Specification sheet

PS-S40 Series
Specifications
OUTPUT
Features:
•
•
•
•
•
•
•
•
Universal AC input/full range
Protections: Short Circuit / Overload / Overvoltage
Cooling by free air convection
DIN rail mountable
LED indicator for power on DC OK relay contact
No load power consumption < 0.75W
100% full load burn-in test
3 year warranty
Cat. No.
PS-S4005
PS-S4012
PS-S4024
PS-S4048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
5V
6A
0~6A
30W
80mVp-p
12V
3.33A
0~3.33A
40W
120mVp-p
24V
1.7A
0~1.7A
40.8W
150mVp-p
48V
0.83A
0~0.83A
39.8W
200mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
5 ~ 6V
±2.0%
12 ~ 15V
±1.0%
24 ~ 30V
±1.0%
48 ~ 56V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
HOLD UP TIME (Typ.)
50ms/230VAC; 20ms/115VAC at full load
PROTECTION
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (max)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
85~264VAC 120~370VDC
47~63Hz
78%
86%
1.1A/115VAC; 0.7A/230VAC
COLD START: 30A/115VAC; 60A/230VAC
≤1mA/ 240VAC
OVERLOAD PROTECTION
88%
88%
105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE PROTECTION
6.25~7.25V
15.6~18V
31.2~36V
57.6~64.8V
Protection type: Shut down overvoltage, re-power on to recover
OVER TEMPERATURE PROTECTION
ENVIRONMENT
SAFETY & EMC
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
Relay contact rating (max.): 30V/ 1A resistive
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25°C; 70% RH)
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204 ; EN61000-6-2; EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
301.7K hrs min. MIL-HDBK-217K (25˚C)
40x90x100mm (WxHxD)
0.3Kg; 42pcs / 13.6 Kg / 0.82CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
66
Mechanical Specification
40
100
5 5 5 5 5
+V +V -V -V
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
+
90
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
DC OK RELAY CONTACT
5,6
+V ADJ
N
L
7.5 7.5
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
DETECTION
CIRCUIT
O.L.P.
CONTROL
O.V.P.
DC OK Relay Contact
age.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
80
70
60
60
40
50
20
-20
40
0
10
20
30
40
50
60
70 (VERTICAL)
85
95
100
115
120
140
160
180
200
220
240
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490