APM-40 SERIES - MINMAX Technology

APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
FEATURES
►Fully encapsulated Plastic Case
►3 Mounting Versions:
- PCB Mounting with Solder Pins
- Chassis Mounting with Screw Terminals
- DIN-Rail Mounting
► Package Dimension 88.9x63.5x30.0 mm (PCB Version)
►Universal Input 85-264VAC, 47-440 Hz
►Protection Class ll
►Extended Operating Temp.Range -40°C to +60°C at full Load
►LED Output Indicator (Chassis Version Models)
►Eco Design, compliant to Energy Star specification and ErP
Directive 2009/125/EC
►Industrial Safety to UL/IEC/EN 90650-1 and UL508
►Medical Safety Approval to UL/IEC/EN 60601-1 3rd Edition
►Over Load and Over Temperature Protection
►3 Year Product Warranty
PRODUCT OVERVIEW
The new MINMAX APM-40 series is a range of fully encapsulated AC/DC power modules. These high performance products feature an extended operating
temperature range of -40°C to +80°C. Universal input voltage 85-264VAC and UL/IEC/EN safety approvals including medical safety and UL508 listing
qualify these power supplies modules for applications in products with worldwide markets. The modules comply with the latest European ErP Directive and
meet Energy Star requirements. EMI-filter meets EN55022, class B and FCC,part15, class B.
The APM-40 series power modules provide an economical solution for many space critical applications in commercial, medical and industrial electronic
equipment.
Model Selection Guide
Model Number PCB Mounting
Output
(For model with Chassis
Voltage
Output Current
Input Current
Max. capacitive
Load
Max.
115VAC, 60Hz
230VAC, 50Hz
@Max. Load
Mounting, add suffix C)
VDC
5
12
15
24
±12
±15
APM-40S05
APM-40S12
APM-40S15
APM-40S24
APM-40D12
APM-40D15
mA
8000
3330
2660
1660
±1660
±1330
mA(typ.)
698
698
698
687
687
687
Efficiency
(typ.)
@Max. Load, 115VAC
μF
8000
3900
3900
680
1500#
1000#
# For each output
419
419
419
413
413
413
%
83
83
83
84
84
84
Input Specifications
Parameter
Model
Min.
Typ.
Max.
Unit
85
---
264
VAC
47
---
440
Hz
120
---
370
VDC
---
---
0.3
W
115VAC
---
---
25
A
230VAC
---
---
50
A
AC Voltage Input Range
Input Frequency Range
All Models
DC Voltage Input Range
No-Load Power Consumption
Inrush Current (Cold Start at 25℃)
E-mail:[email protected]
2012/06/08 P2
Tel:886-6-2923150
Page 1 of 5
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Output Specifications
Parameter
Conditions
Output Voltage Accuracy
Line Regulation
Min.
Typ.
Max.
Unit
-----
±2.0
±0.5
-----
%
%
%
%
Single Output Model
Dual Output Models
--±1.0
----±2.0
--No minimum Load Requirement
5VDC Output Models
1.5
1.8
%VPP of Vo
--Other Output Models
1.0
1.3
%VPP of Vo
--Zener diode clamp
120
--% of Vo
----±0.02
--%/℃
----5
%
85VAC, Hiccup Mode, auto-recovery
105
----% Inom.
Hiccup mode, indefinite (automatic recovery) (long term overload condition may cause damage)
Load Regulation
Min.Load
Ripple & Noise (20MHz)
Over Voltage Protection
Temperature Coefficient
Overshoot
Current Limitation
Short Circuit Protection
General Specifications
Parameter
Conditions
I/O Isolation Voltage (reinforced)
Leakage Current
I/O Isolation Resistance
Switching Frequency
Min.
500 VDC
115VAC, 60Hz
230VAC, 50Hz
MIL-HDBK-217F@25℃, Ground Benign
Conducted and radiated
Standard
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
Hold-up Time
MTBF (calculated)
EMC Emission
EMC Immunity according EN61000-6-1
EN61000-4-6
EN61000-4-8
EN61000-4-11
Protection Class II
Safety (Approvals pending)
Typ.
Max.
Unit
4000
----VACrms
--80
--μA
1000
----MΩ
--130
--KHz
--25
--ms
--80
--ms
TBD
----Hours
EN 55011 class B, EN 55022 class B, FCC part 15 Class B
Specification Requirement
Performance Criteria
Air ±8KV Cont. ±4KV
B
80~1000MHz, 10V/m 80% AM, 1KHz modulation
A
AC port ±2KV DC, SL, TL ±2KV not less than 1 min.
