N-Series Circuit Breaker Datasheet [pdf]

N-Series
N-Series
CIRCUIT BREAKER
Carling Technologies’ high-performance N-Series hydraulic-magnetic circuit breaker is ideally suited for the rigors
and confined spaces of telecom and datacom power distribution units and rack systems. Its innovative, low profile
design features easily accessible load and line terminals and sliding barriers for effortless installation.
With the integration of an optional current transformer, the N-Series is capable of sensing power fluctuations
down to a level of 1%. This optional capability provides precise current monitoring and reporting required for back
billing of the actual power consumed by datacenter storage and routing devices. This feature also facilitates load
adjustments and maximizes efficiency.
A patent pending, flush-rocker actuator and push-to-reset guard offer additional protection against accidental switching.
1-2 poles; ratings: 1-30 amps up to 240 VAC, 277 VAC, 120/240 VAC; 22,000 Amps Max Interrupting Capacity; UL
489 Compliant Sliding Terminal Barriers; EN60947-2 Certified
Resources:
Download 3D CAD Files
IGS
IGS
STP
Watch Product Video
Product Highlights:
Typical Applications:
ŠŠ
ŠŠ
240 VAC, 277 VAC, 120/240 VAC
UL 489 Compliant Sliding Terminal Barriers
ŠŠ 22,000 Amps Max Interrupting Capacity
ŠŠ 1 – 30 Amps Current Rating
ŠŠ Optional Current Transformer
ŠŠ EN60947-2 Certified
ŠŠ
Telecom/Datacom
- PDU’s
- Data Servers
- Data Storage
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: [email protected]
Application Support: [email protected]
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
2 | N-Series Circuit Breaker - Design Features
N-Series
DESIGN FEATURES
CURRENT TRANSFORMER
Remote current sensing via
molex connector
GRIDS (5x)
Arc deionizing splitter plates that
increase arc voltage for quick
interrupt
UPPER ARC RUNNER
Optional, for 277 VAC
rated breakers
“ LOAD “
“ LINE “
TERMINAL
Allows for easy hook-up of wires
on both sides of the breaker
LOWER ARC RUNNER
Motivates arc off of the
stationary contact
SLIDING TERMINAL BARRIERS
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
N-Series Circuit Breaker - General Specifications | 3
Electrical
Current Metering Integrated current transformer.
Measurement range: 1-30 Amps.
Voltage output: 10mV per Amp according to the formula below:
2(Amp) ≤ I ≤ 30(Amp)
V = 0.01× I ± 2%
(with current metering codes 1 or 2)
V = 0.01× I ±1%
(with current metering codes 3 or 4)
V V10
I I10
V10
I10
0.85%
Where V=CT output in volts
V10 =CT output in volts with I=I10 =10 (A); I=primary current in amperage (50/60 Hz). Phase shift between primary current and CT output is 0.25±0.25°. Maximum crest factor of primary current is 1.73.
R1 shall be integrated in the breaker. R2 and R3 are provided by end user
and external to the breaker. Connection: below Load Terminal. 2-pin connector, Molex 35362-0250. Mating Connector housing – Molex PN35507-0200.
