SAG582136600 System Application Guide Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010 Home SYSTEM OVERVIEW Description: The NETSURE™ 211NGFB DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. This power system consists of the following mounted in a 1RU or 2RU high by 19” or 23” wide shelf. • 500W or 1000W Rectifier Modules The 1RU high by 19” wide shelf accommodates two (2) 500W or 1000W Rectifier Modules. The 1RU high by 23” wide shelf accommodates three (3) 500W or 1000W Rectifier Modules. The 2RU high by 19” wide shelf accommodates four (4) 500W or 1000W Rectifier Modules. The 2RU high by 23” wide shelf accommodates six (6) 500W or 1000W Rectifier Modules. The Rectifier Modules provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules are designed to provide constant power. They are designed with the latest patented switch-mode technology using DSP (Digital Signal Processing) functionality for efficient operation. This means that, within the normal operating ambient temperature range and input voltage range, the maximum available output power is a constant 500W or 1000W. Within these ranges, the Rectifier Modules operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. If ambient temperature rises above or input voltage falls below acceptable values, Rectifier Modules continue to operate but at derated output power levels. 1) Constant Voltage Mode: For any initial output voltage setting from 42 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 500W or 1000W. 2) Constant Power Mode: As load increases above approximately 500W or 1000W (non-adjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier Modules operate in the Constant Power Mode unless load continues to increase to the point where the current limit setting is reached. 3) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. List 1 (List 2 similar) List 5 (List 6 similar) Page 1 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 • System Application Guide Spec. No. 582136600 (Model 211NGFB) ACU+ (Advanced Control Unit Plus) Home The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms as well as PCU control, data acquisition, system alarm management, and advanced battery and energy management. The ACU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via Temperature Concentrators (SiteWeb™ TEMP), and ambient air temperature monitoring if equipped with a second temperature probe. The ACU+ provides Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management. • SCU+ (Standard Control Unit Plus) The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions, monitoring functions, and local/remote alarms. The SCU+ contains an LCD display and keypad for local access. It provides connection for binary inputs, programmable relay outputs, and a charge control function. The controller also supports rectifier temperature compensation if the system is equipped with a temperature probe (or multiple temperature probes connected via Temperature Concentrators (SiteWeb™ TEMP), and ambient air temperature monitoring if equipped with a second temperature probe. The SCU+ also provides Ethernet connection and SNMP capability. • Distribution Unit Various Distribution Unit options are available, as described in this document. The Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) contactor. Family: NETSURE™ Spec. No.: 582136600 Model: 211NGFB Input Voltage Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an operating range of 100 to 250 volts. Acceptable input frequency range is 45 to 65 Hz. Output Voltage: -48 Volts DC Output Capacity: Rectifier Module: 500W @ Vout >48Vdc (10.5A @ -48Vdc) or 1000W @ Vout >48Vdc (20.9A @ -48Vdc) Page 2 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home System: See the following table. 208/240VAC Input 120VAC Input +40°C (+104°F) +65°C (+149°F) +40°C (+104°F) +65°C (+149°F) 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 58213660001 20.8A 41.6A 12.6A 25A 20.8A 27.4A 12.6A 16.4A 58213660002 31.2A 62.4A 18.9A 37.5A 31.2A 41.1A 18.9A 24.6A 58213660005 41.6A 83.2A 25.2A 50A 41.6A 54.8A 25.2A 32.8A 58213660006 62.4A 124.8A 37.8A 75A 62.4A 82.2A 37.8A 49.2A System Agency Approval: UL 60950 Recognized, CAN/CSA 22.2 Framework Type: Relay Rack Mounted Mounting Width: 19” or 23”, nominal Mounting Depth: 12” Mounting Height: 1.75” (1RU) or 3.5” (2RU) Access: Front for Installation, Operation, and Maintenance Control: Microprocessor Color: Front Panels are Gray; Shelf is Galvaneal List Options: 1RU High 19” Wide Shelf, 1RU High 23” Wide Shelf, 2RU High 19” Wide Shelf, 2RU High 23” Wide Shelf, SCU + Controller, ACU+ Controller, Rectifier Module (500W), Rectifier Module (1000W), Five (5) Load Lead Assemblies for 10A GMT Fuse Positions, Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions, Five (5) Load Lead Assemblies for 15A GMT Fuse Positions), Shelf Side Battery Cables, Battery Side Battery Cables, Battery Cable, Optional External Battery Cables with Anderson Connector for (1) Battery String, Optional External Battery Cables with Anderson Connector for (2) Battery Strings, Relay Rack Earthquake Anchor Kit, Optional Temperature Probes, Battery Tray for 23” Relay Rack, Battery Tray for 19” Relay Rack, 1RU High Distribution Unit with (10) GMT Fuse Load Positions and with Low Voltage Battery Disconnect (LVBD), 1RU High Distribution Unit with (10) GMT Fuse Load Positions and w/out Low Voltage Disconnect, 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (2) Circuit Breaker Load Positions, (2) Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD), 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (2) Circuit Breaker Load Positions, (2) Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD), 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (2) Circuit Breaker Load Positions, (2) Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect, 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit Breaker Load Positions, and with Low Voltage Battery Disconnect (LVBD), 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit Breaker Load Positions, and with Low Voltage Load Disconnect (LVLD), 2RU High Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit Breaker Load Positions, and w/out Low Voltage Disconnect, 2RU High Page 3 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Distribution Unit with (13) GMT Fuse Load Positions and with Low Voltage Battery Disconnect (LVBD), 2RU High Distribution Unit with (13) GMT Fuse Load Positions and with Low Voltage Load Disconnect (LVLD), 2RU High Distribution Unit with (13) GMT Fuse Load Positions and w/out Low Voltage Disconnect, 1RU High Load Distribution Panel with (20) GMT Fuse Load Positions Accessory Options: Relay Racks, Mounting and Adapter Kits, Distribution Devices, AC Input Cables and Line Cords, Ring & Distribution Module, External Battery Disconnect Unit, Battery Cabinets, SiteWeb™ TEMP Temperature Concentrator, Anderson Battery Connector, Digital Input and Relay Output Cables, Replacement Modules, Wiring Notes, Wiring Illustrations Environment: -40°C (-40°F) to +65°C (+149°F), with deratings (see SPECIFICATIONS section) Page 4 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home 58213660001 Distribution Unit SCU+ P/N 1M521BNA Side AC Input Connectors (P/O List 1) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) 58213660002 Distribution Unit SCU+ P/N 1M521BNA Side AC Input Connectors (P/O List 2) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) Page 5 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 58213660005 Distribution Unit Side AC Input Connectors (P/O List 5) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA 58213660006 Distribution Unit Side AC Input Connectors (P/O List 6) and AC Input Cables/Line Cords Rectifier Module (500W) or Rectifier Module (1000W) SCU+ P/N 1M521BNA or ACU+ P/N 1M820BNA Page 6 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home DISTRIBUTION UNIT (Lists 1 and 2) List BG: (10) GMT Fuse Load Positions Low Voltage Battery Disconnect (LVBD) (1) Set Battery Cables List NG: (10) GMT Fuse Load Positions NO Low Voltage Disconnect (1) Set Battery Cables DISTRIBUTION UNIT (Lists 5 and 6) List BF: (13) GMT Fuse Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LF: (13) GMT Fuse Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points List NF: (13) GMT Fuse Load Positions NO Low Voltage Disconnect (3) Battery Landing Points List BC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Battery Disconnect (LVBD) (3) Battery Landing Points List LC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions Low Voltage Load Disconnect (LVLD) (3) Battery Landing Points List NC: (5) GMT Fuse Load Positions (4) Bullet-Nose Circuit Breaker Load Positions NO Low Voltage Disconnect (3) Battery Landing Points List BA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions Low Voltage Battery Disconnect (LVBD) List LA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions Low Voltage Load Disconnect (LVLD) List NA: (5) GMT Fuse Load Positions (2) Bullet-Nose Circuit Breaker Load Positions (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions NO Low Voltage Disconnect Page 7 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Other List Options List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions (for use w/ Lists BC, LC, NC, BA, LA, and NA) List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions (for use w/ Lists BF, LF, and NF) List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions (for use w/ Lists BF, LF, and NF) List 65: Shelf Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 66: Battery Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 67: Battery Side Battery Cables (for use w/ Lists BF, LF, NF, BC, LC, and NC) List 71: Optional External Battery Cables with Anderson Connector for (1) Battery String (for use w/ Lists BG and NG) List 72: Optional External Battery Cables with Anderson Connector for (2) Battery Strings (for use w/ Lists BG and NG) List 89: Relay Rack Earthquake Anchor Kit List 90: Temperature Probe (9 ft.) List 91: Temperature Probe (30 ft.) List 93: Battery Tray (23”) List 94: Battery Tray (19”) List KG: GMT Fuse Load Distribution Panel Accessory Options SEE ALSO Relay Racks System Overview Mounting and Adapter Kits Table of Contents Distribution Devices Ordering Information AC Input Cables and Line Cords List Descriptions Ring & Distribution Module Accessory Descriptions External Battery Disconnect Unit Specifications SiteWeb™ TEMP Temperature Concentrator Physical Size Information Anderson Battery Connector Related Documentation Digital Input/Relay Output Cables Replacement Modules Wiring Notes Wiring Illustrations Page 8 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 TABLE OF CONTENTS Ordering Information System Overview Picture List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation SYSTEM OVERVIEW.................................................................................................................................................1 58213660001.........................................................................................................................................................5 TABLE OF CONTENTS .............................................................................................................................................9 ORDERING INFORMATION ....................................................................................................................................12 List Options........................................................................................................................................................12 Accessory Options ............................................................................................................................................16 LIST DESCRIPTIONS ..............................................................................................................................................17 List 1: 1RU High by 19” Wide Shelf...............................................................................................................17 List 2: 1RU High by 23” Wide Shelf...............................................................................................................18 List 5: 2RU High by 19” Wide Shelf...............................................................................................................19 List 6: 2RU High by 23” Wide Shelf...............................................................................................................20 Rectifier Module (500W), P/N 1R48500 .........................................................................................................21 Rectifier Module (1000W), P/N 1R481000 .....................................................................................................21 ACU+ (Advanced Control Unit Plus), P/N 1M820BNA ..................................................................................21 SCU+ (Standard Control Unit Plus), P/N 1M521BNA ....................................................................................22 List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ...................................22 List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions .................................22 List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions ...................................23 List 65: Shelf Side Battery Cables, P/N 540814 ...........................................................................................23 List 66: Battery Side Battery Cables, P/N 540954 ........................................................................................23 List 67: Battery Cable, P/N 545709 ................................................................................................................24 List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493 ....................................................................................................................................................24 List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery Strings, P/N 535124 .......................................................................................................................................24 List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ........................................................................25 List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) .........................................................................................................................................25 