EDA20 SERIES

EDA20 SERIES
AC-DC ENCLOSED SWITCHING POWER SUPPLY
FEATURES
‧UNIVERSAL INPUT 88~264VAC
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧3 YEARS WARRANTY
‧HIGH EFFICIENCY UP TO 87%
‧HIGH AVERAGE EFFICIENCY MEET ErP
‧LOW STANDBY POWER CONSUMPTION
R
H
a
UL 60950-1
EN 60950-1
MODEL LIST
MODEL NO.
INPUT
VOLTAGE
OUTPUT
OUTPUT
OUTPUT
WATTAGE VOLTAGE CURRENT
Single Output Models
EFF.
(min.)
EFF.
(typ.)
EFF.
(avg.)
EDA20-05
88~264 VAC
20 WATTS
+ 5 VDC
4000 mA
81%
83%
80%
EDA20-12
88~264 VAC
20.4 WATTS
+ 12 VDC
1700 mA
84%
86%
83%
EDA20-15
88~264 VAC
21 WATTS
+ 15 VDC
1400 mA
85%
87%
84%
EDA20-24
88~264 VAC
21.6 WATTS
+ 24 VDC
900 mA
85%
87%
84%
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Conditions
Conditions
Characteristics
min.
min.
typ.
typ.
max.
max.
unit
unit
Switching frequency
Vi nom, Io nom
Isolation voltage
Input-Output
3,000 / 4,242
VAC / VDC
Input-FG
1,500 / 2,121
VAC / VDC
65
Output-FG
KHz
500 / 710
VAC / VDC
Isolation resistance
Input-Output, @ 500VDC
100
MΩ
Ambient temperature
Operating at Vi nom
-40
o
Derating (see derating curve)
Vi nom, from 61 C to +71 C
Storage temperature
Non operational
-40
Relative humidity
Vi nom, Io nom
20
Temperature coefficient
Vi nom, Io min
MTBF
Bellcore Issue 6 @40 oC, GB
Altitude during operation
www.chinfa.com
2014.07.09
2.5
+ 85
o
C
% / oC
o
C
95
% RH
± 0.03
% / oC
5V
777,000
Hours
12V
835,000
Hours
15V
856,000
Hours
24V
888,000
Hours
IEC 60068-2-13
Dimension
Cooling
+ 71
o
4,850
L92 x W54 x H30
m
mm
Free air convection
[email protected]
P1
EDA20 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Rated input voltage
Conditions
Input current
Vi : 115 / 230 VAC, Io nom
Rated input current
Vi : 88 VAC, Io nom
Line frequency
Vi nom, Io nom
Inrush current
Power dissipation
Vi : 115 / 230 VAC , Io nom
Leakage current
Standby power consumption
max.
unit
240
VAC
AC in
88
264
VAC
DC in
120
375
VDC
Io nom
Absolute input max. range
typ.
100
min.
390 / 250
47
Vi : 230 VAC, Io nom
mA
500
mA
63
20 / 40
Hz
A
5V
4.5
W
12V
15V
4
W
4
W
24V
4
W
Input-Output
0.25
mA
Input-FG
3.5
0.3
mA
max.
unit
+1
%
Vi nom, Io=0A
W
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
0
Load regulation
Vi nom, Io min ...Io nom
Voltage trim range
Vi nom,
0.8 Io nom
Rated continuous loading
Vi nom
Turn on time
Vi nom, Io nom
Vi nom, Io nom
Rise time
Vi nom, Io nom
Vi nom, Io nom
%
VDC
4.5
12V
15V
10.8
13.2
VDC
13.5
16.5
VDC
24V
5V
21.6
27.6
4 A @ 5Vdc / 3.6 A @ 5.5 Vdc
0.9 A @ 24Vdc / 0.75 A @ 27.6 Vdc
1,000
ms
ms
1,500
ms
150
ms
500
ms
150
ms
15 / 80
with 3500μF CAP
Vi nom, Io nom
Ripple & noise
Vi nom, Io nom, BW = 20MHz
Power back immunity
Vi nom, Io nom
1 second
Vi nom, 1~0.5 Io nom
Vi nom, Io nom
Efficiency
Vi nom, Io nom, Po / Pi
2
ms
100
mV
5V
7.5
VDC
12V
15V
18
VDC
22
35
VDC
24V
Capacitor load
VDC
1.7 A @ 12Vdc / 1.5 A @ 13.2 Vdc
1.4 A @ 15Vdc / 1.25 A @ 16.5 Vdc
with 3500μF CAP
Fall time
Transient recovery time
%
5V
24V
Vi : 115 / 230 VAC , Io nom
%
± 0.5
±1
5.5
12V
15V
Hold up time
typ.
