Datasheet

Surge Protection Module
LED Lighting Surge Protection Module > LSP05G
LSP05G Module Series
RoHS
Description
Littelfuse’s LSP05G thermally protected Surge Protective
Device is a self-protected device specially designed to be
used in outdoor and commercial LED lighting fixtures for
transient overvoltage protection. It has been developed with
Littelfuse’s thermally protected varistor technology. Its built-in
thermal disconnect function provides additional protection
to prevent catastrophic failure and fire hazard even under
extreme circumstances of varistor end-of-life or sustaining
over voltage conditions. It also provides high line-to-earth/
ground resistance, facilitating faster production line testing.
LSP05G series connected option allows clear indication of
thermal fault protection by disconnecting power to luminaire,
thereby signaling SPD module replacement. The LSP05G
Surge Protective Device facilitates customer’s product
compliance to IEEE C62.41.2 Location Category C Low ANSI
C136.2 and US Dept. of Energy MSSLC Model Spec.
Agency Approvals
Agency
Standard
Agency File Number
UL1449
for 120V, 240V, 277V Only
E320116
Applications
• Outdoor and Commercial
LED Lighting
• Roadway lighting
• Traffic lighting
• Digital signage
• Wall wash lighting
•
•
•
•
Parking garage lighting
Flood lighting
Tunnel lighting
Street lighting
Additional Information
Datasheet
Resources
Samples
Features
• Maximum Discharge
Current (Imax) 10kA, 8/20µs
• Meets ANSI C136.2
Enhanced Level 10kV/5kA,
IEEE C62.41.2 Location
Category C Low Exposure
and US Dept. of Energy
MSSLC Model Spec.
• Thermally Protected
Varistor technology
• Parallel and Series
Connected SPD Options
• IP66 Water-proof
and Dust-proof
• UL1449 Recognized (120Vac
and 240Vac voltage ratings)
• Series- connected option for
240V and 277V is IEC 6164311 Test Class II and EN
61643-11 Type 2 compliant.
• IEC CB Scheme
Certificate NL-37684
available for 240V and
NL-40516 for 277V
• Compact form factor
with mounting tabs
• 240Vac and 277Vac
are CE compliant and
available for Class I
and Class II installation
based on IEC luminaire
protection classes
• Series connected
– Varistor thermal
protection indication
by removal of power
to luminaire
• High line-to-earth/
ground resistance
• RohS compliant
Absolute Maximum Ratings
• For ratings of individual members of a series, see Device Ratings and Specifications chart
LSP05G Series
Units
Continous:
Max AC Voltage Range (VM(AC)RMS)
Continuous Current
150 to 510
V
5
A
Transient:
Maximum Discharge Current, 8/20μs Waveform (Imax)
10,000
A
Nominal Discharge Current, 8/20µs Waveform (In)
5,000
A
Operating Ambient Temperature Range (TA)
-45 to +85
°C
Storage Temperature Range (TSTG)
-45 to +90
°C
Isolation Voltage Capability (When the thermal disconnect opens)
Insulation Resistance
600
V
>1,000
MΩ
CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only rating and operation of
the device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
© 2016 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 05/24/16
Surge Protection Module
LED Lighting Surge Protection Module > LSP05G
LSP05G Series Device Ratings & Specifications
Part Number
Operating
Voltage (VAC)
MCOV/UC1
(VAC)
Maximum
Discharge
Current2
Imax (A)
Nominal
Discharge
Current3
In (A)
MLV4
(V)
Up
(V)
LSP05G120*
120
150
10,000
5,000
L-N:600
L-G:1410
N-G:1410
L-N:700
L-G:1600
N-G:1600
LSP05G240*
240
275
10,000
5,000
L-N:970
L-G:1410
N-G:1410
L-N:1100
L-G:1600
N-G:1600
X
X
LSP05G277*
277
320
10,000
5,000
L-N: 1130
L-G: 1410
N-G:1410
L-N: 1200
L-G: 1600
N-G:1600
X
X
LSP05G347*
347
420
10,000
5,000
L-N: 1530
L-G: 1550
N-G: 1410
L-N: 1600
L-G: 1700
N-G: 1600
LSP05G480*
480
510
10,000
5,000
L-N: 1800
L-G: 1900
N-G: 1410
L-N: 2100
L-G: 2000
N-G: 1600
LSP05G480*H†
480
510
10,000
5,000
L-N: 1800
L-G: 3090
N-G: 3090
L-N: 2100
L-G: 3700
N-G: 3700
Safety Compliance
5
IEC/EN 61643-116 & 7
UL1449
X
* = S or P
† with 1500Vac Hi-Pot withstand capability in common mode (L-G and N-G)
Glossary:
1. MCOV/UC: Maximum Continuous Operating Voltage - maximum r.m.s. voltage that could be continuously applied to the SPD.
2. Maximum Discharge Current Imax (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20µs
current waveform.
3. Nominal Discharge Current In (A): The nominal discharge current is a measure of the SPDs endurance capability; 15 impulses of discharge current uses the 8/20µs current waveform.
4. MLV: UL1449 Measured limiting voltage; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In);
an average voltage value of 15 impulses
5. Up: IEC 61643-11 Voltage protection level; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In);
a rounding voltage value of maximum measurement.