List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) .......................................................................................................................................25 List 93: Battery Tray for 23” Relay Rack .......................................................................................................26 List 94: Battery Tray for 19” Relay Rack .......................................................................................................29 List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD).........................................................................................................................................32 List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load Disconnect (LVLD) .........................................................................................................................................33 List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect......................................................................................................................................................34 List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) .....................................................35 List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD).........................................................36 List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect ............................................................................37 Page 9 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD).........................................................................................................................................38 List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) .........................................................................................................................................39 List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect......................................................................................................................................................40 List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD).........................................................................................................................................41 List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect......................................................................................................................................................42 List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ...............................................43 ACCESSORY DESCRIPTIONS ...............................................................................................................................44 Relay Racks .......................................................................................................................................................44 Mounting and Adapter Kits ..............................................................................................................................45 Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 ....................................................................45 Optional 19” to 23” Rack Adapter Kit, P/N 540993 ........................................................................................45 Optional 19” to 23” Rack Adapter Kit, P/N 545728 ........................................................................................45 Rear Battery Cable Exit Kit P/N 547645 ........................................................................................................45 Distribution Devices ..........................................................................................................................................46 GMT Load Distribution Fuses ........................................................................................................................46 Bullet Nose-Type Circuit Breakers .................................................................................................................47 Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 .................................................................48 Optional Bulk Output Busbar, P/N 535015 ....................................................................................................48 AC Input Cables and Line Cords .....................................................................................................................49 AC Input Cable Assembly, P/N 535232 .........................................................................................................49 AC Input Line Cord, 208/240VAC, P/N 540946 .............................................................................................49 AC Input Line Cord, 208/240VAC, P/N 545616 .............................................................................................50 AC Input Line Cord, 120VAC, P/N 545252 ....................................................................................................50 AC Input Line Cord, 120VAC, P/N 545478 ....................................................................................................51 AC Input Line Cord, 120VAC, P/N 545479 ....................................................................................................51 AC Input Line Cord, 208/240VAC, P/N 545480 .............................................................................................52 AC Input Line Cord, 120VAC, P/N 545481 ....................................................................................................52 AC Input Line Cord, 208/240VAC, P/N 545553 .............................................................................................53 AC Input Line Cord, 120VAC, P/N 547525 ....................................................................................................53 AC Input Line Cord, 120VAC, P/N 548457 ....................................................................................................54 AP6C57EA/EB Ring & Distribution Module ....................................................................................................55 External Battery Disconnect Unit, P/N 535282 ...............................................................................................57 NETSURE™ 201BC Battery Cabinet (Spec. No. 541434) ..................................................................................58 NETSURE™ 211BC Battery Cabinet (Spec. No. 545534) ..................................................................................59 NETSURE™ 211BC Battery Cabinet (Spec. No. 545506) ..................................................................................60 Site Web™ TEMP Temperature Concentrator (P/N 547490) .........................................................................61 Anderson Battery Connector ...........................................................................................................................62 Digital Input and Relay Output Cables ............................................................................................................63 Replacement Modules ......................................................................................................................................63 Wiring Notes ......................................................................................................................................................64 Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................64 AC Input Branch Circuit Protection and Wiring ..............................................................................................64 External Alarm and Monitoring Wiring............................................................................................................64 Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) ....................................................................65 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) ..............................................................65 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA).................................................66 Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ...................................66 Page 10 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) ..........................................66 Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................68 CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) ............................................................68 Input Battery Wiring (List BG and NG) ...........................................................................................................68 Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) ..................................68 Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) .............................................69 Wiring Illustrations ............................................................................................................................................70 Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................70 AC Input Wiring (Lists 1 and 2) ......................................................................................................................71 AC Input Wiring (Lists 5 and 6) ......................................................................................................................72 External Alarm and Monitoring Wiring (Lists 1 and 2)....................................................................................73 External Alarm and Monitoring Wiring (Lists 5 and 6)....................................................................................74 Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) ................79 Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) ..........80 Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6, List 5 shown) ..................................................................................................................................................81 Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................82 Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown) .........................................................................................................................83 Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)............................................................84 Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................85 Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) .............................................86 Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) .........................................87 SPECIFICATIONS....................................................................................................................................................88 1. System ...........................................................................................................................................................88 1.1 Environmental Ratings .............................................................................................................................88 1.2 Compliance Information ...........................................................................................................................88 1.3 Standard Features....................................................................................................................................89 2. Distribution Unit ............................................................................................................................................90 2.1 List BG and NG in a List 1 and List 2 Shelf ..............................................................................................90 2.2 List 5 and 6 Shelves .................................................................................................................................90 3. GMT Load Distribution Fuse Panel (List KG) .............................................................................................91 3.1 Electrical ...................................................................................................................................................91 PHYSICAL SIZE INFORMATION ............................................................................................................................92 Overall Dimensions – List 1 .............................................................................................................................92 Overall Dimensions – List 2 .............................................................................................................................93 Overall Dimensions – List 5 .............................................................................................................................94 Overall Dimensions – List 6 .............................................................................................................................95 Overall Dimensions – List KG ..........................................................................................................................96 Overall Dimensions – 19” Battery Tray ...........................................................................................................97 Overall Dimensions – 23” Battery Tray ...........................................................................................................98 BATTERY MANUFACTURER INFORMATION ......................................................................................................99 RELATED DOCUMENTATION................................................................................................................................99 REVISION RECORD ..............................................................................................................................................100 Page 11 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home ORDERING INFORMATION List Options Order the following by the items Part Number as specified in the following table. When viewing electronically, click on the link to jump to the detailed description page. List Number Part Number Description Shelf Options 1 58213660001 2 58213660002 5 58213660005 6 58213660006 1RU 19” Mini Shelf. (Shelf requires one [1] AC Feed) (Houses up to [2] Rectifiers, Controller, and Distribution Unit.) 1RU 23” Mini Shelf. (Shelf requires one [1] AC Feed) (Houses up to [3] Rectifiers, Controller, and Distribution Unit.) 2RU 19” Mini Shelf. (Shelf requires two [2] AC Feeds) (Houses up to [4] Rectifiers, Controller, and Distribution Unit.) 2RU 23” Mini Shelf. (Shelf requires two [2] AC Feeds) (Houses up to [6] Rectifiers, Controller, and Distribution Unit.) Controller Options Order by P/N Order by P/N 1M820BNA ACU+ (Advanced Control Unit Plus) 1M521BNA SCU+ (Standard Control Unit Plus) Rectifier Options Order by P/N Order by P/N 1R48500 Model R48-500 Rectifier Module (500W). 