(Current metering is available on AC rated devices only)
I~
(FROM 1 - 30 AMPS)
R2=14Ω±Y%
R1=28Ω±Y%
V
R3=14Ω±Y%
I : 1400
CT
V=0.01 X (I)
Note: When current metering code is 1 or 2; Y to equal 1.0
When current metering code is 3 or 4; Y to equal 0.1
Dielectric Strength
Impedance
Insulation Resistance
Overload
Interrupt Capacity
Mechanical
UL, CSA-1960V 50/60 Hz for one
minute between all electrically
isolated terminals. Comply
with the 8mm spacing and 3750V
50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces and between
main circuits of adjacent poles per
Publications EN 60950 and VDE 0805
See next page
Minimum of 100 Megohms @ 500VDC
50 operations @ 600% of rated current
for AC rated devices
See table A
Endurance
10,000 “On-Off” operations @ 6 per
minute; with rated current & voltage
Trip Free
Trips on overload even when actuator is forcibly held in the “On” position
Trip Indication
The operating actuator moves positively to the “Off” position
when an overload causes the
breaker to trip
Environmental
Environmental
Operating Temperature
Vibration
Shock
Thermal Shock
Moisture Resistance
Salt Spray
MIL-PRF-55629 and MIL-STD-202G
-40°C to +85°C
Withstands 0.06” excursion from 10-55 Hz and 10Gs 55-500 Hz
at rated current per MIL-PRF-55629 and MIL-STD-202G, Method 204D, Test Condition A. Instantaneous and ultra-short curves tested at 90% of rated current
Withstands 50 Gs, 6 ms saw tooth while carrying rated current per MIL-PRF-55629 and MIL-STD-202G, Method 213B, test condition “I”. Instantaneous and ultra short curves tested at 90% of rated current
MIL-PRF-55629 and MIL-STD-202G, Method 107G, Condition A (5-cycles at -55ºC to +25ºC to +85ºC to +25ºC)
MIL-PRF-55629 and MIL-STD-202G, Method 106G, i.e., Ten 24-hour cycles at +25°C to +65°C, 80-98% RH
Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96hrs)
Physical
Number of Poles
1 - 2 poles
Termination
Wire ready and touch proof wire clamp (See Figure 1). Accepts up to (2) #10 AWG wires per terminal.
Designed for use with solid, stranded and flexible stranded wires, with or without ferrule or pin terminals. Also accepts straight fork and flanged fork terminals.
Termination Torque
15-20 in-lbs (Line & Load terminals)
Termination Barrier
Integral sliding barrier to comply with spacing requirements
(See figure 1)
Mounting
Threaded Insert: #6-32 UNC-2B, or M3X0.5-6H B ISO
Insert Termination Torque 7-9 in-lbs
Actuator
Rocker, with or without guard
(See figures 1, 2, and 4)
Internal Circuit Config.
Series Trip
Materials
Housing - Glass Filled Polyester
Rocker – Nylon
Line/Load Terminals - Copper Alloy; Bright Acid Tin Plated
Weight
~107 grams (~3.76 ounces) per pole
Standard Color
Housing – Black
Rocker - Several
(See ordering scheme for colors)
Agency Approvals
UL489, cUL, TUV EN60947-2
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
4 | N-Series Circuit Breaker - General Specifications
Electrical Tables
Table A: Voltage and Current Ratings
N-SERIES TABLE A: ELECTRICAL RATINGS
VOLTAGE
CURRENT
(AMPS)
NUMBER
OF POLES
INTERRUPT CAPACITY (AMPS)
UL 489
EN60947-2 (Ics & Icu)
1-20 A
21-30 A
1-20 A
21-30 A
120/240 VAC
1 - 30
2
10000
5000
5000
5000
240 VAC
1 - 20
1
22000
N/A
5000
5000
277 VAC
1 - 20
1
10000
N/A
N/A
N/A
Electrical: Impedance / Resistance
30
30
CURRENT
TOLERANCE
(AMPS)
(%)
0.10 - 5.0
5.1 - 30.0
+/- 15
+/- 25
30
30
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
N-Series Circuit Breaker - Ordering Scheme | 5
N 1 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Current
Metering
24
6
Frequency
& Delay
620
7
Current Rating
1 2 1
8
Terminal
9
Actuator
Color &
Legend
10
Mounting
1 SERIES
N N-Series Circuit Breaker
8 TERMINAL
1 Screw Terminal
2 ACTUATOR
1
Single Color Low Profile Rocker, Vertical Legend
2
Single Color Low Profile Rocker, Horizontal Legend
