here - Chinfa

DRAN120* SERIES
FOR DC BACKUP SYSTEM
AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧PFC FUNCTION AVAILABLE
‧INPUT VOLTAGE 115/230VAC AUTO SELECT
‧SELV COMPONENTS DESIGN
‧3 YEARS WARRANTY
R
R
H H
Class I, Div 2
a
UL 60950-1
IND. CONT. EQ.
UL 508
EN 60950-1
SELECTION CHART
DRAN 120 - 24 A *
Wattage
12 : 13.6V OUT / 24 : 27.2V OUT / 48 : 54.5V OUT
DC Backup System
SCREW TERMINAL
MODEL LIST
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
+ 13.6 VDC
8.8 A
82%
84%
120 WATTS
+ 27.2 VDC
4.4 A
84%
86%
120 WATTS
+ 54.5 VDC
2.2 A
85%
87%
MODEL NO.
INPUT
VOLTAGE
DRAN120-12A*
115 / 230 VAC
120 WATTS
DRAN120-24A*
115 / 230 VAC
DRAN120-48A*
115 / 230 VAC
- - ++ Rdy
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
+
- - ++ Rdy
+
Rdy
K1
Rdy
DRAN120*
Series
K1
D1
D1
K1
Fuse
LOAD
DRAN120*
Series
K1
Fuse
LOAD
Rdy
BATTERY
Rdy
DRAN120* Series For DC Backup System Application
BATTERY
DRAN120* Series For DC Backup System Application
Note :
1.The suffix "*" is part of the model number, which specifies the product is designed and pre-trim for low-cost DC backup power system with
external Lead-Acid battery, Relay and Fuse.
2.The manufacturer is liable neither for the external components nor the damage to the power supply causing by external components.
3.The total consumption current including loading and battery charging current should not exceed the maximum rated current of power supply.
4.The operation concept of DC backup power system :
A. When AC power alive : The "Rdy" is close circuit to active the external Relay . The power supply feeds current into the external loads and
charges through Relay to the external battery as well.
B. When AC power interrupted : The "Rdy" is remain close circuit to maintain the external Relay remain active, the external battery supply
current to the external loads.
C. When Battery power low : The "Rdy" become open circuit and the external Relay become inactive to disconnect the battery from
external loads.
www.chinfa.com
2014.09.09
[email protected]
P1
FOR DC BACKUP SYSTEM
SPECIFICATION
DRAN120* SERIES
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Characteristics
Switching frequency
Isolation voltage
Conditions
Conditions
Vi nom, Io nom
Input-Output
55
Storage temperature
Relative humidity
Input-Output, @ 500VDC
Operating at Vi nom
o
VAC / VDC
VAC / VDC
100
MΩ
+ 71
-35
o
Vi nom, from +61 C to +71 C
Non operational
-40
+ 85
Vi nom, Io nom
20
95
95
Temperature coefficient
Vi nom, Io min
MTBF
Bellcore Issue 6 @40 oC, GB
2.5
± 0.03
Altitude during operation
EN 60950-1
Dimension
Cooling
Screw terminal type
Installation position
Vertical ( other direction may derating using )
unit
unit
KHz
VAC / VDC
1,500 / 2,121
500 / 710
Output-FG
Derating (see derating curve)
max.
max.
3,000 / 4,242
Input-FG
Isolation resistance
Ambient temperature
typ.
typ.
min.
min.
o
C
% / oC
o
C
% RH
% / oC
12V
481,000
Hours
24V
517,000
Hours
48V
576,000
5,000
L124.5 x W64 x D123.6
Hours
m
mm
Free air convection
Pollution degree
2
INPUT SPECIFICATIONS
Characteristics
Rated input voltage
Absolute input max. range
Conditions
typ.
Vi : 115 / 230 VAC, Io nom
Rated input current
Vi : 90 / 180 VAC, Io nom
Line frequency
Vi nom, Io nom
Inrush current
Power dissipation
Vi : 115 / 230 VAC , Io nom
90
132
AC in
180
264
VAC
DC in
210
375
VDC
2.2 / 0.83
47
Vi : 230 VAC, Io nom
VAC
AC in
VAC
A
2.8 / 1.4
A
63
24 / 48
Hz
A
12V
24
W
24V
20
W
48V
19
Input-Output
W
0.25
mA
3.5
mA
Input-FG
Power factor (Passive)
unit
max.
115 / 230 (auto select)
Io nom
Ta min ... Ta max,
Io nom
Input current
Leakage current
min.
Vi : 230VAC, Io nom
0.7
OUTPUT SPECIFICATIONS
Characteristics
Conditions
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
Load regulation
Vi nom, Io min ...Io nom
Vi nom, 0.8 Io nom
Voltage trim range
min.