1R481000 Model R48-1000 Rectifier Module (1000W). Distribution Unit Options Distribution Unit w/ BF 582136600BF • (1) Battery Shunt • (3) Battery Connection Points • (13) GMT Fuse Load Positions (5) 0A to 15A (8) 0A to 10A • Low Voltage Battery Disconnect (LVBD) FOR USE WITH LISTS 5 AND 6. Page 12 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) List Number SAG582136600 Issue AF, December 9, 2010 Part Number Description Distribution Unit Options (Cont’d) Distribution Unit w/ LF 582136600LF • (1) Battery Shunt • (3) Battery Connection Points • (13) GMT Fuse Load Positions (5) 0A to 15A (8) 0A to 10A • Low Voltage Load Disconnect (LVLD) FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ NF 582136600NF • (1) Battery Shunt • (3) Battery Connection Points • (13) GMT Fuse Load Positions (5) 0A to 15A (8) 0A to 10A • NO Low Voltage Disconnect FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ BC 582136600BC • (1) Battery Shunt • (3) Battery Connection Points • (5) GMT Fuse Load Positions (0A to 10A) • (4) Bullet-Nose Circuit Breaker Load Positions • Low Voltage Battery Disconnect (LVBD) FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ LC 582136600LC • (1) Battery Shunt • (3) Battery Connection Points • (5) GMT Fuse Load Positions (0A to 10A) • (4) Bullet-Nose Circuit Breaker Load Positions • Low Voltage Load Disconnect (LVLD) FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ NC 582136600NC • (1) Battery Shunt • (3) Battery Connection Points • (5) GMT Fuse Load Positions (0A to 10A) • (4) Bullet-Nose Circuit Breaker Load Positions • NO Low Voltage Disconnect FOR USE WITH LISTS 5 AND 6. Page 13 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 List Number System Application Guide Spec. No. 582136600 (Model 211NGFB) Part Number Description Distribution Unit Options (Cont’d) Distribution Unit w/ BA 582136600BA • (1) Battery Shunt • (5) GMT Fuse Load Positions (0A to 10A) • (2) Bullet-Nose Circuit Breaker Load Positions • (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions • Low Voltage Battery Disconnect (LVBD) FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ LA 582136600LA • (1) Battery Shunt • (5) GMT Fuse Load Positions (0A to 10A) • (2) Bullet-Nose Circuit Breaker Load Positions • (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions • Low Voltage Load Disconnect (LVLD) FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ NA 582136600NA • (1) Battery Shunt • (5) GMT Fuse Load Positions (0A to 10A) • (2) Bullet-Nose Circuit Breaker Load Positions • (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions • NO Low Voltage Disconnect FOR USE WITH LISTS 5 AND 6. Distribution Unit w/ BG 582136600BG • (1) Set Battery Cables • (10) GMT Fuse Load Positions (0A to 15A) • Low Voltage Battery Disconnect (LVBD) FOR USE WITH LISTS 1 AND 2. Distribution Unit w/ NG 582136600NG • (1) Set Battery Cables • (10) GMT Fuse Load Positions (0A to 15A) • NO Low Voltage Disconnect FOR USE WITH LISTS 1 AND 2. Other Options 60 58213660060 61 58213660061 Five (5) Load Lead Assemblies for 10A GMT Fuse Positions. Leads are 12’ long and 16 AWG. For use with Lists BC, LC, NC, BA, LA, and NA. Eight (8) Load Lead Assemblies for 10A GMT Fuses Positions. Leads are 12’ long and 16 AWG. For use with Lists BF, LF, and NF. Page 14 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) List Number SAG582136600 Issue AF, December 9, 2010 Part Number Description Other Options (Cont’d) 62 58213660062 65 58213660065 66 58213660066 67 58213660067 71 58213600071 72 58213600072 89 90 91 58213660089 58213660090 58213660091 Five (5) Load Lead Assemblies for 15A GMT Fuse Positions. Leads are 12’ long and 14 AWG. For use with Lists BF, LF, and NF. Shelf Side Battery Cables. Cables are 3’ long and 2 AWG terminated in a 2-position Anderson connector. Remaining end terminated in lugs for connection to shelf. For use with Lists BF, LF, NF, BC, LC, and NC. Battery Side Battery Cables. Cables are 12’ long and 2 AWG terminated in a 2-position Anderson connector. Remaining end un-terminated for connection to batteries. For use with Lists BF, LF, NF, BC, LC, and NC. Output Cable to Battery Cabinet – cables are 4’ long and 8 AWG terminated in a 2-position Anderson connector. Remaining end terminated in lugs for connection to shelf. For Use with Lists BC, LC, NC, BF, LF, and NF. Optional External Battery Cables with Anderson Connector for (1) Battery String. For use with Lists BG and NG. Optional External Battery Cables with Anderson Connector for (2) Battery Strings. For use with Lists BG and NG. Relay Rack Earthquake Anchor Kit. Temperature Probe, 9 ft long. Temperature Probe, 30 ft. long. 93 58213660093 Battery Tray (23”). 94 58213660094 Battery Tray (19”). Distribution Panel w/ KG 582136600KG • (20) GMT Fuse Load Positions (0A to 15A) • NO Low Voltage Disconnect FOR USE WITH LISTS 5 AND 6. Page 15 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Accessory Options Order the following by the items Part Number as specified in the following table. When viewing electronically, click on the link to jump to the detailed description page. Description Part Number Relay Racks Distribution Devices AC Input Cables and Line Cords Ring & Distribution Module External Battery Disconnect Unit Battery Cabinet SiteWeb™ TEMP Temperature Concentrator See ACCESSORY DESCRIPTIONS Section Anderson Battery Connector Digital Input and Relay Output Cables Replacement Modules Wiring Notes Wiring Illustrations Page 16 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home LIST DESCRIPTIONS List 1: 1RU High by 19” Wide Shelf Features ♦ Consists of a 1RU high by 19” wide shelf. ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed. ♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf. A mating half is available. ♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 1 shelf holds up to two (2) Rectifier Modules. Ordering Notes 1) Order List 1 as required. Also order the following as required. 2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file for your site. 3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 1 shelf requires one (1) AC Input Cable or Line Cord. 5) Order one (1) Distribution Unit (List BG or NG) per shelf. 6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71 or 72. 7) Order Relay Rack Anchor Kit(s) (List 89) as required. 8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient air temperature. 9) Order Battery Trays (List 94) as required. 10) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 17 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 2: 1RU High by 23” Wide Shelf Features ♦ Consists of a 1RU high by 23” wide shelf. ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed. ♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf. A mating half is available. ♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 2 shelf holds up to three (3) Rectifier Modules. Ordering Notes 1) Order List 2 as required. Also order the following as required. 2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file for your site. 3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 2 shelf requires one (1) AC Input Cable or Line Cord. 5) Order one (1) Distribution Unit (List BG or NG) per shelf. 6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71 or 72. 7) Order Relay Rack Anchor Kit(s) (List 89) as required. 8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient air temperature. 9) Order Battery Trays (List 93) as required. 10) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 18 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List 5: 2RU High by 19” Wide Shelf Features ♦ Consists of a 2RU high by 19” wide shelf. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds. ♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs. ♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available. ♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 5 shelf holds up to four (4) Rectifier Modules. Ordering Notes 1) Order List 5 as required. Also order the following as required. 2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also specify the appropriate configuration file for your site. 3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 5 shelf requires two (2) AC Input Cables or Line Cords. 5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf. 6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered. Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions. 7) Order one (1) List KG Distribution Fuse Panel per shelf, as required. 8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66) for each List BC, LC, NC, BF, LF, or NF ordered. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order one (1) for each battery cabinet feed required. 11) Order Relay Rack Anchor Kit(s) (List 89) as required. 12) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient air temperature. 13) Order Battery Trays (List 94) as required. 14) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 15) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 16) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 17) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 18) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 19) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 19 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 6: 2RU High by 23” Wide Shelf Features ♦ Consists of a 2RU high by 23” wide shelf. ♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds. ♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs. ♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is available. A “Digital Input Cable” (shelf side and customer side) is also available. ♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit. Restrictions Each List 6 shelf holds up to six (6) Rectifier Modules. Ordering Notes 1) Order List 6 as required. Also order the following as required. 2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also specify the appropriate configuration file for your site. 3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W). 4) Order AC Input Cables or Line Cords as required. Note that each List 6 shelf requires two (2) AC Input Cables or Line Cords. 5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf. 6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered. Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 61 for each List BF, LF, or NF ordered. Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions. Order one (1) List 62 for each List BF, LF, or NF ordered. Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions. 7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required. 8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66) for each List BC, LC, NC, BF, LF, or NF ordered. 9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 10) Order Relay Rack Anchor Kit(s) (List 89) as required. 11) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge Temperature Compensation feature, the other to monitor ambient air temperature. 12) Order Battery Trays (List 93) as required. 13) Order Relay Racks per ACCESSORY DESCRIPTIONS section. 14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section. 16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section. 17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section. 18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 20 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Rectifier Module (500W), P/N 1R48500 Features ♦ Provides one (1) Model R48-500, Spec. No. 1R48500, 500 watt / 48 volt Rectifier Module. Restrictions Each List 1 Shelf holds up to two (2) Rectifier Modules. Each List 2 Shelf holds up to three (3) Rectifier Modules. Each List 5 Shelf holds up to four (4) Rectifier Modules. Each List 6 Shelf holds up to six (6) Rectifier Modules. DO NOT install different wattage Rectifier Modules in same shelf. Ordering Notes 1) Order by P/N (1R48500) as required. Rectifier Module (1000W), P/N 1R481000 Features ♦ Provides one (1) Model R48-1000, Spec. No. 1R481000, 1000 watt / 48 volt Rectifier Module. Restrictions Each List 1 Shelf holds up to two (2) Rectifier Modules. Each List 2 Shelf holds up to three (3) Rectifier Modules. Each List 5 Shelf holds up to four (4) Rectifier Modules. Each List 6 Shelf holds up to six (6) Rectifier Modules. DO NOT install different wattage Rectifier Modules in same shelf. Ordering Notes 1) Order by P/N (1R481000) as required. ACU+ (Advanced Control Unit Plus), P/N 1M820BNA Features ♦ Provides the ACU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions ACU+ is not available in List 1 or List 2 shelves. Each List 5 or List 6 shelf must contain one (1) SCU+ or one (1) ACU+ Controller. Ordering Notes 1) Order one (1) ACU+ (P/N 1M820BMA) or one (1) SCU+ Controller (P/N 1M521BNA) or for each shelf. Page 21 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) SCU+ (Standard Control Unit Plus), P/N 1M521BNA Home Features ♦ Provides the SCU+ Controller. ♦ Factory programmed with the configuration file specified when ordered. Restrictions Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller. Ordering Notes 1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N 1M820BMA) for each shelf. For the SCU+ controller, specify also one of the following configurations. Note: For custom SCU+ configurations, contact Emerson. a) List 1 and 2 with Low Voltage Disconnect: 545304. b) List 1 and 2 without Low Voltage Disconnect: 545305. c) List 5 and 6 with Low Voltage Disconnect: 545298. d) List 5 and 6 without Low Voltage Disconnect: 545299. List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions Features ♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads. Restrictions For use with List BC, LC, NC, BA, LA, and NA Distribution units only. Ordering Notes 1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit. Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206. List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions Features ♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 10A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left unterminated at the remaining end for connection into customer loads. Restrictions For use with List BF, LF, and NF Distribution units only. Ordering Notes 1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit. Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206. Page 22 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions Home Features ♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector to plug into the system’s 15A GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the remaining end for connection into customer loads. Restrictions For use with List BF, LF, and NF Distribution units only. Ordering Notes 1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit. Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988. List 65: Shelf Side Battery Cables, P/N 540814 Features ♦ Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 66). Remaining end terminated in lugs for connection to shelf. Restrictions For use with List BF, LF, NF, BC, LC, and NC Distribution units only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. List 66: Battery Side Battery Cables, P/N 540954 Features ♦ Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red SB120 Anderson connector (mates with the Anderson connector on List 65). Remaining end un-terminated for connection to batteries. Restrictions For use with List BF, LF, NF, BC, LC, and NC only. Ordering Notes 1) Order as required. Each shelf provides landings for up to three (3) battery strings. Page 23 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List 67: Battery Cable, P/N 545709 Features ♦ Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson connector on the battery side. Remaining end terminated in lugs for connection to shelf. Restrictions For use with P/N 541434, P/N 545534 or P/N 545506 Battery cabinets only. For use with List BF, LF, NF, BC, LC, and NC Distribution units only. Ordering Notes 1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered. 2) Order one (1) for each battery cabinet feed required. List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String, P/N 545493 Features ♦ Provides two (2) 6’ long, 8 AWG, battery cables terminated in a Red SB50 Anderson connector for connecting one (1) battery string to the system. ♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains two (2) unterminated cables for connection into a customer battery string. Restrictions For use with List BG and NG only. Ordering Notes 1) Order if required. 2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery Strings, P/N 535124 Features ♦ Provides four (4) 6’ long, 10 AWG, battery cables terminated in a Red SB50 Anderson connector for connecting two (2) battery strings to the system. ♦ One end of the assembly connects to the Anderson connector factory wired to the shelf’s battery connection points, and the other end contains four (4) unterminated cables for connection into customer battery strings. Restrictions For use with List BG and NG Distribution units only. Ordering Notes 1) Order if required. 2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 24 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 Home Features ♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor. Ordering Notes 1) Order as required. List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long) Features ♦ Two Temperature Probes can be connected to this system. One to provide Battery Charge Temperature Compensation and the other to monitor ambient air temperature. Each probe plugs into the IB2 Board. ♦ The Temperature Probe used for Battery Charge Temperature Compensation is mounted near the battery to sense battery ambient temperature. This allows the SCU to automatically increase or decrease the output voltage of the system to maintain battery float current as battery ambient temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. ♦ The Temperature Probe consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04118247 (9 feet long) is shipped loose. Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247. 2) For a Temperature Probe with a longer cable see List 91. List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long) Features ♦ Two Temperature Probes can be connected to this system. One to provide Battery Charge Temperature Compensation and the other to monitor ambient air temperature. Each probe plugs into the IB2 Board. ♦ The Temperature Probe used for Battery Charge Temperature Compensation is mounted near the battery to sense battery ambient temperature. This allows the SCU to automatically increase or decrease the output voltage of the system to maintain battery float current as battery ambient temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. ♦ The Temperature Probe consists of two pieces that plug together to make a complete probe. When ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped loose. Page 25 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Ordering Notes 1) Order up to two (2) Temperature Probes for each shelf, as required. Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740. 2) For a Temperature Probe with a shorter cable see List 90. List 93: Battery Tray for 23” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 23” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that two battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). ♦ P/N 362736700 P/N 528496 P/N 362736700 Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 23” relay racks only. Maximum number of List 93’s per rack is three (3). A single List 93 must mount at bottom of rack. Multiple List 93’s must mount starting at bottom of rack and working upward. P/N 540842 Ordering Notes 1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions above. 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. The following tables list batteries recommended for use with List 93. Page 26 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Battery Tray P/N 528496 Manufacturer* Model Emerson Network Power P/N GNB Marathon GNB Marathon Northstar Northstar Deka Unigy I C&D Douglas Douglas M12V125FT M12V155FT NSB110FT NSB170FT 12AVR-150ET FA 12-150F DGS12-150F DSN12-170F -112795 --122018 FA12150 125453 -- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 125 155 110 167 150 150 150 170.8 4.90 X 22.00 X 11.15 4.90 X 22.00 X 11.15 4.92 X 22.05 X 8.94 4.92 X 22.05 X 12.60 4.90 X 22.00 X 11.75 4.92 X 21.97 X 12.70 4.90 X 22.00 X 12.70 4.92 X 22.05 X 12.60 7U 7U 7U 8U 8U 8U 8U 8U 105 119 91.3 131 115 131 137 129.6 * See Battery Manufacturer Information located at the end of this document. Battery Tray P/N 540842 Manufacturer* Model Emerson Network Power P/N GNB Marathon GNB Marathon GNB Marathon Northstar Northstar Douglas Douglas M12V35FT M12V50FT M12V60FT NSB40FT** NSB60FT** DGS12-25F DGS12-50F -------- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 35 47 59 38.1 57.9 25 50 4.21 X 11.02 X 7.44 4.21 X 11.02 X 9.09 4.21 X 11.02 X 10.35 3.80 X 9.80 X 8.20 4.20 X 11.30 X 10.40 3.94 X 10.80 X 7.60 3.94 X 10.80 X 11.60 6U 7U 7U 6U 7U 6U 8U 31 40 51 34 49 27 48 * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See table above. Page 27 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 5) Battery lugs are provided, as specified from the following table. Battery Specified GNB Marathon M12V125FT GNB Marathon M12V155FT Northstar NSB110FT Northstar NSB170FT Deka Unigy I 12AVR-150ET C&D FA 12-150F Douglas DGS12-150F Douglas DSN12-170F GNB Marathon M12V35FT GNB Marathon M12V50FT GNB Marathon M12V60FT Northstar NSB40FT Northstar NSB60FT Douglas DGS12-25F Douglas DGS12-50F Battery Lug Kit Part Number (Kit provides two lugs for one tray.) Lists 5 and 6 Lists 1 and 2 528234 540989 (for use with 10 AWG wire and List 72) 528236 545581 (for use with 8 AWG wire and List 71) 528234 6) Specify with or without battery disconnect circuit breakers. If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from the following table. Also specify breaker mounting on left side of tray, right side of tray, or remote mounting. Note: All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. Also order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Ampere Rating P/N Electrical/Mechanical Trip1 (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. Ampere Rating P/N Electrical/Mechanical Trip1 (Black Handle) 35 40 50 60 70 75 100 256693500 256693900 256694300 256694700 256695100 256695500 256695900 Page 28 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List 94: Battery Tray for 19” Relay Rack Features ♦ Provides one battery tray that mounts four (4) 12V front terminal Valve Regulated Lead Acid (VRLA) batteries. Batteries are configured as one (1) 48V string. ♦ Accepts various VRLA batteries. See Ordering Notes below. ♦ See Overall Dimensions - 19” Battery Tray under PHYSICAL SIZE INFORMATION for battery tray dimensions and typical arrangement. Note that three battery trays are available to accommodate the various size batteries listed in the Ordering Notes tables. ♦ Trays can be ordered with or without battery disconnect circuit breakers. When circuit breakers are ordered, one is provided in the -48V lead of each battery string (1 circuit breaker per tray). ♦ P/N 362736700 P/N 541036 P/N 362736700 Battery cables are available terminated at the power system end in an Anderson connector. Battery lugs are available for the remaining end. Restrictions For 19” relay racks only. Maximum number of List 94’s per rack is three (3). A single List 94 must mount at bottom of rack. Multiple List 94’s must mount starting at bottom of rack and working upward. P/N 541034 Ordering Notes 1) Order multiples of List 94 for more than one (1) battery tray. See Restrictions above. P/N 362736700 2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required. 3) Order batteries separately. The following tables list batteries recommended for use with List 94. P/N 540841 Page 29 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Battery Tray P/N 541036 Manufacturer* Model Emerson Network Power P/N Northstar Northstar GNB Marathon NSB90FT NSB100FT M12V90FT ---- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 90 100 90 4.25 X 15.59 X 10.04 4.25 X 15.59 X 11.03 4.13 X 15.55 X 10.63 7U 7U 7U 70.6 78.5 70 * See Battery Manufacturer Information located at the end of this document. Battery Tray P/N 541034 Manufacturer* Model Emerson Network Power P/N GNB Marathon M12V105FT -- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 105 4.33 X 20.12 X 9.37 7U 79 * See Battery Manufacturer Information located at the end of this document. Battery Tray P/N 540841 Manufacturer* Model Emerson Network Power P/N GNB Marathon GNB Marathon GNB Marathon Northstar Northstar Douglas Douglas M12V35FT M12V50FT M12V60FT NSB40FT** NSB60FT** DGS12-25F DGS12-50F -------- Rated 8-Hr. Capacity (Ah) Dimension WxLxH (Inches) Required Tray Spacing Weight (per battery) (lbs) 35 47 59 38.1 57.9 25 50 4.21 X 11.02 X 7.44 4.21 X 11.02 X 9.09 4.21 X 11.02 X 10.35 3.80 X 9.80 X 8.20 4.20 X 11.30 X 10.40 3.94 X 10.80 X 7.60 3.94 X 10.80 X 11.60 6U 7U 7U 6U 7U 6U 8U 31 40 51 34 49 27 48 * See Battery Manufacturer Information located at the end of this document. ** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information. 4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required for battery clearance. See table above. Page 30 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home 5) Battery lugs are provided, as specified from the following table. Battery Specified Northstar NSB90FT Northstar NSB100FT GNB Marathon M12V90FT GNB Marathon M12V105FT GNB Marathon M12V35FT GNB Marathon M12V50FT GNB Marathon M12V60FT Northstar NSB40FT Northstar NSB60FT Douglas DGS12-25F Douglas DGS12-50F Battery Lug Kit Part Number (Kit provides two lugs for one tray.) Lists 5 and 6 Lists 1 and 2 540989 (for use with 10 AWG wire and List 72) 528234 545581 (for use with 8 AWG wire and List 71) 6) Specify with or without battery disconnect circuit breakers. If ordering List 94 with circuit breakers, order one (1) circuit breaker per List 94 from the following table. Also specify breaker mounting on left side of tray, right side of tray, or remote mounting. Note: All List 94 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the first tray ordered. Also order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3) battery disconnect circuit breakers. Ampere Rating P/N Electrical/Mechanical Trip1 (Black Handle) 1 256690300 3 256690700 5 256691100 10 256691500 15 256691900 20 256692300 25 256692700 30 256693100 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. Ampere Rating P/N Electrical/Mechanical Trip1 (Black Handle) 35 40 50 60 70 75 100 256693500 256693900 256694300 256694700 256695100 256695500 256695900 Page 31 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value. In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value. In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. GMT fuses load bottom to top / highest to lowest value. In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. Page 32 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load Disconnect (LVLD) Features ♦ Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value. In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value. In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. GMT fuses load bottom to top / highest to lowest value. In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. Page 33 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, and thirteen (13) GMT fuse load distribution positions. ♦ Five (5) 0A to 15A GMT fuse load distribution positions. ♦ Eight (8) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C (+149°F). In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value. In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value. In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. GMT fuses load bottom to top / highest to lowest value. In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for the 15A fuse blocks. 5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. Page 34 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 35 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD) Features ♦ Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List LC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 36 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, (3) battery connection points, four (4) bullet nose-type circuit breaker load distribution positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required. List 65 and List 67 are factory installed. 