battery Disconnect Unit, P/N 535282 Features ♦ Battery Disconnect Unit with mounting tabs. ♦ Two 1/4-20 studs w/hardware provided for installation of single hole battery lugs. ♦ One (10’ long) alarm lead provided. Restrictions Circuit breakers are ordered separately. Maximum number of Battery Disconnect Units per system is three (3). Ordering Notes 1) Order by P/N 535282 as required. 2) Order a circuit breaker for each Battery Disconnect Unit from Table 4. 3) Also order the following lug kits for each battery disconnect circuit breaker ordered: 545581(for use with 8 AWG wire and List 71), 540989 (for use with 10 AWG wire and List 72) or 555069 (for use with 6 AWG wire and List 73) and 541031 (wire with lugs for connection from battery disconnect to battery string). 4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery Disconnect Units are to be used (daisy-chains the alarm terminal of up to three [3] Battery Disconnect Units). (Section of alarm lead between Battery Disconnect Units is 30”, section of alarm lead between Battery Disconnect Unit and system’s alarm terminal is 84”.) Yellow Jumper/Alarm Lead (P/N 524384) (for use when more than one Battery Disconnect Units are ordered) Ampere Rating P/N Electrical/Mechanical 1 Trip (Black Handle) Ampere Rating P/N Electrical/Mechanical 1 Trip (Black Handle) 1 256690300 35 256693500 3 256690700 40 256693900 5 256691100 50 256694300 10 256691500 60 256694700 15 256691900 70 256695100 20 256692300 75 256695500 25 256692700 100 256695900 30 256693100 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. Table 4 Battery Disconnect Unit Circuit Breakers Page 59 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 541434) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Order Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 541434 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Hawker SBS 15 139091 14 12.50 Fiamm 12SLA12 139092 12 12.35 EaglePicher HE-12V7.7FR 139094 6.9 5.94 EaglePicher HE-12V12.7FR 139093 11.6* 9.68 Enersys NP18-12FR 139774 16 * 13.60 * 10Hr rate 3) When ordering 139774 batteries, also order 545427 Battery Connection kit. 4) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 60 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 545534) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545534 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys SBS B10 140553 38 28.20 C&D / Dynasty TEL12-30 140455 30.5 26.70 3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 61 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 545506) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545506 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys SBS B10 140553 38 28.20 Enersys SBS 40 140581 38 28.00 C&D/ Dynasty TEL12-30 140455 30.5 26.70 C&D/ Dynasty TEL12-45 140454 46 26.70 3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 62 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NetSure™ 211BC Battery Cabinet (Spec. No. 554631) Features ♦ The NetSure™ 211BC Battery Cabinet is rated at 30 amperes, and can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 554631 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. ♦ Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery GNB M12V40F 241173815 40 39.00 Note: When wall mounted, a battery cabinet frame grounding landing point adapter, P/N 556872, is provided. This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet. Frame Grounding Point (1/4-20 Studs on 5/8” Centers) Frame Ground Landing Point Adapter P/N 556872 Attach Frame Ground Landing Point Adapter to Cabinet Page 63 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) SM TEMP Temperature Concentrator (P/N 547490) Home Features ♦ Allows for multiple temperature probes to be used for temperature compensation. Compensation can be based on highest probe temperature or average probe temperature. ♦ Provides (8) temperature probe inputs per SM TEMP. ♦ Can be cascaded up to (8) SM TEMP modules, connecting up to 64 temperature probes. ♦ Provides analog output for all controllers. Restrictions Concentrator needs to plug into analog temp input on IB2 board. Ordering Notes 1) Order P/N 547490. 