AMR1 SERIES AC - DC DIN RAIL MOUNTABLE POWER SUPPLY INDUSTRIAL CONTROL EQUIPMENT FEATURES ‧UNIVERSAL INPUT 90~264VAC ‧SHORT CIRCUIT PROTECTION ‧INTERNAL INPUT FILTER ‧LOW PROFILE FOR BUILDING AUTOMATION ‧3 YEARS WARRANTY R R R H HH Class I, Div 2 a UL 60950-1 UL 1310 IND. CONT. EQ. UL 508 EN 60950-1 MODEL LIST MODEL NO. INPUT VOLTAGE OUTPUT WATTAGE OUTPUT VOLTAGE OUTPUT CURRENT EFF. (min.) EFF. (typ.) Single Output Models AMR1-05 90~264 VAC 7.5 WATTS + 5 VDC 1500 mA 73% 75% AMR1-12 90~264 VAC 10 WATTS + 12 VDC 830 mA 77% 79% AMR1-15 90~264 VAC 10 WATTS + 15 VDC 670 mA 78% 80% AMR1-24 90~264 VAC 10 WATTS + 24 VDC 420 mA 78% 80% SPECIFICATION o All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed GENERAL Characteristics min. Conditions Switching frequency Vi nom, Io nom Isolation voltage Input-Output Isolation resistance Input-Output, @ 500VDC Ambient temperature Operating at Vi nom typ. max. 132 o unit KHz 3,000/4,242 VAC / VDC 100 MΩ + 71 -40 o o C % / oC Derating (see derating curve) Vi nom, from +61 C to +71 C Storage temperature Non operational -40 + 85 Relative humidity Vi nom, Io nom 20 95 % RH Temperature coefficient Vi nom, Io min ± 0.03 % / oC MTBF Bellcore Issue 6 @40oC, GB Altitude during operation Free air convection Installation position Vertical ( other direction may derating using ) www.chinfa.com 2014.08.11 C 5V 901,000 Hours 888,000 Hours 15V 893,000 Hours 24V 910,000 Hours 4,850 L91 x W18 x D56.5 Cooling o 12V IEC 60068-2-13 Dimension Pollution degree 2.5 m mm 2 [email protected] P1 AMR1 SERIES SPECIFICATION o All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed INPUT SPECIFICATIONS Characteristics Rated input voltage Absolute input max. range Conditions Io nom Ta min ... Ta max, Io nom Input current Vi : 115 / 230 VAC, Io nom Rated input current Vi : 90 VAC, Io nom Line frequency Vi nom, Io nom Inrush current Power dissipation Vi : 115 / 230 VAC , Io nom Leakage current Vi : 230 VAC, Io nom typ. max. unit 100 240 VAC AC in 90 264 VAC DC in 120 375 VDC min. 200 / 135 47 mA 300 mA 63 16 / 32 Hz A 5V 2.5 W 12V 15V 2.7 W 2.5 W 24V 2.5 Input-Output W 0.25 mA max. unit ±1 % OUTPUT SPECIFICATIONS Characteristics Conditions min. Output voltage accuracy (Adjusted before shipment) Vi nom, Io max Minimum load Line regulation Load regulation Hold up time Vi nom Io nom, Vi min ...Vi max Vi nom, Io min ...Io nom Vi : 115 / 230 VAC , Io nom Vi nom, Io nom Vi nom, Io nom Capacitor load Vi nom, Io nom Vi nom, Io nom Capacitor load Vi nom, Io nom Vi nom, 1~0.5 Io nom Vi nom, Io nom, BW = 20MHz Vi nom, Io nom 5V 12V 15V 24V Vi nom, Io nom 5V 12V 15V 24V Vi nom, Io nom 5V 12V 15V 24V Vi nom, Io nom 5V 12V 15V 24V Vi nom, Io nom, Po / Pi Turn on time Rise time Fall time Transient recovery time Ripple & noise Power back immunity Capacitor load DC ON indicator threshold at start up (Green LED) DC LOW indicator threshold after start up (Red LED) Efficiency typ. 0 % % % ms ms ms ms ms ms ms ±1 ±1 10 / 30 1,000 1,500 150 500 150 2 50 mV VDC VDC VDC VDC μF 3,500 μF 1,800 μF 1,500 μF 560 4.5 VDC 3.5 VDC 10.8 9 VDC 13.5 11 