5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 37 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 38 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load Disconnect (LVLD) Features ♦ Provides a Distribution Unit with Low Voltage Load Disconnect (LVLD), a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 39 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, two (2) bullet nose-type circuit breaker load distribution positions, two (2) bullet nose-type circuit breaker battery disconnect positions, five (5) GMT fuse load distribution positions. ♦ Five (5) 0A to 10A GMT fuse load distribution positions. Restrictions For use with List 5 and 6 only. Maximum distribution current is 72A at @ +65°C (+149°F) and 100A @ +40°C (+104°F). The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A. Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F). Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. There are no restrictions in an ambient of +40°C (+104°F). See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for the 10A fuse blocks. 4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section. Page 40 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery Disconnect (LVBD) Features ♦ Provides a Distribution Unit with Low Voltage Battery Disconnect (LVBD), battery cables, and ten (10) GMT fuse load distribution positions (15A maximum). ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Ten (10) 0A to 15A GMT fuse load distribution positions. Restrictions For use with List 1 and 2 only. The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71 or 72. 4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 41 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage Disconnect Features ♦ Provides a Distribution Unit w/out low voltage disconnect, a battery shunt, battery cables, and ten (10) GMT fuse load distribution positions (15A maximum). ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Ten (10) 0A to 15A GMT fuse load distribution positions. Restrictions For use with List 1 and 2 only. The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A fuses. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf. Also order the following as required. 2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section. 3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per List 71 or 72. 4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section. Page 42 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions Features ♦ 1U-high GMT fuse panel that provides Single Load Distribution (-48V) ♦ Provides twenty (20) 0A to 15A GMT fuse load distribution positions. ♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C ♦ Factory mounted and connected to List 5 or 6 shelf. Restrictions For use with List 5 and 6 only. Mounts only immediately above List 5 or 6 shelf. For use with List BA, BC, BF, NA, NC and NF only. Maximum distribution current is 80A. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Ordering Notes 1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required. Also order the following as required. 2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section. Page 43 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home ACCESSORY DESCRIPTIONS Relay Racks Features ♦ The following relay racks are available. Restrictions Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory mounted in the relay rack. Ordering Notes 1) Order from relay racks listed in Table 1. Part Number Available Mounting Positions (1RU = 1-3/4”) Size Notes 23” Relay Racks 543156 51-3/8” H x 23” W 28RU Welded 543161 6’0” H x 23” W 37RU Welded 543160 7’0” H x 23” W 45RU Seismic (Note 1) 543162 7’0” H x 23” W 45RU Welded 543163 7’6” H x 23” W 48RU Welded 543164 8’0” H x 23” W 51RU Welded 19” Relay Racks 525003 51-3/8” H x 19” W 28RU Welded 534653 6’0" H x 19” W 37RU Seismic (Note 1) 524961 6’0” H x 19” W 37RU Welded 534654 6’6” H x 19” W 41RU Seismic (Note 1) 534651 6’6” H x 19” W 41RU Welded 528183 7’0” H x 19” W 45RU Seismic (Note 1) 524988 7’0” H x 19”W 45RU Welded 524963 7’6” H x 19” W 48RU Welded 534652 8’0" H x 19” W 51RU Welded Note 1: Complies with Bellcore Seismic Zone 4 requirements. Table 1 Available Relay Racks Page 44 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Mounting and Adapter Kits Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 Features ♦ Allows for horizontal or vertical wall mounting. Restrictions For use with List 1 or 2 only. Customer must supply mounting fasteners for attaching the Wall Mount Bracket to the wall. Ordering Notes 1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2) P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to the shelf. Optional 19” to 23” Rack Adapter Kit, P/N 540993 Features ♦ Allows for 23” relay rack mounting Restrictions For use with List 1 only. Ordering Notes 1) Order P/N 540993, which consists of two (2) P/N 540994 adapters and four (4) 12-24 x 1/”2 thread forming screws. Optional 19” to 23” Rack Adapter Kit, P/N 545728 Features ♦ Allows for 23” relay rack mounting Restrictions For use with List 5 only. Ordering Notes 1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread forming screws. Rear Battery Cable Exit Kit P/N 547645 Features ♦ Provides 12” battery cables exiting rear of shelf Restrictions For use with List 5 only. Ordering Notes 1) For use with Battery Cabinets only. Page 45 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Distribution Devices GMT Load Distribution Fuses Features ♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8) 0-10A GMT load distribution fuses. ♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses. ♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses. ♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses. Restrictions When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere fuses, for which load should not exceed 70% of device rating. See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only), Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only), and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order GMT fuses per Table 2. Ampere Rating P/N Fuse Color 18/100 GMT-A 248610301 -- 1/4 248610200 Violet 1/2 248610300 Red 3/4 248610500 Brown 1-1/3 248610700 White 2 248610800 Orange 3 248610900 Blue 5 248611000 Green 7-1/2 248611300 Black-White 10 248611200 Red-White 15 248611500 Red-Blue Replacement Dummy Fuse 248872600 --- Replacement Safety Fuse Cover Lists BF, LF, NF, BC, LC, NC, BA, LA, NA and KG 102774 Lists BG and NG 248898700 -- Table 2 GMT Fuses Page 46 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Bullet Nose-Type Circuit Breakers Features ♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit breakers. ♦ Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit breakers and up to two (2) bullet nose-type load distribution circuit breakers. Restrictions See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section. See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) and Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) under WIRING NOTES for additional wiring restrictions. Ordering Notes 1) Order circuit breakers per Table 3. P/N Ampere Rating 1 3 5 10 15 20 25 30 35 40 45 50 60 70 75 80 100 Electrical Trip1 (White Handle) Electrical/ Mechanical Trip2 (Black Handle) 102272 101596 102273 101597 102274 101598 102275 101599 102276 101600 102277 101601 102278 101602 102279 101603 102280 101604 102281 101605 121998 121997 102282 101606 102283 101607 102284 101608 102285 101609 121996 121995 102286 101610 See Table 6 for recommended wire sizes and lugs. Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical trip condition only. 2 Provides an alarm during an electrical or manual trip condition. Note that Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers. Table 3 Bullet Nose-Type Circuit Breakers Page 47 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 Features ♦ Factory installed in a List BC, LC, NC, BA, LA, and NA Distribution Unit. ♦ Provides six (6) 0A to 15A GMT fuse load distribution positions. ♦ Screw clamp type load and load return terminals provided. ♦ Includes six (6) dummy fuses equipped with safety fuse covers. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA. Terminal block wire size capacity: 24 to 14 AWG. Requires two (2) bullet device mounting positions. Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position. Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device. See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS section. Factory installed only. Ordering Notes 1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required. 2) Order GMT fuses as required per Table 2. Optional Bulk Output Busbar, P/N 535015 Features ♦ Each Bulk Output Busbar installs in a single circuit breaker position in a List BC, LC, NC, BA, LA, and NA Distribution Unit. Restrictions For use with Lists BC, LC, NC, BA, LA, and NA. Ordering Notes 3) Order by P/N 535015 as required. Page 48 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home AC Input Cables and Line Cords AC Input Cable Assembly, P/N 535232 Features ♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and the remaining end un-terminated. Restrictions Rated for 30A. For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 208/240VAC, P/N 540946 Features ♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 49 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 545616 Features ♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-30P twist-lock plug. Restrictions For 208/240 VAC only (rated for 30A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 120VAC, P/N 545252 Features ♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 50 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home AC Input Line Cord, 120VAC, P/N 545478 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 equipped with R48-500 Rectifier Modules. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. AC Input Line Cord, 120VAC, P/N 545479 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-15P twist-lock plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 equipped with R48-500 Rectifier Modules. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 51 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 208/240VAC, P/N 545480 Features ♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-15P twist-lock plug. Restrictions For 240 VAC only (rated for 15A at 208/240VAC). For use with List 1 and 5. For use with List 2 and 6 with R48-500 Rectifiers. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. AC Input Line Cord, 120VAC, P/N 545481 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-20P twist-lock plug. Restrictions For 120 VAC only (rated for 20A at 120VAC). For use with List 1 and 5. For use with List 2 and 6 with R48-500 Rectifiers. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 52 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home AC Input Line Cord, 208/240VAC, P/N 545553 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L6-20P twist-lock plug. Restrictions For 240 VAC only (rated for 20A at 208/240VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. AC Input Line Cord, 120VAC, P/N 547525 Features ♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA L5-30P twist-lock plug. Restrictions For 120 VAC only (rated for 30A at 120VAC). For use with List 1, 2, 5, and 6. Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered. Page 53 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Line Cord, 120VAC, P/N 548457 Features ♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord; ♦ terminated on one end with a Molex plug which mates with AC input receptacle on the Power/Distribution Shelf, ♦ and on the remaining end with a NEMA 5-15P plug. Restrictions For 120 VAC only (rated for 15A at 120VAC). For use with List 1 and 5 with R48-500 Rectifiers. Each List 1 requires one (1) AC Input Cable Assembly/Line Cord. Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords. Ordering Notes 1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered. 2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered. Page 54 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home AP6C57EA/EB Ring & Distribution Module Features ♦ When used with List 5 or 6, this module is designed to supply a filtered and regulated –48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems (such as SLC-96 or SLC Series-5) requiring up to 45 A of load capacity. ♦ Designed to mount in a 23” relay rack, the module is one rack unit high, with 5” front projection. ♦ Includes two (2) 50VA ringers with automatic transfer capability (N+1 redundancy). ♦ Provides 35 DC distribution fuse positions, configured in five groups of seven, feeding five channel banks. Includes 35 dummy fuses. ♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution fuses are included with each cable assembly ordered. ♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic pair, with surge protection. ♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete specifications. Restrictions Cannot be used with Distribution units List BF, LF, or NF. Ordering Notes 1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626). 2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order AP6C57EB (A7000796). 3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable assemblies can be mixed. ORDERING CODE DESCRIPTION P7000858 Cable assy for one SLC96 channel bank (8 ft.) P7001139 Cable assy for one SLC96 channel bank (20 ft.) P7000859 Cable assy for one SLC5 channel bank (8 ft.) P7001136 Cable assy for one SLC5 channel bank (20 ft.) P7000937* Cable assy for one channel bank, generic applications (8 ft.) *Note: Each channel bank position on the panel has a maximum capacity of 11A. 4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect between a power shelf and the DC input terminals of one (1) Ring & Distribution Module. Page 55 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home 5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following table. ORDERING CODE 547646 547647 DESCRIPTION Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use a flat washer, not provided.) 6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the following table. ORDERING CODE DESCRIPTION A0885525 A0885530 A0885531 A0885532 A7000627 (AP8C55AA) 1.33A Alarm SAN-O Fuse 3A Alarm SAN-O Fuse 5A Alarm SAN-O Fuse 10A Alarm SAN-O Fuse 50VA Ring Generator Page 56 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home External Battery Disconnect Unit, P/N 535282 Features ♦ Battery Disconnect Unit with mounting tabs. ♦ Two 1/4-20 studs w/hardware provided for installation of single hole battery lugs. ♦ One (10’ long) alarm lead provided. Restrictions Circuit breakers are ordered separately. Maximum number of Battery Disconnect Units per system is three (3). Ordering Notes 1) Order by P/N 535282 as required. 