Turn on time
www.chinfa.com
2014.09.09
%
± 0.5
±1
%
24V
22.5
45
25 / 30
28.5
VDC
55
VDC
ms
1,000
ms
1,500
ms
150
ms
500
ms
150
ms
Vi nom, Io nom
12V model : with 7000μF CAP
Vi nom, Io nom
Vi nom, 1~0.5 Io nom
%
VDC
12V model : with 7000μF CAP
24V, 48V models : with 3500μF CAP
Fall time
Transient recovery time
%
14.5
Vi nom, Io nom
Vi nom, Io nom
±1
11.4
24V, 48V models : with 3500μF CAP
Rise time
unit
12V
Vi : 115 / 230 VAC , Io nom
Vi nom, Io nom
max.
0
48V
Hold up time
typ.
2
ms
[email protected]
P2
FOR DC BACKUP SYSTEM
DRAN120* SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
OUTPUT SPECIFICATIONS
Characteristics
Ripple & noise
Vi nom, Io nom, BW = 20MHz
Power back immunity
Vi nom, Io nom
max.
12V
18
VDC
24V
35
VDC
48V
63
Vi nom, Io nom
12V
24V, 48V
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
12V
Vi nom, Io nom
unit
mV
50
Capacitor load
DC LOW indicator threshold
after start up (Red LED)
typ.
min.
Conditions
VDC
μF
7,000
10.4
3,500
μF
11.4
VDC
24V
21.2
22.2
VDC
48V
42.8
43.8
VDC
12V
10.3
11.3
VDC
24V
21.1
22.1
VDC
48V
42.7
43.7
VDC
max.
unit
CONTROL AND PROTECTION
Characteristics
T3.15A / 250 VAC internal
Internal surge voltage protection
IEC 61000-4-5
Rated over load protection
Vi nom
Rdy Close indicator threshold
at start up
Power Rdy
Power Rdy
Varistor
Rdy Open indicator threshold
after start up
Contact rating at 60VDC
Vi nom, 0.8 Io nom (Auto Recovery)
105
125
%
10.4
11.4
VDC
12V
24V
21.2
22.2
VDC
48V
42.8
43.8
VDC
12V
10.3
11.3
VDC
24V
21.1
22.1
VDC
48V
42.7
43.7
VDC
Electrical isolation
Over voltage protection
typ.
min.
Conditions
Input fuse
VDC
500
0.3
A
12V
15
16.8
V
24V
30
33
V
48V
60
66
V
Output short circuit
Fold forward
Degree of protection
IP20
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CCC
Vibration resistance
GB4943.1, GB9254, GB17625.1
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
124.5 x 64 x 123.6 mm (4.9x 2.52 x 4.87 inches)
Case material
Metal
Weight
920 g
Packing
1.02 kg ; 20
www.chinfa.com
2014.09.09
/ 21.5 kg / 2.01 CUFT
[email protected]
P3
FOR DC BACKUP SYSTEM
DRAN120* SERIES
MECHANISM & PIN CONFIGURATION
CONSTRUCTION
mm [inch]
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
64 .00 [2. 52 ]
6
11 6.60 [4. 59 ]
7.00 [0. 30 ]
1
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
Screw terminal:
AWG24-10(0.2~4mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum9pound-inches.
-Output connector can withstand torque at
maximum5.5pound-inches.
8 m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
- - ++ Rdy
Vout ADJ.
124.50 [4.90]
DC LO
DC ON
DRAN120*
L
INSTALLATION
N
GENERAL TOLERANCE
7
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
9
PIN ASSIGNMENT
Designation
PIN NO.
5, 6
A normal open relay contact for DC ON level control
Positive output terminal
V -
Negative output terminal
OUT
3, 4
Description
RDY
V+
IN
1, 2
L
Input terminals (phase conductor, no polarity at DC input)
N
Input terminals (neutral conductor, no polarity at DC input)
DC ON
Operation indicator LED
DC LO
DC LOW voltage indicator LED
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
Ground this terminal to minimize high-frequency emissions
7
8
OTHER
9
CIRCUIT SCHEMATIC
‧Block diagram for DRAN120* series
L
Fuse
Filter
N
Inrush Current
Limiter,
Rectifier and
Auto Select
115 / 230 Vac
Y
Vo +
PFC
Circuit
Smoothing
Circuit
Switching
Device
PWM
Controller
Rectifier
Current
Detection
Vo -
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vout
ADJ.
Output
Level
Detection
DC ON
(Green LED)
DC LOW
(Red LED)
(Relay Contact)
DERATING CURVE
Power out [ % ]
100
75
Safe Operating Area
0
-35
www.chinfa.com
2014.09.09
61
Temperature [ oC ]
71
[email protected]
P4