6. Series module used in parallel connection for indication circuit connection.
7. LSP05G240S & LSP05G277S are certified by DEKRA with below IEC 61643-11 specifications
LSP05G240S Specification
Parameter
Value
Unit
Temporary overvoltage TOV
UT
337
V
LV system fault 255 V x 1.32 at tT = 5 s, TN power grid
Temporary overvoltage TOV
UT
442
V
LV system fault 255 V x 1.732 at tT = 120 min, TN power grid
A
max., gG fuse
Power grids
TN
Backup fuse
16
End of life indication
yes
Max earth leakage current at Uc
Condition
Optical, light ON: SPD is functional
Light OFF: SPD has reached end-of-life
50
µA
Parameter
Value
Unit
Temporary overvoltage TOV
UT
403
V
LV system fault 305 V x 1.32 at tT = 5 s, TN power grid
Temporary overvoltage TOV
UT
529
V
LV system fault 305 V x 1.732 at tT = 120 min, TN power grid
A
max., gG fuse
LSP05G277S Specification
Power grids
TN
Backup fuse
20
End of life indication
yes
Max. rms, to GND
Condition
Optical, light ON: SPD is functional
Light OFF: SPD has reached end-of-life
LSP05G Protection Levels Up
Ic 8/20 µS
5kA
LSP05G240S
Differential mode U2
970V
Common mode U1/U2
1600V/1410V
Ic 8/20 µS
5kA
LSP05G277S
Differential mode U2
1130V
Common mode U1/U2
1600V/1410V
Notes:
• It is normal practice to disconnect components that intentionally breakdown between Line and Protective Earth, otherwise the apparent leakage current measured by the Hi-Pot tester
may
incorrectly be judged a “failure.”
• Maximum Discharge Current Imax (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20µs current
waveform. All Devices pass maximum discharge current with possible, safe opening of thermal disconnect.
© 2016 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 05/24/16
Surge Protection Module
LED Lighting Surge Protection Module > LSP05G
L
L
or
N/G
L
L
N
N
AC/DC
Power
Supply
G
+
-
LED Module
Parallel Connection
SPD
Dimensions
Series Version
L
L
N
N
AC/DC
Supply
G
Parallel Connection
(for Class II Unearthed)
L
L
Power
+
-
LED Module
SPD
~X3316
L
Notes:
+
AC/DC
1. Black: Line; White: Neutral;NGreen: Ground.
L
or N
Power
(P/N with suffix X3333/X3316: Brown: Line;- Blue: Neutral;
LED Module
Green-Yellow
stripe: Ground) Supply
N/G
G
2. Wire Gauge: AWG16, wire length: 100mm±20mm, wire stripping length:10±2mm.
3. Caution: Line/neutral wires must be correctly connected to AC power grid. Wiring
error on line/neutral polarity may cause module failure.
Parallel Version
Parallel Connection
With LED indicating SPD status
- ON (green): SPD is online
- OFF: SPD needs replacement
LED normally on
SPD
LSP10xxxS
R
Application/Installation Schematic
L
L
or
N/G
L
L
N
N
AC/DC
Power
Supply
G
+
L
-
LED Module
L
N/G
Parallel Connection
or
L
L
N
N
AC/DC
Power
SPD
Supply
+
AC/DC
+
-
LED Module
G
SPD
LSP05GxxxP
Series Connection
SPD
LSP05GxxxS
LSP10xxxS
L
L
N
N
AC/DC
Power
Supply
G
+
-
L
L
N
N
LED Module
Supply
G
Parallel Connection
(for Class II Unearthed)
L
N/G
or
L
L
N
N
G
Parallel Connection
With LED indicating SPD status
- ON (green): SPD is online
- OFF: SPD needs replacement
-
LED Module
SPD
~X3316
Series Connection
(for Class II Unearthed)
L
Power
AC/DC
Power
Supply
+
-
LED Module
LED normally on
SPD
LSP05GxxxS
LSP10xxxS
SPD
~X3316
R
Notes:
1. Series module used in parallel connection for indication circuit connection.
2.LED indicator and associated circuitry are not included in the module.
3. Black wire is AC line voltage (hot); white wire is AC neutral voltage.
4. Black wire voltage is cut off when SPD needs replacement.
5. R is current limiting resistor; it resistance/wattage is determined by AC line voltage and desired current driving LED. Example: AC line voltage 240V, LED: 1.6mA, resistor:150Kohm/0.5W.
© 2016 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 05/24/16
Surge Protection Module
LED Lighting Surge Protection Module > LSP05G
Repetitive Surge Capability
100,000
SURGE CURRENT (A)
10,000
1,000
100
MODEL SIZE = 20mm
TA = -55oC TO 85 oC
130 to 625V M(AC) RATING
1
2
15
104
105
106
10 2
10 3
Pulse Rating
(8x20µSec)
Strikes
Surge
1
2
15
100
1,000
10,000A
7,000A
5,000A
1,500A
700A
∞
10
1
10
100
1,000
IMPULSE DURATION (μs)
10,000
Part Numbering System
LSP 05G 120 P N H Xxxxx
Littelfuse Surge Protection Module
5kA (Nominal Discharge Current)
Operating Voltage
P: Parallel connection
S: Series connection
Blank: Waterproof IP66
N: Non-waterproof
Blank: No Hi-Pot withstand capability in
common mode
H: With 1500Vac Hi-Pot withstand
capability in common mode (L-G and N-G)
© 2016 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 05/24/16
Other Options:
X3333: with GND wire connection, available for 240Vac and 277Vac rating with
CE Marking for Class I
earthed luminaire installation
Wire Color: Line: Brown, Neutral: Blue,
Ground/P: Green with yellow stripe
X3316: without GND wire connection,
available for 240Vac and 277Vac rating
with CE Marking for Class II
unearthed luminaire installation
Wire Color: Line: Brown, Neutral: Blue
X3379: Input wire length:
110mm +/-10mm,
output wire length: 210mm+/-10mm
Product is CE Marked for Class I earthed
Luminaire installation and Class II
unearthed Luminaire installation (if earth
connection is not utilized).