B
1.2/50μS(8/20μS) AC dif. ±2KV DC ±1KV
B
0.15~80MHz, 10Vrms (functional earth ports included)
B
80% AM, 1KHz modulation
A
50Hz/60Hz, 30A/m
30%, 10ms
B
60%, 100ms, 95%, 5000ms
C
According IEC/EN 60536
cUL/UL 60950-1,60601-1, UL508 listed
IEC/EN 60950-1,60601-1 3rd Edition
Input Fuse
All Models
External Fuse (Recommended)
3.15A Slow – Blow Type
Environmental Specifications
Parameter
Conditions
Ambient
Above +60℃
Temperature Range (operational)
Power Derating
Storage Temperature Range
Over Temperature Protection
Humidity (non condensing)
Cooling
E-mail:[email protected]
2012/06/08 P2
-40℃
-40℃
Shutdown at 90℃ (automatic recovery at approx. 67℃)
--Free-Air convection
Tel:886-6-2923150
Page 2 of 5
+80℃
1.5W / ℃
+95℃
95% rel. H
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Notes
1
This product is not designed for use in critical life support systems, equipment used in hazardous environment, nuclear control systems or other
2
Specifications typical at Ta=+25℃, resistive load, 115VAC, 60Hz input voltage, after warm-up time rated output current unless otherwise noted.
3
Ripple & Noise measurement bandwidth is 0~20 MHz, measured with a 0.1μF/50V MLCC and a 1μF/50V Aluminum electrolytic.
4
Safety approvals cover frequency 47-63 Hz.
5
All AC/DC modules should be externally fused at the front end for protection.
such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet.
6
Other input and output voltage may be available, please contact factory.
7
To order the module with chassis mount package, please add a suffix C (e.g. APM-40S05C).
8
Part number for DIN-Rail mounting bracket: AC-DIN-02
9
That “natural convection” is about 20LFM but is not equal to still air (0 LFM).
10
Specifications subject to change without notice.
Package Specifications PCB Mounting
Mechanical Dimensions
Pin Connections
5
6
15.9 [0.63]
6.0
[0.24]
15.24
[0.60]
12.7
[0.50]
4
0.7
[0.03]
3
81.3 [3.20]
31.6 [1.24]
Pin
Single Output
Dual Output
1
AC (N)
AC (N)
2
AC (L)
AC (L)
3
+Vout
+Vout
4
No Pin
No Pin
5
-Vout
Common
6
No Pin
No Pin
7
NC
-Vout
88.9 [3.50]
7
12.7
[0.50]
1.0
[ 0.04]
15.24
[0.60]
30.0
[1.18]
NC: No Connection
Bottom View
2
1
5.0
[0.20]
Mounting M4.0 Thread
dimensions in mm (inches)
►Tolerance: ±0.5
63.5 [2.50]
►Pin
Physical Characteristics
Case Size
:
Case Material
:
Plastic resin + Fiberglass (flammability to UL 94V-0 rated)
Pin Material
:
Copper Alloy with Gold Plate Over Nickel Subplate
Weight
:
TBD
88.9x63.5x30.0mm (3.50x2.50x1.18 inches)
E-mail:[email protected]
2012/06/08 P2
►All
55.88 [2.20]
Tel:886-6-2923150
Page 3 of 5
(±0.02)
diameter  1.0 ±0.1 (0.04±0.004)
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Package Specifications Chassis Mounting (order code suffix C)
Mechanical Dimensions
Connections
Pin
Single Output
Dual Output
1
AC (N)
AC (N)
2
AC (L)
AC (L)
3
+Vout
+Vout
4
NC
NC
5
-Vout
Common
Indication LED
2
Top view
1
63.8 [2.51]
7
6
5
4
3
50.0 [1.97]
4 x O 3.5
POWER "GOOD" INDICATOR
6
NC
NC
7
NC
-Vout
100.0 [3.94]
NC: No Connection
112.0 [4.41]
92.0 [3.62]
34.1 [1.34]
10.0 [0.39]
5.0 [0.20]
16.8 [0.66]
►All
Physical Characteristics
Case Size
:
Case Material
:
112.0x63.8x34.1mm (4.41x2.51x1.34 inches)
Plastic resin + Fiberglass (flammability to UL 94V-0 rated)
Weight
:
TBD
Package Specifications with DIN Rail Mounting Bracket
Mechanical Dimensions
Indication LED
2
1
63.8 [2.51]
Top view
50.0 [1.97]
4 x O 3.5
7
6
5
4
3
POWER "GOOD" INDICATOR
100.0 [3.94]
112.0 [4.41]
Physical Characteristics
Case Size
:
112.0x63.8x34.1mm (4.41x2.51x1.34 inches)
Case Material
:
Plastic resin + Fiberglass (flammability to UL 94V-0 rated)
Weight
:
TBD
2012/06/08 P2
Tel:886-6-2923150
Page 4 of 5
34.1 [1.34]
11.0[0.43]
3.0[0.12]
5.0
[0.20]
10.0 [0.39]
16.8[0.66]
92.0 [3.62]
E-mail:[email protected]
dimensions in mm (inches)
►Tolerance: ±0.5
(±0.02)
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
DIN-Rail Mounting Bracket (Order code for Kit : AC-DIN-02)
Minmax Technology Co., Ltd.
18, Sin Sin Road, An-Ping Industrial District, Tainan 702, Taiwan
Tel: 886-6-2923150 Fax: 886-6-2923149 E-mail: [email protected]
2012/06/08 P2