AC 输出

Panel Mount
Datasheet
PM22 Series
Panel Mount SSRs
• Output ratings up to 95 Amps at 600VAC
• Built-in overvoltage protection
• DBC substrate for superior thermal performance
• LED input status indicator
• IP20 touch-safe housing
• AC or DC control
• 4000 VAC optical isolation
• C-UL-US and TUV approved
PRODUCT SELECTION
Control Voltage
90-280 VAC/VDC
4-32 VDC
25A
50A
95A
PM2260A25V
PM2260D25V
PM2260A50V
PM2260D50V
PM2260A95V
PM2260D95V
AVAILABLE OPTIONS
Series
PM22
Required for valid part number
For options only and not required for valid part number
Operating Voltage
60: 48-600 VAC
60
A
Rated Load Current
25: 25 Amps
50: 50 Amps
95: 95 Amps [High I2t]
25
Control Voltage (1)
A: 90-280 VAC/VDC
D: 4-32 VDC
U
V
Switching Type
Blank: Zero Voltage
Turn-On
Thermal Pad
R: Instantaneous Turn-On Blank: Not Included
(Motor Rating Certified) H: Included
R
H
U
J
Terminal Layout
Input Connector
V: Contactor Configuration Blank: Screw Terminal
J: Spring Terminal
OUTPUT SPECIFICATIONS (2)
Description
Operating Voltage (47-440Hz) [VRMS]
Transient Overvoltage [Vpk] (3)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
Load Current, General Use UL508/LC A IEC 62314 @ 40°C [ARMS] (4)
Load Current, Motor Starting UL508 FLA/LC B IEC 62314 @ 40°C [ARMS] (4)
Minimum Load Current [mARMS]
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Juntion to Case (Rjc) [°C/W]
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
Minimum Heat Sink for Rated Current @ 40ºC [°C/W]
Minimum Power Factor (at Maximum Load) (5)
Motor Rating UL 508/IEC62314 [HP (kW)]: 120 VAC
Motor Rating UL 508/IEC62314 [HP (kW)]: 240 VAC
Motor Rating UL 508/IEC62314 [HP (kW)]: 480 VAC
25A
50A
95A
48-600
1200
1
500
25
8.5/4.8
100
286/300
1.35
0.49
409/375
2
0.5
0.5 (0.37)
1.5 (1.1)
3 (2.24)
48-600
1200
1
500
50
14/7.6
100
716/750
1.35
0.27
2563/2343
0.7
0.5
1 (0.74)
3 (2.2)
5 (3.7)
48-600
1200
1
500
95
26/14
150
1290/1350
1.30
0.2
8320/7593
0.25
0.5
2 (1.5)
5 (3.73)
10 (7.4)
INPUT SPECIFICATIONS (2)
Description
Control Voltage Range
Maximum Reverse Voltage
Minimum Turn-On Voltage
Must Turn-Off Voltage
Minimum Input Current (for on-state)
Maximum Input Current
Nominal Input Impedance
Maximum Turn-On Time [msec]
Maximum Turn-Off Time [msec]
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
PM2260DxxV
4-32 VDC (6)
-32 VDC
4 VDC
1 VDC
10 mA
15 mA
Current Limited
1/2 Cycle (8)
1/2 Cycle
PM2260AxxV
90-280 VAC/VDC (7)
90 VAC/VDC
5 VAC/VDC
6 mA
10 mA
Current Limited
20
30
Panel Mount
Datasheet
GENERAL SPECIFICATIONS (2)
Description
Parameters
Dielectric Strength, Input to Output (50/60Hz)
Dielectric Strength, Input/Output to Baseplate (50/60Hz)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range (9)
Ambient Storage Temperature Range
Short Circuit Current Rating (10)
Weight (typical)
Housing Material
Baseplate Material
