Specification sheet

Features:
PS-C480 Series
• High efficiency 94% and low power dissipation
• 150% peak load capability
• Built-in active PFC function, PF>0.94
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
• Cooling by free air convection
• Built-in constant current limiting circuit
• DIN rail mountable
• UL 508(industrial control equipment) approved
• EN61000-6-2(EN50082-2) industrial immunity level
• Built-in DC OK relay contact
• 100% full load burn-in test
• 3 year warranty
Specifications
OUTPUT
Cat. No.
PS-C48024
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
24V
48V
20A
10A
0 ~ 20A
0 ~ 10A
480W
480W
30A
15A
720W (3 sec.)
3 seconds peak power max. and the average output power should not exceed the rate power
100mVp-p
120mVp-p
RIPPLE & NOISE (max)
PS-C48048
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
24 ~ 28V
±1.2%
48 ~ 55V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±0.5%
±1.0%
±1.0%
1500ms, 150ms / 230VAC
3000ms, 150ms / 115VAC at full load
14ms / 230VAC at full load
90 ~ 264VAC
127 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
47 ~ 63Hz
0.94 / 230VAC
94%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
Derating may be needed under low input voltages, please check the derating curve for more detail
0.99 / 115VAC at full load
After 30 minutes of burn-in
PROTECTION
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVERVOLTAGE
5A / 115VAC
2.5A / 230VAC
40A / 115VAC
80A / 230VAC
≤ 0.8 mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut
down overvoltage with auto-recovery
≥ 150% rated power, constant current limiting with auto-recovery within 2 seconds and shut
down overvoltage after 2 seconds
29 ~ 33V
56 ~ 65V
OVERTEMPERATURE
105˚C ± 5˚C (TSW: detect on heat sink of power switch)
Protection type: Shut down overvoltage with auto-recovery on re-power on to recovery
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
ENVIRONMENT
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.
-25 ~ +70˚C (Refer to output load derating curve)
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
20 ~ 95% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC O/P-DC OK: 0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC (25˚C; 70% RH)
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2),
EN61204-3; heavy industry level; criteria A, SEMI F47, GL approved
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
112.9K hrs min. MIL-HDBK-217K (25˚C)
85.5x125.2x128.5mm (WxHxD)
1.6Kg; 8pcs / 13.8Kg / 0.9CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
120
Mechanical Specification
TB2
1
2
3
4
5
6
7
8
128.5
+V ADJ
1
TB1
3
+
NC
2
1,2
3,4
5,6
7,8
125.2
Assignment
Assignment
FG
AC/N
AC/L
1
2
3
85.5
DC OK Relay Contact
age.
Block Diagram
I/P
POWER
SWITCHING
PFC
CIRCUIT
&
RECTIFIERS
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
O.L.P.
DETECTION
CIRCUIT
FG
PFC
CONTROL
CONTROL
O.V.P.
Peak Loading
720W
720W
480W
240W
Output Derating VS Input Voltage
Derating Curve
100
150
90
120
80
100
70
60
Continuous
80
50
60
40
-25
0
10
20
30
40
50
60
70
(VERTICAL)
90
100
110
135
155
230
264
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
121