PS-S40 Series Specifications OUTPUT Features: • • • • • • • • Universal AC input/full range Protections: Short Circuit / Overload / Overvoltage Cooling by free air convection DIN rail mountable LED indicator for power on DC OK relay contact No load power consumption < 0.75W 100% full load burn-in test 3 year warranty Cat. No. PS-S4005 PS-S4012 PS-S4024 PS-S4048 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER RIPPLE & NOISE (max) 5V 6A 0~6A 30W 80mVp-p 12V 3.33A 0~3.33A 40W 120mVp-p 24V 1.7A 0~1.7A 40.8W 150mVp-p 48V 0.83A 0~0.83A 39.8W 200mVp-p Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor VOLTAGE ADJ. RANGE VOLTAGE TOLERANCE 5 ~ 6V ±2.0% 12 ~ 15V ±1.0% 24 ~ 30V ±1.0% 48 ~ 56V ±1.0% Tolerance: includes set up tolerance, line regulation and load regulation. LINE REGULATION LOAD REGULATION SETUP, RISE TIME ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% 500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load ±1.0% ±1.0% Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. INPUT HOLD UP TIME (Typ.) 50ms/230VAC; 20ms/115VAC at full load PROTECTION VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY (Typ.) AC CURRENT (max) INRUSH CURRENT (Typ.) LEAKAGE CURRENT 85~264VAC 120~370VDC 47~63Hz 78% 86% 1.1A/115VAC; 0.7A/230VAC COLD START: 30A/115VAC; 60A/230VAC ≤1mA/ 240VAC OVERLOAD PROTECTION 88% 88% 105% ~ 150% rated output power Protection type: Constant current limiting, recovers automatically after fault condition is removed OVERVOLTAGE PROTECTION 6.25~7.25V 15.6~18V 31.2~36V 57.6~64.8V Protection type: Shut down overvoltage, re-power on to recover OVER TEMPERATURE PROTECTION ENVIRONMENT SAFETY & EMC DC OK AKTIV SIGNAL (max.) Power supply shut down at 70˚C constant current limiting / output voltage goes to 0; re-power on to recover Relay contact rating (max.): 30V/ 1A resistive WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MOUNTING -20 ~ +70˚C (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85˚C, 10 ~ 95% RH ±0.03% ˚C (0 ~ 50˚C) Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes Compliance to IEC60068-2-6 SAFETY STANDARDS UL508 EN60950-1 compliant I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25°C; 70% RH) Compliance to EN55011 EN55022 (CISPR22) EN61204-3 Class B Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204 ; EN61000-6-2; EN61204-3; light industry level; criteria A WITHSTAND VOLTAGE ISOLATION RESISTANCE EMI CONDUCTION & RADIATION HARMONIC CURRENT EMS IMMUNITY The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. OTHERS MTBF DIMENSION PACKING 301.7K hrs min. MIL-HDBK-217K (25˚C) 40x90x100mm (WxHxD) 0.3Kg; 42pcs / 13.6 Kg / 0.82CUFT All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature. For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power. 66 Mechanical Specification 40 100 5 5 5 5 5 +V +V -V -V Terminal Pin. No Assign. (TB1) Pin No. 1 2 3 Assignment FG AC/N AC/L + 90 Terminal Pin. No Assign. (TB2) Pin No. Assignment 1,2 DC OUTPUT +V DC OUTPUT -V 3,4 DC OK RELAY CONTACT 5,6 +V ADJ N L 7.5 7.5 Block Diagram RECTIFIERS & FILTER EMI FILTER I/P POWER SWITCHING RECTIFIERS & FILTER +V -V O.C.P. DETECTION CIRCUIT O.L.P. CONTROL O.V.P. DC OK Relay Contact age. Derating Curve Output Derating VS Input Voltage Ta=25 100 100 90 80 80 70 60 60 40 50 20 -20 40 0 10 20 30 40 50 60 70 (VERTICAL) 85 95 100 115 120 140 160 180 200 220 240 264 Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937. Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 67