Hardware Finish
Input Terminal Screw Torque Range (in-lb/Nm)
Load Terminal Screw Torque Range (in-lb/Nm)
SSR Mounting Screw Torque Range (in-lb/Nm)
Humidity
LED Input Status Indicator
4000 VRMS
4000 VRMS
109 Ohms
8 pF
-40 to 80 °C
-40 to 100 °C
100kA
2.3 oz (65 g)
UL94 V-0
Aluminum
Nickel Plating
5/0.5 (11)
18-20/2-2.2
20-25/2.2-2.8
95% non-condensing
Green
INPUT CURRENT INFORMATION
90-280 VAC/VDC Input
7
12
6
Input Current (mA)
Input Current (mA)
4-32 VDC Input
14
10
8
6
4
2
0
5
4
3
2
1
0
5
10
15
20
25
30
0
35
0
40
Input Voltage (VDC)
80
120
160
200
240
280
Input Voltage (VAC/VDC)
SURGE CURRENT INFORMATION
PM2260x50V
Surge Current (Amp) AC Peak
Surge Current (Amp) AC Peak
PM2260x25V
300
250
200
150
100
50
0
0.01
0.1
1
700
600
500
400
300
200
100
0
0.01
10
Surge Duration (sec)
Surge Current (Amp) AC Peak
PM2260x95V
1200
1000
Single Pulse (12)
800
600
400
200
0.01
0.1
1
Surge Duration (sec)
1400
0
0.1
1
10
Surge Duration (sec)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
10
Panel Mount
Datasheet
THERMAL DERATE INFORMATION (9)
2.5ºC/W
0.7ºC/W
5ºC/W
0.25ºC/W
2.5ºC/W
1ºC/W
15
10
5
20
30
40
50
60
Ambient Temperature (ºC)
70
40
30
20
10
0
80
Load Current (Amps)
20
20
30
40
50
60
Ambient Temperature (ºC)
70
EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAM
DC Control
+3/A1
DC V
-
Trigger
Circuit
OUTPUT
1/L1
INPUT
+
2/T1
-4/A2
Current
Limiter
Load
A
V AC
B
Load
Load can be wired in position A or B
AC/DC Control
Current
Limiter
+3/A1
V
AC/DC
Converter
Trigger
Circuit
-4/A2
OUTPUT
INPUT
-/
1/L1
Load
A
+/
AC/DC
2/T1
V AC
B
Load
Load can be wired in position A or B
Recommended Wire Sizes
Terminal
Configuration
Output
Wire Size
(Solid / Stranded)
Wire Pull-Out
Strength (lb)[N]
2 x 20 AWG (0.75 mm2) [minimum]
25 [111]
2 x 10 AWG (6 mm2)
80 [355]
2 x 8 AWG (10 mm ) [maximum]
90 [400]
2
Screw
Input
Spring
0.5ºC/W
0.36ºC/W
2.5ºC/W
100
50
Load Current (Amps)
Load Current (Amps)
25
0
PM2260x95V
PM2260x50V
PM22xxx25x
2ºC/W
30 AWG (0.05 mm2) [minimum]
4.5 [20]
12 AWG (3.3 mm2) [maximum]
30 [133]
26 AWG (0.13 mm2) [minimum]
5 [22]
12 AWG (3.3 mm2) [maximum]
5 [22]
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
80
80
60
40
20
0
20
30
40
50
60
Ambient Temperature (ºC)
70
80
Panel Mount
Datasheet
MECHANICAL SPECIFICATIONS
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
1.87
[47.5]
Input Connector
1/L1
2.85
[72.3]
+3/A1
1.88
[47.8]
-4/A2
Screw
Terminal
3.62
[91.9]
Spring
Terminal
2/T1
1.19
[30.2]
0.89
[22.5]
ACCESSORIES
New Accessories!
Recommended Accessories
Connectors
Part number: CP201, CP202
Connectors
ID Marker
Hardware
Kit
Heat Sink
Part No.
Thermal Resistance Thermal Pad
[ºC/W]
CP201
CNLB
HK8
HS259DR
2.5
CP202
CNLN
HS073
0.7
CNL2
HS072
0.7
HS053
0.5
HS033
0.36
HS023
0.25
Pluggable input connectors, 2 position, with screw
terminals (CP201) or spring type terminals (CP202).