VDC 19.2 21.6 4.5 VDC 3.5 VDC 10.8 9 VDC 13.5 11 VDC 19.2 21.6 Up to 80%, See model list and typ efficiency curve 7.5 18 22 35 CONTROL AND PROTECTION Characteristics Input fuse Internal surge voltage protection Rated over load protection Over voltage protection min. Conditions IEC 61000-4-5 Vi nom (see typ current limited curve) Vi nom, Io nom 5V (Auto Recovery) 12V 15V 24V Output short circuit Degree of protection www.chinfa.com 2014.08.11 125 5.75 15 18 30 typ. max. T1A / 250VAC internal Varistor 185 6.5 16.5 20 33 Hiccup mode IP20 unit % VDC VDC VDC VDC [email protected] P2 AMR1 SERIES SPECIFICATION All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed APPROVALS AND STANDARDS UL / cUL UL 508 Listed UL 60950-1, UL 1310 Class 2 Power Recognized ISA 12.12.01(Class I, Division 2, Groups A, B, C and D) TUV EN 60950-1 CE EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3 EN 61000-6-2, EN 55024, EN 61000-4-2 Level 3, EN 61000-4-3 Level 3 EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3 EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11 ENV 50204 Level 2, EN 61204-3 Vibration resistance meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis ) Shock resistance meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face) PHYSICAL CHARACTERISTICS Case size 91 x 18 x 56.5 mm (3.58 x 0.71 x 2.22 inches) Case material Plastic Weight 65g Packing 0.11kg ; 120 / 14.5kg / 2.28CUFT MECHANISM & PIN CONFIGURATION mm [inch] CONSTRUCTION Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safely and firmly on the rail; no tools required even to remove 2 1 + INSTALLATION 12.00 [0.47] 11.00 [0.43] 18.00 [0.71] 45.00 [1.77] DC LO L 3 N 56.50 [2.22] 49.60 [1.95] 32.30 [1.27] 51.50 [2.02] 91.00 [3.58] DC ON 91.00 [3.58] 4 Ventilation / Cooling Normal convection All sides 25m/m free space For cooling recommended Connector size range AWG26-12 (0.2~2.5mm2) flexible / solid cable -Connector can withstand torque at maximum 5 pound-inches. 4~5m/m stripping at cable end recommends. Use copper conductors only, 60/75 oC GENERAL TOLERANCE 0.00[0.00] - 30.00[1.18] ±0.30[0.01] 30.00[1.18] - 120.00[4.72] ±0.50[0.02] PIN ASSIGNMENT 1 2 3 OUT Designation IN PIN NO OTHER 4 www.chinfa.com 2014.08.11 Description - Negative output terminal + Positive output terminal L Input terminals (phase conductor, no polarity at DC input) N Input terminals (neutral conductor, no polarity at DC input) DC ON Operation indicator LED DC LO DC Low indicator LED [email protected] P3 AMR1 SERIES CIRCUIT SCHEMATIC ‧Block diagram for AMR1 series L Fuse N Vo + Inrush Current Limiter and rectifier Switching Device Rectifier Vo Control circuit Reference & Error Amp. Opto Isolation Output Level Detection DC ON (Green LED) DC LO (Red LED) TYP. CURRENT LIMITED CURVE Output Voltage [ % ] v AMR 1-24 Hiccup mode 100 50 t Time DERATING CURVE TYP. EFFICIENCY CURVE AMR1-24 85 80 EFFICIENCY [ % ] Power out [ % ] 100 75 Safe Operating Area 75 70 65 60 230 Vac 115 Vac 55 50 0 -40 61 Temperature [ oC ] www.chinfa.com 2014.08.11 71 10 25 50 75 100 Power out [ % ] [email protected] P4