Features:
• Universal AC input / full range
• Built in active PFC function
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL 508(industrial control equipment)approved
• LED indicator for power on
• 100% full load burn-in test
• Fixed switching frequency at 100KHz
• 3 year warranty
Specifications
OUTPUT
Cat. No.
PSP-24024
PSP-24048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
24V
10A
0 ~ 10A
240W
80mVp-p
48V
5A
0 ~ 5A
240W
150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.0%
48 ~ 53V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±1.0%
800ms, 40ms / 230VAC
24ms / 230VAC
85 ~ 264VAC
±0.5%
±1.0%
800ms, 40ms / 115VAC at full load
24ms / 115VAC at full load
120 ~ 370VDC
Derating may be needed under low input voltages, please check the derating curve for more detail
PROTECTION
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (max.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
47 ~ 63Hz
0.96 / 230VAC
0.99 / 115VAC at full load
84%
2.8A / 115VAC; 1.4A / 230VAC
COLD START 27A / 115VAC
45A / 230VAC
≤ 3.5mA / 240VAC
85%
105 ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
30 ~ 36V
54 ~ 60V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
ENVIRONMENT
SAFETY & EMC
100˚C ± 5˚C (TSW: detect on heat sink of power transistor)
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
UL60950-1
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
Compliance to EN55011; EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
heavy industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
289.9K hrs min. MIL-HDBK-217K (25˚C)
125.5x125.2x100mm (WxHxD)
1.2Kg; 12pcs / 15.5Kg / 1.29CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
96
Mechanical Specification
125.5
100
125.2
LED
TB1
3 2 1
1
2
3
TB2
4 3 2 1
Assignment
Assignment
FG
AC/N
AC/L
1,2
3,4
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
PFC
CIRCUIT
RECTIFIERS
&
FILTER
POWER
SWITCHING
FG
O.L.P.
+V
-V
CONSTANT
CURRENT
LIMITING &
DETECTION
CIRCUIT
PWM & PFC
CONTROL
O.V.P.
O.T.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
230VAC
90
80
80
60
70
110VAC
60
40
50
20
40
-10
0
10
20
30
40
50 55 60
70 (VERTICAL)
Vin: --230VAC
110VAC
85
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
97