DRAN30/60 SERIES AC - DC DIN RAIL MOUNTABLE POWER SUPPLY INDUSTRIAL CONTROL EQUIPMENT FEATURES ‧UNIVERSAL INPUT 85~264VAC ‧SHORT CIRCUIT PROTECTION ‧INTERNAL INPUT FILTER ‧3 YEARS WARRANTY R R R HH H UL 1310 Class I, Div 2 EN 61558-1 EN 61558-2-16 a UL 60950-1 IND. CONT. EQ. UL 508 EN 60950-1 MODEL LIST DRAN 60- 24 x Wattage 05 : 05V OUT 24 : 24V OUT 12 : 12V OUT 48 : 48V OUT BLANK : SPRING TERMINAL TYPE A : SCREW TERMINAL TYPE MODEL LIST MODEL NO. INPUT VOLTAGE OUTPUT WATTAGE OUTPUT VOLTAGE OUTPUT CURRENT EFF. (min.) EFF. (typ.) Single Output Models DRAN30-05(A) 85~264 VAC 30 WATTS + 5 VDC 6A 77% 79% DRAN30-12(A) 85~264 VAC 30 WATTS + 12 VDC 2.5 A 82% 84% DRAN30-24(A) 85~264 VAC 30 WATTS + 24 VDC 1.25 A 83% 86% DRAN30-48(A) 85~264 VAC 30 WATTS + 48 VDC 0.625A 83% 86% DRAN60-05(A) 85~264 VAC 50 WATTS + 5 VDC 10 A 77% 79% DRAN60-12(A) 85~264 VAC 60 WATTS + 12 VDC 5A 84% 86% DRAN60-24(A) 85~264 VAC 60 WATTS + 24 VDC 2.5 A 86% 89% DRAN60-48(A) 85~264 VAC 60 WATTS + 48 VDC 1.25 A 86% 89% max. max. unit unit 135 KHz SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed GENERAL Conditions Conditions Characteristics min. min. typ. typ. Switching frequency Vi nom, Io nom Isolation voltage Input-Output 3,000 / 4,242 VAC / VDC Input-FG 1,500 / 2,121 VAC / VDC 500 / 710 VAC / VDC 55 Output-FG Isolation resistance Input-Output, @ 500VDC 100 Ambient temperature Operating at Vi nom -40 o o MΩ + 71 o C % / oC Derating (see derating curve) Vi nom, from +61 C to +71 C Storage temperature Non operational -40 + 85 Relative humidity Vi nom, Io nom 20 95 % RH Temperature coefficient Vi nom, Io min ± 0.03 % / oC www.chinfa.com 2015.05.12 2.5 o C [email protected] P1 DRAN30/60 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed GENERAL Conditions Conditions Characteristics MTBF min. min. DRAN30 Bellcore Issue 6 @40oC, GB DRAN60 Bellcore Issue 6 @40oC, GB Altitude during operation Dimension Cooling Installation position max. max. typ. unit unit 5V 12V 612,000 640,000 Hours Hours 24V 665,000 Hours 48V 5V 675,000 Hours 532,000 Hours 12V 556,000 Hours 24V 580,000 Hours 48V 596,000 EN 60950-1 Spring & Screw terminal type 5,000 Hours m mm L90 x W40.5 x D114 Free air convection Vertical ( other direction may derating using ) Pollution degree 2 INPUT SPECIFICATIONS Characteristics Rated input voltage Absolute input max. range Input current max. unit VAC 100 240 85 264 VAC 90 375 VDC Vi : 115 / 230 VAC, Io nom DC in DRAN30 Vi : 115 / 230 VAC, Io nom DRAN60 Vi : 85 VAC, Io nom Line frequency Vi nom, Io nom Inrush current Vi : 115 / 230 VAC , Io nom Leakage current typ. AC in Io nom Ta min ... Ta max, Io nom Rated input current Power dissipation min. Conditions 560 / 330 mA 1,060 / 590 DRAN30 / 60 mA 800 / 1,500 mA Hz DRAN30 63 20 / 40 DRAN60 30 / 60 47 DRAN30 / DRAN60 series Vi : 230 VAC, Io nom A A 5V 8.5 / 12.5 