SLIM 系列DC控制过态继电器DC SLIM Solid State

S/MOD/SLD0x205/D/16/04/2003
页 1 / 3 F/GB
SLIM 系列DC控制过态继电器
DC SLIM Solid State Relay
SLD0x205
DC 输入/input
24VDC 4A 输出/output
• 针脚和电磁继电器完全兼容 .
• 5 ,12 ,24 和 48 VDC 控制.
• 24VDC - 4A 输出( 见降容曲线).
• 内置电压箝位.
• Pin to pin compatible with Electromechanic Relays.
• 5 ; 12; 24 and 48VDC control
• 24VDC - 4A output ( see derating curve)
• Integrated clamping voltage.
grid 0,1"/ 栅格 2,54mm top view/仰视图
5
(0.20)
15
(0.59)
28
(1.10)
3,5
(0.14)
A2 -
3,8
(0.15)
0,5 x 0,4mm
(0.02 x 0.015)
(-)
4
3 (+)
INPUT
16,5
(0.65)
5,1
(0.20)
底部图/
Bottom View
-
+
A1 +
2 - ø 0,8 mm
1,4
(0.06)
2
(0.08)
0.15
1 x 0,4mm
(0.04 x 0.015)
2 - ø 1,1mm
0.20
0.65
PCB 布局/Layout
(+) 2
1 (-)
OUTPUT
控制特性 ( 20°C) /
Control characteristics (at 20°C)
参数/Parameter
控制电压 / Control voltage
控制电流 / Control current (@
Uc nom )
释放电压/Release voltage
输入内阻 / Input internal resistor
SLD01205 SLD02205 SLD03205 SLD04205
DC
DC
DC
DC
Symbol Min Nom Max Min Nom Max Min Nom Max Min Nom Max Unit
Uc
3
5
10
7
12 20
18
24 32
38
48
58
V
Ic
5,5
Uc off
Rc
12
27
5,5
10
18
1,8
5,5
7,7
3,6
320
10,2
3,5
4,4
8,3
1070
3000
5,3
mA
8,3
V
Ω
10800
通用特性 / General characteristics
参数/Parameter
工作温度 /Operating temperature range
储藏温度 /Storage temperature range
输入-输出隔离 / Input-output isolation
Conditions
外壳 / Case
外壳 / Case
重量/Weight
最大焊接温度 / Maximum soldering heat(1 mm 外壳/case)
符合 / Conformity
认证 / Approved
Symbol
Tc max
Tc max
Typ.
-20 / +80
°C
-25 / +80
°C
2500
VRMS
8
g
Ts max
220
°C
IEC60947-5-1 & IEC60947-1
UL pending
10 s

Proud to serve you
All technical characteristics are subject to change without previous notice.
Caractéristiques sujettes à modifications sans préavis.
celduc
r
e
l
a
i
s
S/MOD/SLD0x205/D/16/04/2003
页 2 / 3 F/GB
输出特性( 20°C) / Output characteristics (at 20°C)
参数/Parameter
负载电压 / Load voltage
工作电压 / Operating range
DC12额定电流(电阻负载)/ DC-12 nominal current (Resistive loads...)
DC13额定电流(电磁铁)/ DC13 nominal current (Electromagnets)
DC6额定电流(灯)/ DC-6 nominal current (Lamps)
非重复过载电流 /Non repetitive overload current
通态电压降/ On state voltage drop
静态输出导通电阻 / Static output on-resistance
断态漏电流/ Off state leakage current
最小负载电流 / Minimum load current
Conditions
( 见图2/see Fig. 2 )
( 见图2/see Fig. 2 )
(见图2&3/see Fig. 2 &3)
tp=1s (见图3/Fig. 3)
@ Il nom,
Uc nom , Il=2A
@Ul=24V
接通时间/ Turn on time
关断时间/ Turn off time
工作频率 / Operating switching frequency
瞬间电压抑制器/Transient voltage suppressor
崩溃电压/ Breakdown voltage
峰值功率消耗 / Peak power dissipation
峰值电压(钳位电压) / Peak voltage (clamping voltage)
抗传导水平/Conducted immunity level
抗传导水平/Conducted immunity level
Uc nom DC
Uc nom DC
Uc nom DC
@1mA
Pulse 10/1000µs
IEC 1000-4-4 (bursts)
IEC 1000-4-5 (shocks)
Symbol
Typ.
Unit
Ul
24
V
Ulmin-max
0-32
V
Il DC-12
4
A
Il DC-13
4
A
Il DC-6
4
A
Il pulse
9A
A
Vd
0,24V @ 2A
V
R on max
120
mΩ
Ilk max
<1
mA
Ilmin
1
mA
ton max
50
µs
toff max
600
µs
fs
100(*)
Hz
是/ yes
Ubr min
36
V
Pr
600
W
Up max
60
V
1kV criterion A /4kV criterion B
Control :0,5kV crit. A
Output 1kV crit. A
(*) : 工作频率 : 有很高的工作频率,通断操作会增加过态继电器的温度,因此,高频操作时必须
限制工作电流,当小电流时,工作频率的限制根据通断时间而定.意思是高频操作是可能的.
(*) : Operating frequency : With high frequency operating, turn ON and turn OFF commutation can increase the temperature of the SSR. So, with high frequency operating, it is necessary to limit a little bit the current. With low current, the frequency limit is given by the turn ON and turn OFF time, that means high frequency operating is possible.
图3/Fig. 3 : 非重复浪涌电流 /
Non repetitive surge current
图2/Fig. 2 : 负载电流和环境温度特性 /
Load current vs. ambient temperature characteristics
浪涌电流/Surge current Itsm (Apeak) = f(t)
5
4,5
50
4
3,5
40
Itsm (Apeak)
I (A)
5,5
3
2,5
2
1,5
30
20
10
1
0,5
0
0,001
0
0
10
20
30
40
50
60
70
80
环境温度/Tambient(°C)
警告:
* 如果许多固态继电器一个接一个安装,必须考虑降容.
0,01
0,1
t(s)
1
10
Cautions :
* In case of many SSRs side by side , take a derating current
in to account .
* On inductive loads put a free-wheeling diode (or clamp ).
See page 3.
* 对电感性负载需接一个二极管(或箝位).
见第3页.

celduc
r
e
l
a
i
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
S/MOD/SLD03205/D/16/04/2003
页 3 / 3 F/GB
感性负载上的应用
Application on Inductive load
典型应用:/ Typical application :
a) 使用二极管 (DRL)
Using Free wheel diode (DRL).
阀 / Valve
+24VDC
一个二极管保护固态继电器,但是会
增加关断时间.
SLD
DRL
A free wheel diode protect the relay, but the
turn OFF time increases.
0VDC
b) 使用固态继电器的内部电压保护 (Dz)
Using internal voltage protection of the relay ( Dz)
+24VDC
SLD
Dz
固态继电器的内部电压保护(Dz)能被使用,
utilisée dans la limite de sa puissance dissipée, ce qui
limite la fréquence de commutation :
F max = 0,6/LI2 ( L= 负载的感应系数 ; I = 负载电流)
The internal voltage protection (Dz)of the relay can be used but the
switching frequency must be adapted to the max power dissipation
of the internal protection :
F max = 0,6/LI2 ( L= inductance of the load ; I = load current)
0VDC
c) 在负载上用transils或VDR保护 : 用一个高电压固态继电器 : 见 SLD0x210 数据页
Using transils or VDR protection on the load :
use a higher voltage relay : see SLD0x210 data-sheet
+24VDC
SLD
0VDC

celduc
r
e
l
a
i
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19