2) Order up to (8) 3-meter (P/N 547749) or 10-meter (P/N 547750) temperature probes for each concentrator. SM Module RS-485 Interface Cable P/N 547674 Features ♦ Provides 4’ cable for connecting SM supervisory modules to the system RS-485 interface connector. ♦ For interface with SM AC, SM BAT, SM BRC, or SM IO modules. Restrictions One (1) RS-485 connector is available in the system. Ordering Notes 1) Order P/N 547674 as required. PCU Blank Filler Panel, P/N PSK4820R-1 Features ♦ Provides 1x2U blank filler panel for rectifier module. Ordering Notes 1) Order P/N PSK4820R-1 as required. Page 64 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Anderson Battery Connector Features Includes the components necessary to assemble an Anderson connector onto a battery cable. Restrictions Appropriate battery post mating lugs must be ordered separately. Ordering Notes Order Anderson connector housings and lugs per the following table. ♦ Single Part Number for a Housing and Lugs Emerson P/N Anderson P/N (not available in kit form, order components individually per the second half of this table) (not available in kit form, order components individually per the second half of this table) 133196 6331G1 Emerson P/N Anderson P/N 138922 992G1 Lug (accepts 8 AWG wire) (2 required per housing) 247109602 5952 Lug (accepts 6 AWG wire) (2 required per housing) 111691 5900 Description For a single string (spare for List 71). Consists of two (2) lugs (Anderson P/N 5952) and one (1) Red Connector (Anderson P/N 992G1). Lugs accept 8 AWG wire. Allows for the connection of one (1) battery string (both polarities) (one wire per lug). For a single string (spare for List 73). Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red Connector (Anderson P/N 992G1). Lugs accept 6 AWG wire. Allows for the connection of one (1) battery string (both polarities) (one wire per lug). For a double string (spare for List 72). Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red Connector (Anderson P/N 992G1). Lugs accept 6 AWG wires. Allows for the connection of two (2) battery strings (both polarities) (two [10 AWG] wires per lug). Individual Housing and Lugs Part Numbers (spare for List 1, 2, 71, and 73) Description Housing Page 65 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Digital Input and Relay Output Cables Features ♦ Lists 1 and 2: Two sets of customer wiring cables are available. One set is for Digital Inputs and Relay outputs. The other set is for an additional -48V digital input. One half of the Digital Inputs and Relay Outputs cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. The additional -48V digital input cable must be ordered separately. When ordered, one half of the -48V digital input cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end. Lists 5 and 6: Two sets of customer wiring cables are available. One set is for the Digital Inputs and another set, for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end. Ordering Notes 1) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (2 ft.) is provided and factory connected in the List 1 and 2 shelves. The mating cable, P/N 545495 (10 ft.) must be ordered separately. For additional -48V Digital Input Cable Kit, order P/N 554935. 2) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (3 ft.) is provided and factory connected in the List 5 and 6 shelves. A mating cable, P/N 541309 (10 ft.) or P/N 545644 (50 ft.), must be ordered separately. For the Digital Inputs Cable, order P/N 541310 (shelf side, 3 ft.) and P/N 541311 (customer side, 10 ft.). Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only. ♦ Page 66 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home User Replaceable Components Ordering Notes 1) Refer to Table 5. Item Part Number 500W Rectifier Module 1R48500 1000W Rectifier Module 1R481000 Rectifier Blank Panel PSK4820R-1 Rectifier Module Fan 32010093 NCU Controller Module ACU+ Controller Module SCU+ Controller Module Temperature Probe 1M830BNA* * Also specify the appropriate NCU configuration file. Refer to the configuration file label on your existing NCU Controller. 1M820BNA* * Also specify the appropriate ACU+ configuration file. Refer to the configuration file label on your existing ACU+ Controller. 1M521BNA* * Also specify the appropriate SCU+ configuration file. Refer to the configuration file label on your existing SCU+ Controller. Order per List 90 (9 ft. long) or List 91 (30 Ft. long) (or if only one piece of the two piece probe is needed, see the List 90 or 91 description for part numbers). See “Optional Temperature Probes” on page 44 for temperature probe options with a mounting tab. Table 5 Replacement Module Part Numbers Page 67 of 109 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue W, January 12, 2015 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Wiring Notes Refer also to the next section, Wiring Illustrations. Shelf Frame Grounding Stud Features ♦ An M5 frame grounding stud with hardware is provided on the rear of the shelf. Restrictions Recommended frame ground wire size is 6 AWG. AC Input Branch Circuit Prot