2) Order a circuit breaker for each Battery Disconnect Unit from Table 4. 3) Also order the following lug kits for each battery disconnect circuit breaker ordered: 545581(for use with 8 AWG wire and List 71) or 540989 (for use with 10 AWG wire and List 72) and 541031 (wire with lugs for connection from battery disconnect to battery string). 4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery Disconnect Units are to be used (daisy-chains the alarm terminal of up to three [3] Battery Disconnect Units). (Section of alarm lead between Battery Disconnect Units is 30”, section of alarm lead between Battery Disconnect Unit and system’s alarm terminal is 84”.) P/N P/N Ampere Rating Electrical/Mechanical Trip1 (Black Handle) Yellow Jumper/Alarm Lead (P/N 524384) (for use when more than one Battery Disconnect Units are ordered) Ampere Rating Electrical/Mechanical Trip1 (Black Handle) 1 256690300 35 3 256690700 40 5 256691100 50 10 256691500 60 15 256691900 70 20 256692300 75 25 256692700 100 30 256693100 Circuit Breaker Alarm Operation: 1 Provides an alarm during an electrical or manual trip condition. 256693500 256693900 256694300 256694700 256695100 256695500 256695900 Table 4 Battery Disconnect Unit Circuit Breakers Page 57 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NETSURE™ 201BC Battery Cabinet (Spec. No. 541434) Features ♦ The NETSURE™ 201BC Battery Cabinet can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Order Notes) into the Battery Cabinet provided. ♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 541434 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Hawker Fiamm EaglePicher EaglePicher Enersys SBS 15 12SLA12 HE-12V7.7FR HE-12V12.7FR NP18-12FR 139091 139092 139094 139093 139774 14 12 6.9 11.6* 16 * 12.50 12.35 5.94 9.68 13.60 * 10Hr rate 3) When ordering 139774 batteries, also order 545427 Battery Connection kit. Page 58 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home NETSURE™ 211BC Battery Cabinet (Spec. No. 545534) Features ♦ The NETSURE™ 211BC Battery Cabinet can be mounted in a 19” or 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. ♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545534 as required. 2) Also order two (2) batteries per Battery Cabinet per the following table. Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys C&D / Dynasty SBS B10 TEL12-30 140553 140455 38 30.5 28.20 26.70 Page 59 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home NETSURE™ 211BC Battery Cabinet (Spec. No. 545506) Features ♦ The NETSURE™ 211BC Battery Cabinet can be mounted in a 23” nominal relay rack, or mounted to a suitable wall. ♦ The Battery Cabinet contains one (1) 40 ampere battery disconnect circuit breaker. ♦ Battery circuit breaker alarm leads are provided to tie into the power system’s alarm circuit. ♦ The Battery Cabinet is equipped with a battery cable terminated in an Anderson connector. ♦ Cables to connect the batteries (as specified in the table under Ordering Notes) into the Battery Cabinet provided. ♦ Battery Cabinets can be paralleled to provide greater reserve time. Battery cabinets contain a second Anderson battery connector for plugging one cabinet into another. Ordering Notes 1) Order by Spec. No. 545506 as required. 2) Also order four (4) batteries per Battery Cabinet per the following table. Battery Manufacturer Manufacturer P/N Emerson P/N Capacity Amp-Hours (8Hr rate) Weight (lb) per Battery Enersys Enersys C&D/ Dynasty C&D/ Dynasty SBS B10 SBS 40 TEL12-30 TEL12-45 140553 140581 140455 140454 38 38 30.5 46 28.20 28.00 26.70 26.70 Page 60 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Site Web™ TEMP Temperature Concentrator (P/N 547490) Features ♦ Allows for multiple temperature probes to be used for temperature compensation. Compensation can be based on highest probe temperature or average probe temperature. ♦ Provides (8) temperature probe inputs per SiteWeb™ TEMP. ♦ Can be cascaded up to (8) SiteWeb™ TEMP modules, connecting up to 64 temperature probes. ♦ Provides CAN output for ACU+ and analog output for all controllers. Restrictions Concentrator needs to plug into analog temp input on IB2 board. Ordering Notes 1) Order P/N 547490. 2) Order up to (8) List 90 or 91 temperature probes for each concentrator. Page 61 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Anderson Battery Connector Features ♦ Includes the components necessary to assemble an Anderson connector onto a battery cable. Restrictions Appropriate battery post mating lugs must be ordered separately. Ordering Notes Order Anderson connector housings and lugs per the following table. Single Part Number for a Housing and Lugs Emerson P/N Anderson P/N For a single string (spare for List 71). Consists of two (2) lugs (Anderson P/N 5952) and one (1) Red Connector (Anderson P/N 992G1). Lugs accept 8 AWG wire. Allows for the connection of one (1) battery string (both polarities) (one wire per lug). (not available in kit form, order components individually per the second half of this table) (not available in kit form, order components individually per the second half of this table) For a double string (spare for List 72). Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red Connector (Anderson P/N 992G1). Lugs accept 6 AWG wires. Allows for the connection of two (2) battery strings (both polarities) (two [10 AWG] wires per lug). 133196 6331G1 Emerson P/N Anderson P/N 138922 247109602 992G1 5952 Description Individual Housing and Lugs Part Numbers (spare for List 1, 2, and 71) Description Housing Lug (accepts 8 AWG wire) (2 required per housing) Page 62 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Digital Input and Relay Output Cables Features ♦ Lists 5 and 6: Two sets of customer wiring cables are available. One set for the Digital Inputs and another set for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The other half has a mating connector on one end and is un-terminated on the other end. ♦ Lists 1 and 2: One set of customer wiring cables is available (Digital Inputs and Relay Outputs). One half of the cable is provided and factory connected in the shelf. The other half (includes mating connector on one end and un-terminated on the other end) must be ordered separately. Ordering Notes 1) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (shelf side) is provided and factory connected in the List 5 and 6 shelf, and P/N 541309 or P/N 545644 (customer side) must be ordered separately. For the Digital Inputs Cable, order both P/Ns 541310 (shelf side) and P/N 541311 (customer side). Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only. 2) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (shelf side) is provided and factory connected in the List 1 and 2 shelf and P/N 545495 (customer side) must be ordered separately. Replacement Modules Ordering Notes 1) Refer to Table 5. Item Part Number 500W Rectifier Module 1000W Rectifier Module Rectifier Module Fan 1R48500 1R481000 32010156 1M521BNA* * Also specify the appropriate SCU+ configuration file. Refer to the configuration file label on your existing SCU+ Controller. 1M820BNA* * Also specify the appropriate ACU+ configuration file. Refer to the configuration file label on your existing ACU+ Controller. Order per List 90 (9 ft. long) or List 91 (30 Ft. long) (or if only one piece of the two piece probe is needed, see the List 90 or 91 description for part numbers) SCU+ Controller Module ACU+ Controller Module Temperature Probe Table 5 Replacement Module Part Numbers Page 63 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Wiring Notes Refer also to the next section, Wiring Illustrations. Illustrations Shelf Frame Grounding Stud (List 1 and 2 Only) Features ♦ An M5 frame grounding stud with hardware is provided on the rear of the shelf Restrictions Recommended frame ground wire size is 6 AWG. AC Input Branch Circuit Protection and Wiring Features ♦ Each shelf contains one (1) or two (2) side mounted plug-in AC input connector(s). ♦ AC Input Cable Assemblies/Line Cords are available that plug into the shelf’s AC input connector. Restrictions Lists 1 and 2 require one (1) AC input branch circuit. The AC input branch circuit feeds two (2) (List 1) or three (3) (List 2) rectifiers. Refer to the following table for recommended branch circuit protection. Lists 5 and 6 require two (2) AC input branch circuits. Each AC input branch circuit feeds two (2) (List 5) or three (3) (List 6) rectifiers. Refer to the following table for recommended branch circuit protection. AC Input Branch Circuit Protection System 208/240VAC Input 120VAC Input 500W Rect. 1000W Rect. 500W Rect. 1000W Rect. 58213660001 58213660005 (2-Rectifiers per AC Feed) 15A 15A 15A 20A 58213660002 58213660006 (3-Rectifiers per AC Feed) 15A 20A 20A 25A / 30A For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this document. External Alarm and Monitoring Wiring Features ♦ List 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board mounted inside the shelf. One half of a Relay Outputs Cable is factory connected to these terminals. The other half (includes mating connector on one end and un-terminated on the other end) is ordered separately. If ordered, one half of a Digital Input Cable is factory connected Page 64 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 to these terminals. The other half includes a mating connector on one end and is un-terminated on the other end. ♦ Home List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is factory connected to these terminals. The other half (includes mating connector on one end and unterminated on the other end) is ordered separately. Restrictions Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft. 18-20 AWG for Loop Lengths Over 200 ft. Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) Features ♦ Load and load return leads are connected to a screw-type terminal block located on the front of the Distribution Unit. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Terminal block wire size capacity is 20 to 12 AWG. Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) Features ♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of fuse amperage sizes, and that two different types of receptacles are provided. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Ordering Notes 1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111 [reel]. 2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco 350537-3 [reel]. Page 65 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA) Home Features ♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Ordering Notes 1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated at the remaining end for connection into customer loads. * Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111 [reel]. Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) Features ♦ Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse Module. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Terminal block wire size capacity is 24 to 14 AWG. Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) Features ♦ Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire, recommended to use a customer supplied flat washer between the lug and the nut supplied on the termination. Ordering Notes 1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6. Page 66 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home 2) For other available lugs, refer to drawings 031110100 through 031110300. Circuit Breaker Amperage 1, 3, 5, 10A 15A 20A 25A 30A 35A 40A 45A 50A 60A 70A 75A 80A 90A 100A 2-hole 1 2 3 4 5 6 Recm 90°C Wire Size (1) 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG (2) Loop Length (feet) 37 (3, 4, 5) 58 (3, 4, 5) 93 (3, 4, 5) 148 (3, 4, 5) 24 (3, 4) --------- 39 (3, 4, 5) 29 (3, 4) -------- 62 (3, 4, 5) 46 (3, 4, 5) 37 (3, 4,) 31 (3, 4) ------ 99 (3, 4, 5) 74 (3, 4, 5) 59 (3, 4, 5) 49 (3, 4, 5) 42 (3, 4) 37 (3, 4) 33 (3, 4) 29 (3) -- 245390100 4 AWG 2 AWG 236 (3, 4, 5) -- -- 157 (3, 4, 5) 118 (3, 4, 5) 94 (3, 4, 5) 78 (3, 4, 5) 67 (3, 4, 5) 59 (3, 4, 5) 52 (3, 4) 47 (3, 4,) 39 (3, 4) ----107 (3, 4) 94 (3, 4) 83 (3, 4) 75 (3, 4) 62 (3, 4) 53 (3, 4) 50 (3, 4) 47 (3, 4) 41 (3) -- --------99 (3, 4) 85 (3, 4) 79 (3, 4) 74 (3, 4) 66 (3, 4) 59 (3, 4) 245346800 245346900 Recommended Crimp Lug (6) 245390100 245390100 245346600 245346500 Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and 65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads. Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature. Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature. Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature. Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping information. Table 6 Recommended Battery and Load Distribution Wire Size and Lug Selection (Bullet Nose-Type Circuit Breaker) Page 67 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Load Distribution Wiring (GMT Fuses) (List KG) Features ♦ Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front of the assembly. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. Terminal block wire size capacity is 26 to 14 AWG. CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) Features ♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring. Restrictions Recommended CO ground wire size is 6 AWG. Recommended lug is 245346500 (2-hole, 10-32 clearance holes, 5/8” centers). Input Battery Wiring (List BG and NG) Features ♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952]. ♦ Additional strings of battery may be connected to the system using the available battery cable kits (see List 71 and List 72). Restrictions Battery leads are NOT internally fused. Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) Features ♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes. All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire, Page 68 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 recommended to use a customer supplied flat washer between the lug and the nut supplied on the termination. Home Ordering Notes 1) The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 6. 2) For other available lugs, refer to drawings 031110100 through 031110300. Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) Features ♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Restrictions All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied. Maximum size of wire to be connected to a single lug position is 2 AWG. Maximum lug width, 0.61 inches. Ordering Notes 1) Battery wire size varies depending on load, therefore no specific information is provided for wire size. When making connections, observe correct polarity. 