3
Single Color Push To Reset Low Profile Rocker, Vertical Legend
4
Single Color Push To Reset Low Profile Rocker, Horizontal Legend
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
3 POLES
1
One
2
Two
4 CIRCUIT
B Series Trip (current)
11 APPLICATION RATING
C 120/240 VAC (2 Pole only)
D 2 240 VAC
F 3 277 VAC
6 FREQUENCY & DELAY
21 50/60 Hz Ultra Short
22 50/60 Hz Short
24 50/60 Hz Medium
26 50/60 Hz Long
12 AGENCY APPROVAL
A Without Approvals
G UL 489 Listed
U 4 TUV Certified, IEC 60947-2
3 5 UL 489 Listed, TUV Certified
50/60 Hz Short, HI-Inrush
50/60 Hz Medium, Hi-Inrush
50/60 Hz Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE
410
512
415
517
420
522
425
527
430
435
AMPERES
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.50
440
445
450
455
460
465
470
475
480
485
4.00
4.50
5.00
5.50
6.00
6.50
7.00
7.50
8.00
8.50
490
495
610
710
611
711
612
712
613
614
9.00
9.50
10.00
10.50
11.00
11.50
12.00
12.50
13.00
14.00
12
Agency
Approval
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
10 MOUNTING
1 6-32 x .195 inches Threaded Inserts
2 ISO M3 x 5 mm Threaded Inserts
5 CURRENT METERING
0
Without Current Transformer
1 1 Integrated Current Transformer, +/- 2%, 1 per unit
2
Integrated Current Transformer, +/- 2%, 1 per pole
3 2,6 Integrated Current Transformer, +/- 1%, 1 per unit
6
4 Integrated Current Transformer, +/- 1%, 1 per pole
42
44
46
D G
11
Rating
615 15.00
616 16.00
61717.00
61818.00
62020.00
62222.00
62424.00
62525.00
63030.00
Notes:
1 On multi pole units one current transformer is supplied on the actuator pole
2 Available up to 20 amps
3 Voltage rating F only available as a 1 pole device at 20 amps maximum
4 TUV approval requires dual (I-O, ON-OFF) markings
5 Approval Code “3” requires Dual (I-O, ON-OFF) markings on rocker.
6 +/-1% tolerance only available when used with +/-0.1% tolerance external
burden resistor.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 | N-Series Circuit Breaker - Dimensional Specifications
Dimensional Specifications: in. [mm]
Figure 1. N-Series 1-Pole Construction
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
N-Series Circuit Breaker - Dimensional Specifications | 7
Dimensional Specifications: in. [mm]
Figure 2. N-Series 2-Pole Construction
Figure 3. N-Series Panel Cut-Out
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 | Notes
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Reps & Contact | 9
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
«
«
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
Michigan
TEMCO Northwest
Alaska, Hawaii
«
NORTHERN
Hanna Lind Ltd.
Melody
Emery
Sierra
Bridge Marketing
Omega Limited
Dy-tronix Inc.
LD. Allen
Norris
DM Assoc
East
Pacent
DM
Assoc
TSI North
TSI
WEST
Signal
Enterprises
Luscombe
Engineering
Pinnacle Marketing
Sunbelt Components
«
South America
DM Mexico
Mexico
SOUTHEAST
ProRep
Solutions
«
Matrix
LATIN AMERICA
Americas
Europe
Middle East
Africa
Asia-Pacific
Oceania
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: [email protected] Application Support: [email protected]
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: [email protected]
Northern Region Sales Office: [email protected]
Southeast Region Sales Office: [email protected]
Midwest Region Sales Office: [email protected]
West Region Sales Office: [email protected]
Latin America Sales Office: [email protected]
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: [email protected]
Shenzhen, China: [email protected]
Shanghai, China: [email protected]
Pune, India: [email protected]
Kaohsiung, Taiwan: [email protected]
Yokohama, Japan: [email protected]
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: [email protected]
Germany: [email protected]
France: [email protected]
www.carlingtech.com
REV_06_2016