W 12V 24V 5.6 / 9.0 W 5.5 / 8.8 W 48V 4.9 / 7.8 W Input-Output 0.25 mA Input-FG 3.5 mA max. unit +1 % OUTPUT SPECIFICATIONS Characteristics Conditions min. Output voltage accuracy (Adjusted before shipment) Vi nom, Io max 0 Minimum load Line regulation Vi nom Io nom, Vi min ...Vi max 0 Load regulation Vi nom, Io min ...Io nom Voltage trim range DRAN30 & DRAN60 series Vi nom, 0.8 Io nom Rated continuous loading % ± 0.5 5.5 VDC % 5 12V 24V 12 14 VDC 24 28 VDC 48 DRAN30 series 48V 5V Vi nom 12V 2.5 A @ 12Vdc / 2.1 A @ 14 Vdc 24V 1.25 A @ 24Vdc / 1.05 A @ 28 Vdc 48V 0.625 A @ 48Vdc / 0.54 A @ 55 Vdc Vi nom Hold up time Vi : 115 / 230 VAC , Io nom Turn on time Vi nom, Io nom Vi nom, Io nom 2015.05.12 % ± 0.5 5V DRAN60 series www.chinfa.com typ. with Capacitor load 55 6 A @ 5Vdc / 5.4 A @ 5.5 Vdc 5V 10 A @ 5Vdc / 9.0 A @ 5.5 Vdc 12V 5 A @ 12Vdc / 4.25 A @ 14 Vdc 24V 2.5 A @ 24Vdc / 2.1 A @ 28 Vdc 48V 1.25 A @ 48Vdc / 1.08 A @ 55 Vdc VDC 2,000 ms ms 2,000 ms 20 / 30 [email protected] P2 DRAN30/60 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed OUTPUT SPECIFICATIONS Characteristics Rise time Conditions Vi nom, Io nom Vi nom, Io nom min. typ. max. with Capacitor load unit ms 150 ms 500 Fall time Transient recovery time Vi nom, Io nom 150 ms Vi nom, 1~0.5 Io nom Ripple & noise Vi nom, Io nom, BW = 20MHz 2 50 mV Power back immunity DRAN30 & DRAN60 Vi nom, Io nom 1 second Capacitor load Vi nom, Io nom DC ON indicator threshold at start up (Green LED) Vi nom, Io nom Efficiency ms 5V 7.5 VDC 12V 24V 18 VDC 35 VDC 48V 63 DRAN30 / 60 5V 3,500 / 7,000 VDC μF 3.5 4.5 VDC 12V 24V 9.0 10.8 VDC 18 21.6 VDC 48V VDC 37 43 Up to 89%, See model list and typ efficiency curve Vi nom, Io nom, Po / Pi CONTROL AND PROTECTION Characteristics Conditions min. typ. Input fuse Internal surge voltage protection Rated over load protection Power Rdy (for 24V model only) Over voltage protection max. unit T2A / 250VAC internal Varistor IEC 61000-4-5 Vi nom (see typ current limited curve) 110 150 % Threshold voltage of contact closed (at start up) 18.8 19.6 VDC Vi nom, 0.8 Io nom (Auto Recovery) 5V 6.0 6.8 VDC 12V 15 16.5 VDC 24V 30 33 VDC 48V 60 66 VDC Output short circuit Fold forward Degree of protection IP20 APPROVALS AND STANDARDS UL / cUL UL 508 Listed UL 60950-1, UL 1310 Class 2 Power (only 5V and DRAN60-12(A) w/o Class 2) Recognized ISA 12.12.01(Class I, Division 2, Groups A, B, C and D) TUV EN 60950-1 EN 61558-1, EN 61558-2-16 (meet EN 60204-1) CE EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3 EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3 EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4 EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11 ENV 50204 Level 2, EN 61204-3 CCC GB4943.1, GB9254, GB17625.1 Vibration resistance meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis ) Shock resistance meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face) PHYSICAL CHARACTERISTICS Case size 90 x 40.5 x 114 mm (3.6 x 1.59 x 4.49 inches) Case material Plastic Weight DRAN30 : 270 g Packing DRAN30 : 0.35 kg ; 40 www.chinfa.com 2015.05.12 DRAN60 : 340 g / 15 kg / 2.16 CUFT DRAN60 : 0.41 kg ; 40 / 17.5 kg / 2.16 CUFT [email protected] P3 DRAN30/60 SERIES MECHANISM & PIN CONFIGURATION CONSTRUCTION 40.50 [1.59] 40.50 [1.59] 54321 54321 -- -- ++ Rdy Vout ADJ. 90.00 [3.60] 90.00 [3.60] mm [inch] DC ON 114.00 [4.49] INSTALLATION Ventilation / Cooling Normal convection All sides 25mm free space For cooling recommended Connector size range Spring terminal: AWG24-14 (0.2~2mm2 ) flexible / solid cable, 10 m/m stripping at cable end recommends Screw terminal: AWG26-12 (0.2~2.5mm2 ) flexible / solid cable, connector can withstand torque at maximum 5 pound-inches. 4-5 m/m stripping at cable end recommends Use copper conductors only, 60 / 75oC ++ Rdy Vout ADJ. DC ON N L N L 6 7 8 6 7 8 Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safeIy and firmly on the rail. GENERAL TOLERANCE 0.00[0.00] - 30.00[1.18] ±0.30[0.01] 30.00[1.18] - 120.00[4.72] ±0.50[0.02] PIN ASSIGNMENT Designation PIN NO. 1 OUT 2 3 4 5 Description RDY + DC OK output for relay (not connect except 24V model) + - Positive output terminal - Negative output terminal Positive output terminal Negative output terminal Ground this terminal to minimize high-frequency emissions IN 6 7 OTHER 8 N Input terminals (neutral conductor, no polarity at DC input) L Vout ADJ. Input terminals (phase conductor, no polarity at DC input) DC ON Operation indicator LED Trimmer-potentiometer for Vout adjustment Fig. 1 Rdy connection RL > 700ohm Rdy 2.2K 0.5W Rdy - Vout 5.1V 0.3W - Vout b ) 5V signal a ) Relay CIRCUIT SCHEMATIC ‧Block diagram L Fuse Line Filter N Inrush Current Switching Limiter and Device Rectifier PWM Controller Y Y Y Vo + Rectifier Vo - Opto Isolation Reference & Error Amp. Opto Isolation Over Voltage Detection Output Level Detection Vout ADJ. DC ON (Green LED) 1) RDY (Open Collector) Note: 1) for 24V Model Only www.chinfa.com 2015.05.12 [email protected] P4 DRAN30/60 SERIES TYP. CURRENT LIMITED CURVE Output Voltage [ % ] DRAN30-24(A) 100 75 230 Vac 115 Vac 50 25 0 120 130 140 150 160 170 180 190 Output Current [ % ] Output Voltage [ % ] DRAN60-24(A) 100 75 230 Vac 115 Vac 50 25 0 110 120 130 140 150 160 170 180 190 Output Current [ % ] DERATING CURVE Power out [ % ] 100 75 Safe Operating Area 0 -40 o 61 71 Temperature [ C ] TYP. EFFICIENCY CURVE 95 90 85 80 75 70 65 60 55 50 45 40 10 www.chinfa.com 2015.05.12 DRAN60-24(A) EFFICIENCY [ % ] EFFICIENCY [ % ] DRAN30-24(A) 230 Vac 115 Vac 25 50 Power out [ % ] 75 100 95 90 85 80 75 70 65 60 55 50 45 40 10 230 Vac 115 Vac 25 50 Power out [ % ] 75 100 [email protected] P5