2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables. Page 69 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Wiring Illustrations Shelf Frame Grounding Stud (List 1 and 2 Only) Rear View Connect a frame grounding lead to this stud, if required. Stud is a Size M5. Page 70 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home AC Input Wiring (Lists 1 and 2) List 1 List 2 Front Front Rectifiers are numbered left to right as viewed from the front. AC input connections are AC input connections are made using the supplied AC made using the supplied AC input cable assemblies/ input cable assemblies/ line cords connected here. line cords connected here. Front View AC Input Cable Assembly AC Input Line Cord Blue* White* Green/Yellow* Green* Brown* Black* L2-N Ground L1 * color of AC Input Cable Assembly/Line Cord lead. ENSURE THE PROPER VOLTAGE AC BRANCH CIRCUIT AND LINE CORDS WITH THE APPROPRIATE PLUG ARE USED FOR YOUR APPLICATION. Nominal 120/208/240V AC Input for Rectifier Module: List 1 (19” Shelf): #1 and #2 List 2 (23” Shelf): #1, #2, and # 3 500W Rectifier: 120/208/240 VAC Input 1000W Rectifier: 120/208/240 VAC Input * AC Input Cable Assembly / Line Cords Part Number 545232 540946 545252 545478 545479 545480 545481 545553 545616 547525 548457 Customer End unterminated L6-30P L5-30P 5-15P L5-15P L6-15P L5-20P L6-20P L6-30P L5-30P 5-15P (List 1 & 2) (List 1 & 2) (List 1 & 2) (List 1 w/ R48-500) (List 1 w/ R48-500) (List 1; List 2 w/ R48-500) (List 1; List 2 w/ R48-500) (List 1 & 2) (List 1 & 2) (List 1 & 2) (List 1 w/ R48-500) “WARNING - HIGH LEAKAGE CURRENT.” An industrial style plug is required when providing power to three (3) or more Rectifier Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard. Page 71 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home AC Input Wiring (Lists 5 and 6) List 5 List 6 Front Front 4 AC input connections are made using the supplied AC input cable assemblies/ line cords connected here. 2 3 6 1 AC input connections are made using the supplied AC input cable assemblies/ line cords connected here. 5 4 2 3 1 Rectifiers are numbered as shown above Rectifiers are numbered as shown above Front View ENSURE THE PROPER VOLTAGE AC BRANCH CIRCUIT AND LINE CORDS WITH THE APPROPRIATE PLUG ARE USED FOR YOUR APPLICATION. L2-N Ground L1 500W Rectifier: 120/208/240 VAC Input 1000W Rectifier: 120/208/240 VAC Input Blue* White* Green/Yellow* Green* Brown* Black* Nominal 120/208/240V AC Input for Rectifier Module: List 5 (19” Shelf): #3 and #4 List 6 (23” Shelf): #3, #4, and #6 * AC Input Cable Assembly / Line Cords Customer End unterminated L6-30P L5-30P 5-15P L5-15P L6-15P L5-20P L6-20P L6-30P L5-30P 5-15P AC Input Line Cord * color of AC Input Cable Assembly/Line Cord lead. Nominal 120/208/240V AC Input for Rectifier Module: List 5 (19” Shelf): #1 and #2 List 6 (23” Shelf): #1, #2, and #5 Part Number 545232 540946 545252 545478 545479 545480 545481 545553 545616 547525 548457 AC Input Cable Assembly (List 5 & 6) (List 5 & 6) (List 5 & 6) (List 5 w/ R48-500) (List 5 w/ R48-500) (List 5; List 6 w/ R48-500) (List 5; List 6 w/ R48-500) (List 5 & 6) (List 5 & 6) (List 5 & 6) (List 5 w/ R48-500) “WARNING - HIGH LEAKAGE CURRENT.” An industrial style plug is required when providing power to three (3) or more Rectifier Modules with a flexible cord. Plug and outlet types 1-15, 2-15, 2-20, 5-15, and 5-20 as specified in IEC 60083 are considered to be NON-INDUSTRIAL within the meaning of this standard. Page 72 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home External Alarm and Monitoring Wiring (Lists 1 and 2) SCU+ Controller Notes Relay Output/Digital Input Cable P/N 545494 is factory connected to terminals. Mating half (w/ unterminated ends) available, P/N 545495. Digital Input 1 is factory wired to Load Breaker / Fuse Alarm. Digital Input 2 default is External Battery Disconnect Circuit Breaker Alarm. SCU+ Controller (Top View) A factory-connected jumper supplies +BAT (Battery Return) to the positive side of Digital Input #2. When ordered, Temperature Probe leads are factory connected to SCU+ Connector Board located in the Distribution Unit. These are labeled T1 and T2. NC = Normally Closed COM = Common NO = Normally Open (48/24V) Digital Inputs Major Summary Alarm Relay Outputs Minor Summary Alarm All relay contacts are shown with the relay deenergized. Page 73 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home External Alarm and Monitoring Wiring (Lists 5 and 6) Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed only. Notes Relay Output Cable P/N 541308 is factory connected to Relay Output terminals. Mating half (w/ unterminated ends) available, P/N 541309. If ordered, Digital Input Cable P/N 541310 is factory connected to Digital Input terminals. Mating half (w/ unterminated ends) available, P/N 541311. Digital Input 1 is factory wired to Load Breaker / Fuse Alarm. Digital Input 2 is reserved for External Battery Breaker Alarm. A factory connected jumper supplies +BAT (Battery Return) to the positive side of digitla Input #2. Digital Inputs 3 through 7 are User defined. Digital Input 8 is reserved for Emergency Stop. Digital Input 9 is not available in this system. When ordered, Temperature Probe leads are factory connected to J11 and J12. These are labeled 1 and 2. NC = Normally Closed COM = Common NO = Normally Open All relay contacts are shown with the relay deenergized. 7 J9 RS-485 Connection for SM AC, SM BAT, SITEWEB™ BRC, or SM IO Supervisory Modules. See module data sheets. (Functional with ACU+ Only.) SCU+/ACU+ Customer Interface Board Relay Outputs 5 3 J8 J7 Digital Inputs 1* J6 NO C NC NO C NC NO C NC NO C NC 5 3 1 5 3 1 5 3 1 5 3 1 8 7 6 5 4 3 2 1 J5 J4 J3 5 3 1 5 3 1 5 3 1 + 6 4 2 6 4 2 6 4 2 6 4 2 NO C NC NO C NC NO C NC NO C NC 8 6 4 6 4 2 6 4 2 6 4 2 J12 Temp. Probe #2 or SiteWeb™ TEMP J11 Temp. Probe #1 or SiteWeb™ TEMP 2 ON SW1 Switch settings must be in this position SCU+/ACU+ Customer Interface Board to interface with the SCU+/ACU+ Controller (Top View) * The SCU+/ACU+ relay assigned to "Major Summary" alarm (relay 1 by default) operates in the "Fail Safe Mode". "Fail Safe Mode" means Relay 1 is de-energized during an alarm condition, opening contacts between C and NO terminals, and closing contacts between C and NC terminals. The remaining seven (7) relays of the SCU+/ACU+ energize during an alarm condition, closing contacts between C and NO terminals, and opening contacts between C and NC terminals. Page 74 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Yellow Alarm Lead (P/N 535294) (factory wired to circuit breaker alarm terminal) Alarm Wiring to a Single External Battery Disconnect Unit Procedure 1. Connect YELLOW lead exiting top of Battery Disconnect Unit per table below. Remove quick connect terminal first. The YELLOW lead is factory connected to circuit breaker “C (Common)” alarm terminal in the Battery Disconnect Unit. 2. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 3. Connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker “NC (Normally Closed)” alarm terminal. Torque to 84 in-lbs using supplied hardware To To Power System Battery Connect to shelf per table below. Remove quick connect terminal first. EXTERNAL BATTERY DISCONNECT UNIT (Side cover removed in illustration to show wiring details.) External Battery Disconnect Circuit Breaker Alarm Input: A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2. BREAKER ALARM CONNECTION Shelf List Alarm Cable on shelf CONNECT YELLOW WIRE TO: 1 or 2 545495 NO YES Must order Cable 545495 R-BK Lead of 545495. Splice and heat shrink tubing included with 545495 5 or 6 541311 NO YES Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2) O-R Lead of 541311. Splice and heat shrink tubing included with 541311 Page 75 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Yellow Jumper/Alarm Lead (P/N 524384) (Ordered separately and supplied loose. Must be wired by the customer to each circuit breaker “C (Common)” alarm terminal) Yellow Alarm Lead (P/N 535294) (factory wired to circuit breaker alarm terminal) * No terminal on 524384 jumper Connect to shelf per table below. REMOVE COMPLETELY FROM ALL BATTERY DISCONNECT UNITS AND DISCARD. see previous page see previous page see previous page 1st EXTERNAL BATTERY DISCONNECT UNIT (Side cover removed in illustration to show wiring details.) 2nd EXTERNAL BATTERY DISCONNECT UNIT Alarm Wiring to (2) to (3) External Battery Disconnect Units 3rd EXTERNAL BATTERY DISCONNECT UNIT Procedure 1. Completely remove YELLOW lead exiting top of ALL Battery Disconnect Units and discard. 2. Connect separately ordered YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals in ALL Battery Disconnect Units. Connect remaining end per table below. 3. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 4. In ALL Battery Disconnect Units, connect loose end of Jumper factory connected to bottom terminal on circuit breaker to circuit breaker “NC (Normally Closed)” alarm terminal. External Battery Disconnect Circuit Breaker Alarm Input: A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2. BREAKER ALARM CONNECTION Shelf List Alarm Cable on shelf CONNECT YELLOW WIRE TO: 1 or 2 545495 NO YES Must order Cable 545495 R-BK Lead of 545495. Splice and heat shrink tubing included with 545495 5 or 6 541311 NO YES Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2) O-R Lead of 541311. Splice and heat shrink tubing included with 541311 Page 76 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Yellow Jumper/Alarm Lead (P/N 524384) (Ordered separately and supplied loose. Must be wired by the customer to each circuit breaker “C (Common)” alarm terminal) * No terminal on 524384 jumper Connect to shelf per table below. see previous page see previous page see previous page 1st BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (Side cover removed in illustration to show wiring details.) 2nd BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (if furnished) Alarm Wiring to Battery Disconnect Circuit Breakers when (1) to (3) Battery Trays are Used 3rd BATTERY TRAY BATTERY DISCONNECT CIRCUIT BREAKER (if furnished) Procedure 1. 2. Connect kit-supplied YELLOW jumper/alarm lead (P/N 524384) to circuit breaker “C (Common)” alarm terminals on ALL Battery Disconnect Circuit Breakers. Connect remaining per table below. There is NO connection to the circuit breaker “NO (Normally Open)” alarm terminal. 3. On ALL Battery Disconnect circuit breakers, there should be a factory connected Jumper connected from the bottom terminal on the circuit breaker to the circuit breaker “NC (Normally Closed)” alarm terminal. External Battery Disconnect Circuit Breaker Alarm Input: A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2. BREAKER ALARM CONNECTION Shelf List Alarm Cable on shelf CONNECT YELLOW WIRE TO: 1 or 2 545495 NO YES Must order Cable 545495 R-BK Lead of 545495. Splice and heat shrink tubing included with 545495 5 or 6 541311 NO YES Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2) O-R Lead of 541311. Splice and heat shrink tubing included with 541311 Page 77 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Yellow Jumper/Alarm Lead (P/O Cabinet) Orange Wire on 541434 not used Connect to shelf per table below. alarm wire alarm wire 1st BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER alarm wire 2nd BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER Alarm Wiring to Battery Cabinets 3rd BATTERY CABINET BATTERY DISCONNECT CIRCUIT BREAKER Procedure 1. Remove quick connect terminal from YELLOW battery cabinet alarm lead. 2. Wire per table below. External Battery Disconnect Circuit Breaker Alarm Input: A battery disconnect circuit breaker alarm is activated when the circuit breaker is in the OFF position, and provides -48VDC to Digital Input # 2. BREAKER ALARM CONNECTION Shelf List Alarm Cable on shelf CONNECT YELLOW WIRE TO: 1 or 2 545495 NO YES Must order Cable 545495 R-BK Lead of 545495. Splice and heat shrink tubing included with 545495 5 or 6 541311 NO YES Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2) O-R Lead of 541311. Splice and heat shrink tubing included with 541311 Page 78 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) Connect to Front Terminal Block Load Return Leads -48V Distribution Leads Terminal Fuse Position Load Return Load (-48V) 1 2 3 4 5 6 7 8 9 10 1 3 5 7 9 11 13 15 17 19 2 4 6 8 10 12 14 16 18 20 Page 79 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) Front Load Distribution Leads Enter Here GMT Fuse Positions (Max. 15A) GMT Fuse Load Distribution Leads Connect Here Mating Connectors and 12' Leads provided with List 62. -48V on Left (Black Lead), Return on Right (White Lead) GMT Fuse Positions (Max. 10A) GMT Fuse Load Distribution Leads Connect Here Mating Connectors and 12' Leads provided with List 61. -48V on Left (Black Lead), Return on Right (White Lead) Page 80 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6, List 5 shown) Front Load Distribution Leads Enter Here GMT Fuse Positions GMT Fuse Load Distribution Leads Connect Here Mating Connectors and 12' Leads provided with List 60. -48V on Left (Black Lead), Return on Right (White Lead); as viewed from side with door closed. Page 81 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) -48V Distribution Leads Load Return Leads Page 82 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed in a List 5 or 6, List 5 shown) Front Circuit Breaker Load Distribution and CO Ground Leads Enter Here Load Distribution Circuit Breakers Front Portion of shelf removed in illustration for clarity. Leads are brought into side of shelf, and tools to secure lugs from front of shelf. Load Return Leads CO Ground Lead -48V Load Distribution Leads 10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs. Page 83 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown) Front CO Ground, Circuit Breaker Load Distribution, and Circuit Breaker Battery Leads Enter Here Load Distribution Circuit Breakers Battery Disconnect Circuit Breakers Front Portion of shelf removed in illustration for clarity. Leads are brought into side of shelf, and tools to secure lugs from front of shelf. OBSERVE PROPER POLARITY WHEN MAKING BATTERY CONNECTIONS Battery Return Leads Load Return Leads CO Ground Lead -48V Load Distribution Leads -48V Battery Leads 10-32 studs (w/ hardware) on 5/8" centers for installation of customer provided two hole lugs. Page 84 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 Home "B" Side Load Returns #1 - #5 #6 - #10 Connections are made to screw compression terminal blocks. Wire size range is 26 to 14 AWG. "B" Side Loads #1 - #5 "A" Side Loads #6 - #10 "A" Side Load Returns #1 - #5 #6 - #10 "A" Side Loads #1 - #5 Load Distribution Wiring (GMT Fuses) (List KG) "B" Side Loads #6 - #10 System Application Guide Spec. No. 582136600 (Model 211NGFB) Page 85 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) Rear View Connect battery leads to factory installed leads exiting the shelf here. These leads are factory terminated in an Anderson connector. A mating half to this connector is provided for connection to customer battery leads. External battery cables are also available to connect 1 (List 71) or 2 (List 72) strings of batteries to the system. OBSERVE PROPER POLARITY. LEADS AND CONNECTORS ARE MARKED WITH A PLUS AND MINUS SYMBOL OR TEXT. Minus (-48V Battery) Plus (Battery Return) Page 86 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) List NF Distribution Unit shown. List BF, LF, BC, LC, and NC similar. Front List 65 provides 3' long, 2 AWG, battery cables terminated on one end with lugs to connect to the input battery landings and on the other end with an Anderson connector. Distribution Unit List 66 provides 12' long, 2 AWG, battery cables terminated on one end in an Anderson connector and left unterminated at the remaining end for connection of battery lugs. Battery, Battery Return, and CO Ground Leads Enter Here List BC, LC, and NC Distribution Unit Battery: 1/4-20 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs. CO Ground: 10-32 studs (w/hardware) on 5/8" centers for installation of customer provided two hole lugs. CO Ground Lead List BF, LF, and NF Distribution Unit Right Side Battery Return Leads CO Ground Lead OBSERVE PROPER POLARITY WHEN MAKING BATTERY CONNECTIONS Right Side Battery Return Leads -48 Battery Leads -48 Battery Leads Page 87 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home SPECIFICATIONS Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000) supplied with your Power System. For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B) supplied with your Power System. For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (Cdrawing) supplied with your Power System. 