Compatible with Contactor configuration NOVA22
SSRs.
HSP-7
Hardware Kit
Part number: HK8
Bag with 2 SSR mounting screws 8-32 x 3/8, Hex Socket
Cap, compatible with PM22 Series Panel Mount SSRs.
Used to mount the SSR onto any of our compatible heat
sinks.
Heat Sink
Part number: HS259DR
DIN Rail mountable heat sink with 2.5°C/W thermal
resistance. Heat sink material is aluminum with black
anodized finish. Suitable for mounting a single PM22
Series Panel Mount SSRs.
Thermal Pad
Part number: HSP-7
Non-adhesive thermal pad for half-puck package SSRs.
Compatible with PM22 Series Panel Mount SSRs.
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
Panel Mount
Datasheet
AGENCY APPROVALS
E116949
Certification in accordance with:
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
TUV Certified in accordance to EN62314
Vibration Resistance:
IEC 60068-2-6: Amplitude Range 10-500 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27: Peak Acceleration 50g, Duration11ms.
Electromagnetic Compatibility
Generic
Standard
IEC 61000-6-2
Immunity for
Industrial
Environments
Inmunity Tests
Test Specification
Level
Performance
Electrostatic Discharge
8kV air discharge
Criterion A
IEC 61000-4-2
6kV contact discharge
Criterion A
Fast transients (burst)
Output
IEC 61000-4-4
Input
Surge
IEC 61000-4-5
Output
2kV, 5kHz, 100kHz Criterion B
1kV, 5kHz, 100kHz Criterion B
1kV Line to Line
Criterion B
2kV Line to Earth
Criterion B
AC Input 1kV Line to Line
Criterion A
Option
Criterion A
2kV Line to Earth
GENERAL NOTES
(1) Control voltage 18-52 VAC/VDC is available upon request.
(2) All parameters at 25°C unless otherwise specified.
(3) Output will self trigger between 900-1200 Vpk, not suitable for capacitive loads.
(4) Heat sinking required, see derating curves. For load currents greater than 50A use conductors with at least 75°C insulation.
(5) High inductive loads requires nominal control voltage; AC input models only.
(6) Increase minimum voltage by 1 V for operations from -20 to -40°C.
(7) For ambient temperatures above 40°C the maximum control voltage must not exceed 250 VAC/VDC.
(8) Turn-on time for Instantaneous turn-on versions is 0.1 msec.
(9) AC input models operating range is -20 to 60°C.
(10) When protected with the appropriate class and rated fuse. For detailed info please contact Crydom Technical Support.
(11) Input torque to screw terminals Connector.
(12) For single surge pulse Tc=25°C; Tj=125°C. For AC Output SSRs, AC RMS value of surge current equals the peak value divided by √2 (1.414).
Rev. 060216
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
Panel Mount
Datasheet
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
• Disconnect all
power before
installing or
working with
this equipment.
• Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
• Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
• Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
• Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
• Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
• Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
• Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
• Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
存在电击、
爆炸或电弧
闪烁危险
•
在操作此设
备之前请先
关闭电源。
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
• Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Le non-respect de cette directive peut entraîner,
Failure to follow these instructions can result in des lésions corporelles graves ou des
serious injury, or equipment damage.
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
材料损坏和高温外壳的危险性
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
• 产品的一侧面板可能很热,在其冷却前请
不要触碰。
• 遵照正确的安装说明,包括扭矩值。
• 请勿让液体及其他异物进入本产品。
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
Panel Mount
Datasheet
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr (VI))
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
Semiconductor die
Solder
附件 - 环保信息
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
部件
名称
铅
汞
镉
有毒有害物质或元素
六价铬
多溴联苯
(Pb)
(Hg)
(Cd)
(Cr (VI))
半导体芯片
焊接点
50
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
(PBB)
多溴二苯醚