VDC
μF
3,500
Up to 87%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
Conditions
min.
Input fuse
Internal surge voltage protection
Rated over load protection
www.chinfa.com
2014.07.09
typ.
unit
max.
T2A / 250VAC internal
IEC 61000-4-5
Vi nom (see typ current limited curve)
Varistor
120
160
%
[email protected]
P2
EDA20 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
CONTROL AND PROTECTION
Characteristics
Vi nom, 0.8 Io nom (Auto Recovery)
Over voltage protection
typ.
min.
max.
unit
5V
5.75
6.75
VDC
12V
13.8
16.2
VDC
15V
17.25
20.25
VDC
24V
28.8
32.4
VDC
Conditions
Output short circuit
Hiccup mode
APPROVALS AND STANDARDS
UL / cUL
UL 60950-1 Recognized
TUV
EN 60950-1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8
EN 61000-4-11, ENV 50204, EN 61204-3
Vibration resistance
meet IEC 60068-2-6 (10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
92 x 54 x 30 mm (3.62 x 2.13 x 1.18 inches)
Case material
Plastic
Weight
140 g
Packing
0.15kg ; 60
/ 9.5kg / 0.76CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
INSTALLATION
Ventilation / Cooling
Normal convection
Connector size range
AWG22-12 (0.2~2.5mm2 ) flexible / solid cable,
connector can withstand torque at maximum
8 pound-inches.
2-T3
-V
45.00 [1.77]
N
DC ON
+V
+
6.4 [0.25]
(AC)
7.62 [0.30]
L
GENERAL TOLERANCE
4-T3
L=Max 5mm
66.00 [2.60]
30.00 [1.18]
22.00 [0.87]
10.00 [0.39]
15.00 [0.60]
±0.50[0.02]
54.00 [2.13]
1
2014.07.09
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
84.20 [3.31]
92.00 [3.62]
www.chinfa.com
0.00[0.00] - 30.00[1.18]
2
3
4
5
Vout AD
[email protected]
P3
EDA20 SERIES
PIN ASSIGNMENT
Designation
PIN NO.
Input terminals (phase conductor, no polarity at DC input)
Input terminals (neutral conductor, no polarity at DC input)
IN
2
Description
L
N
OTHER OUT
1
-
Negative output terminal
+
Vout ADJ.
Positive output terminal
DC ON
Operation indicator LED
Ground this terminal to minimize high-frequency emissions
3
4
5
Trimmer-potentiometer for Vout adjustment
CIRCUIT SCHEMATIC
‧Block diagram for EDA20 series
L
Fuse
Vo +
Rectifier
Line
Filter
Inrush Current
Switching
Limiter and
Device
Rectifier
Vo -
N
Y
Control
Circuit
FG
Opto Isolation
Reference &
Error Amp.
Vout ADJ.
TYP. CURRENT LIMITED CURVE
Output Voltage [ % ]
v
EDA20
Hiccup mode
100
50
t
Time
DERATING CURVE
TYP. EFFICIENCY CURVE
EDA20-24
85
80
EFFICIENCY [ % ]
Power out [ % ]
100
75
Safe Operating Area
75
70
65
230 Vac
115 Vac
60
0
-40
www.chinfa.com
2014.07.09
61
Temperature [ oC ]
71
10
25
50
Power out [ % ]
75
100
[email protected]
P4