1. SYSTEM 1.1 Environmental Ratings 1.1.1 Operating Ambient Temperature Range (Specification Compliant): (A) -40°C (-40°F) to +65°C (+149°F) with derating output. (B) -40°C (-40°F) to +40°C (+104°F) with full power performance. 1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F). 1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of 0% to 90%, non-condensing. 1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m). 1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-combustible surface. This product must be located in a Controlled Environment with access to Craftspersons only. This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally controlled electronic equipment enclosure). This product is intended to be connected to the common bonding network in a Network Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure). Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack and 2' for the rear of the relay rack. Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4” multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf). Mounting angles are positioned for a 5-inch front projection mounting only. 1.1.6 1.2 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient Temperature Range stated above. Compliance Information 1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6. Note: This level of protection is a widely used standard for telecommunications power equipment. As with all such equipment, it is the end user's responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes/categories stated for the equipment. Page 88 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) 1.2.2 SAG582136600 Issue AF, December 9, 2010 Home Safety Compliance: (A) This unit meets the requirements of UL 60950, Standard for Information Technology Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data Processing, or Information Processing Equipment. (B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified by UL ("c UR") as a Component Type Power Supply. 1.2.3 EMC and Safety: (A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and Immunity requirements as specified in GR-1089-Core Issue 4. EMC Emissions EN 55022: 1998 CFR 47 – Part 15 GR-1089 Issue 4 Test Level Conducted Class B Radiated Class B Immunity GR-1089 Issue 4 EN 61000-4-2 Electrostatic Discharge EN 61000-4-4 Electric Fast Transients Radiated Immunity Conducted Immunity Surge IEEE C62.41 8kV / 15kV 0.25kV / 0.5kV 8.5V/m 89dBuA 2kV / 6kV SAFETY EN 60950-1: 2001 1.2.4 Safety of Information Technology Equipment, including Electrical Business Equipment NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS compliance reports. For NETSURE™ 211NGFB to remain compliant during a fan failure condition, the backup battery connection must be utilized to provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50% output power. If no backup battery connection is used, the system must operate with a redundant module installed. 1.3 Standard Features 1.3.1 AC Input Connections: AC input cable assemblies and line cords are available. (A) List 1 and 2: Mounted to the side of the shelf is an AC input housing with one (1) plug-in connector for one (1) AC input feed. (B) List 5 and 6: Mounted to the side of the shelf is an AC input housing with two (2) plug-in connectors for two (2) AC input feeds. 1.3.2 Battery Connections: Battery cables are available. (A) List 1 and 2: Battery leads are connected to an Anderson connector exiting the rear of the unit. (B) Lists 5 and 6: Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf. Page 89 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 1.3.3 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Load Connections: (A) List 1 and 2: Load and load return leads are connected to a screw-type terminal block located on the front of the shelf. (B) Lists 5 and 6: Load distribution (circuit breakers, if furnished) and load return leads terminated in two-hole lugs are connected to threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. 1.3.4 Alarm and Monitoring Connections: Customer wiring cables are available. (A) List 1 and 2: Relay output and digital input leads are connected to screw-type terminal blocks located on the SCU+ located inside the shelf. These leads enter the rear of the shelf. (B) Lists 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on the Customer Interface Board located inside the shelf. These leads enter the right side (as viewed from the front) of the shelf and are accessible from the front of the shelf. 1.3.5 Dimensions and Weights: Refer to the PHYSICAL SIZE INFORMATION section of this document. 2. DISTRIBUTION UNIT 2.1 List BG and NG in a List 1 and List 2 Shelf 2.1.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document. 2.1.2 Battery Connection (A) 8 AWG cables (48” long) factory wired and terminated in an Anderson type connector. 2.1.3 Standard Features (A) Provides ten (10) GMT load fuse positions (18/100A to 15A fuses). (B) Provides front access screw-clamp type load and load return terminals. (C) Provides the connections for system battery input. (D) Equipped with an optional Low Voltage Battery Disconnect (LVBD) contactor. (E) Provides a load fuse alarm indicator. 2.2 List 5 and 6 Shelves 2.2.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document. 2.2.2 Standard Features (A) Lists BC, LC, and NC: Provides thirteen (13) GMT load distribution fuse positions. (B) Lists BF, LF, and NF: Provides four (4) load distribution circuit breaker positions, and five (5) GMT load distribution fuse positions. (C) Lists BA, LA, and NA: Provides two (2) battery disconnect circuit breaker positions. Provides two (2) load distribution circuit breaker positions. Provides five (5) GMT load distribution fuse positions. (D) Dimensions: 83mm (H) x 157mm (W) x 274mm (D). 3.25” (H) x 6.2” (W) x 10.8” (D). (E) Weight (w/out LVD): 3 kg (7 lbs). Page 90 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 3. GMT LOAD DISTRIBUTION FUSE PANEL (LIST KG) 3.1 Home Electrical 3.1.1 Input/Output Voltage: Nominal –48VDC 3.1.2 Current: 40A per side, 80A total (Note: The split (A/B) input bus feature provided on panel is factory connected for single input only.) 3.1.3 Fuse Alarm Circuit: If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System Controller fuse alarm. Page 91 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home PHYSICAL SIZE INFORMATION Overall Dimensions – List 1 Top View Left Side View 17.3 18.3 19.0 5 0.5 12 Right Side View Front View 1.25 Rear View Bottom View 1.72 0.23 Notes: 1. All dimensions are in inches, unless otherwise specified. 2. Weight in LBS. Net: 16 Shipping: 3. Finish: Front Panels are Gray Shelf is Galvaneal. Page 92 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Overall Dimensions – List 2 Top View Left Side View 21.3 22.3 23.0 5 0.5 12 Right Side View Front View 1.25 Rear View Bottom View 1.72 0.23 Notes: 1. All dimensions are in inches, unless otherwise specified. 2. Weight in LBS. Net: 20.5 Shipping: 3. Finish: Front Panels are Gray Shelf is Galvaneal. Page 93 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Overall Dimensions – List 5 Top View Left Side View 17.3 18.3 19.0 19.4 Front View 5 12 0.5 Right Side View 3.00 Rear View Bottom View 3.46 0.23 Notes: 1. All dimensions are in inches, unless otherwise specified. 2. Weight in LBS. Net: 30 Shipping: 3. Finish: Front Panels are Gray Shelf is Galvaneal. Page 94 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Overall Dimensions – List 6 Top View Left Side View 21.3 22.3 23.0 23.4 5 12 0.5 Right Side View Front View 3.46 3.00 Rear View Bottom View 0.23 Notes: 1. All dimensions are in inches, unless otherwise specified. 2. Weight in LBS. Net: 39 Shipping: 3. Finish: Front Panels are Gray Shelf is Galvaneal. Page 95 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Overall Dimensions – List KG Notes: 1. Dimensions in inches unless otherwise specified. 2. Finish: Gray 3. Weight: Net: Shipping: 8.31 10.00 5.05 See Mounting Angle Detail Top View 0.92 17.25 Left Side View 1.75 Right Side View 18.25 19.25 22.31 23.25 Front View Bottom View R 0.125 (TYP) 0.235 0.125 Mounting Angle Detail 0.500 0.500 0.125 0.235 1.250 1.250 0.125 0.125 Page 96 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 Home Overall Dimensions – 19” Battery Tray Optional Battery Disconnect Circuit Breakers (Shown on Right Side, Available on Either Side) A See Note 3 10.50 12.25 14.00 (as ordered) ISO View Front View Notes: 1. All dimensions are in inches, unless otherwise specified. 2. P/N 541036 tray shown. P/Ns 541034 and 540841 similar. 3. Dimension Dimension Tray P/N A B 541036 7.03 16.47 541034 7.03 20.95 540841 6.90 12.50 B See Note 3 Right Side View 4. Weight in LBS. (per tray, less batteries). Part No. 541036 541034 540841 With Circuit Without Circuit Breaker Option Breaker Option 20.5 lbs 18.5 lbs 25.3 lbs 23.3 lbs 18.5 lbs 16.5 lbs 5. Finish: Gray 6. Maximum trays available per rack is three (3). Page 97 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home Overall Dimensions – 23” Battery Tray Optional Battery Disconnect Circuit Breakers (Shown on Right Side, Available on Either Side) A See Note 3 10.50 12.25 14.00 (as ordered) ISO View Front View Notes: 1. All dimensions are in inches, unless otherwise specified. 2. P/N 528496 tray shown. P/N 540842 similar. 3. Dimension Dimension Tray P/N A B 528496 9.781 24.437 540842 6.90 12.50 B See Note 3 Right Side View 4. Weight in LBS. (per tray, less batteries). Part No. 528496 540842 With Circuit Without Circuit Breaker Option Breaker Option 33 lbs 29 lbs 20 lbs 18 lbs 5. Finish: Gray 6. Maximum trays available per rack is three (3). Page 98 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582136600 (Model 211NGFB) SAG582136600 Issue AF, December 9, 2010 BATTERY MANUFACTURER INFORMATION Home Some equipment described in this System Application Guide is designed to accommodate batteries from various manufacturers. The following are referenced in this document. C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858 Deka®: East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147 Douglas®: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159 MarathonTM: GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543. Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803 RELATED DOCUMENTATION Installation Instructions: Section 6031 User Instructions: Section 6032 Battery Cabinet Spec. No. 541434 Installation and User Instructions: Section 6023 Battery Cabinet Spec. No. 545534 Installation and User Instructions: Section 6033 Battery Cabinet Spec. No. 545506 Installation and User Instructions: Section 6036 Rectifier User Instructions: UM1R481000 SCU+ Controller User Instructions: UM1M521B ACU+ Controller User Instructions: UM1M820B Page 99 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582136600 Issue AF, December 9, 2010 System Application Guide Spec. No. 582136600 (Model 211NGFB) Home REVISION RECORD Issue Change Number (ECO) AA LLP212765 AB LLP213064 AC LLP213144 AD LLP213376 AE LLP214159 AF LLP214106 Description of Change Date Approved New List BC, LC, and NC RESTRICTIONS updated. Reference to custom SCU+ configurations added. Custom digital input cable kit added. Lists BF, LF, and NF now available (note stating Lists were unavailable removed from document). Restriction added to Battery Cabinet P/N 541434 that it can only be used with List 1 and 2. Added 545644, 58213660067, 545728, 540993, 545616, 547525, 548457, 541285, 545534, and 545506. Updated breaker alarm wiring and system ratings and wiring information. Changed input cord gauges per LLP213702 Add P/N 547645 Add AP6C57EA/EB Ring and Distribution Module List LA now available (notes stating List was unavailable removed from document). Added List KG, List 91, ACU+, and SiteWeb™ TEMP. Removed Rectifier and Controller specification information, and referenced the separate Rectifier and Controller User Manuals. 09/16/2009 John Jasko 10/09/2009 John Jasko 01/06/2010 John Jasko 05/19/2010 Shanon Ravacio 09/03/2010 Shanon Ravacio Tim Strouse Dec 14, 2010 John Kirkpatrick Dec 14, 2010 Emerson Network Power, Energy Systems, North America, Inc. 4350 Weaver Parkway, Warrenville, IL 60555 Toll Free: 800-800-1280 (USA and Canada) Telephone: 440-246-6999 Fax: 440-246-4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: Secure.EmersonNetworkPower.com Page 100 of 100 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.