L-Series Circuit Breaker

L-Series
Circuit Breaker
Available with Current Monitor
The L-Series high performance, compact hydraulicmagnetic circuit breaker is ideally suited for the rigors and
confined spaces found in today’s telecom/datacom power
distribution units and rack systems. It provides best in class
performance in an innovative low profile, space saving
package complementing the overall spatial objectives
required by telecommunications and data-communications
systems designers in their quest to reduce the overall size
of equipment, while increasing transmission capacity.
The optional current transformer allows outlet metering
and monitoring of power usage thus facilitating load
adjustments and maximizing efficiency. Further, a patent
pending flush rocker actuator design and optional push-toreset guard offers additional protection against accidental
switching.
Number of poles: 1-3. Maximum current and voltage
ratings: .1-32A, 120/240-240VAC. Maximum interrupting
capacity: 5000 Amps
Resources:
Download 3D CAD Files
IGS
STP
Watch Product Video
Product Highlights:
Optional current transformer
ŠŠ Ultra low profile design saves valuable space
ŠŠ Optional handle guard actuator
ŠŠ UL 489 LISTED Branch Circuit breaker
ŠŠ Designed for worldwide datacenter
compatibility with up to 240VAC ratings
ŠŠ
Applications:
Telecom/Datacom Industry
– Power Distribution Units
– Data Servers
– Data Storage
ŠŠ
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: [email protected]
Application Support: [email protected]
Phone: (860) 793-9281 • Fax: (860) 793-9231
www.carlingtech.com
2 | L-Series Circuit Breaker - Design Features
L-Series Circuit Breaker
Design Features
1–Pole Configuration
with Low Profile Rocker Actuator
Patent Pending Flush
Rocker Actuator
PATENT PENDING
LOW PROFILE
DESIGN: 1.760
inch (4.4 cm)
Integrated
Molex
Connector
For optional
current
transformer
2–Pole Configuration
with Push-To-Reset Guard
Optional Push-To-Reset Guard
INTER-POLE
BARRIER
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
L-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Voltage, Current and IC Ratings
Voltage
(VAC)
Current
(Amps)
240
240
240
415/240
120/240
120/240
0.1 - 32
0.1 - 32
0.1 - 20
0.1 - 20
0.1 - 32
0.1 - 32
Number
of Poles
Phase
Current
Metering
1
1
3
3
1
1
Yes
Yes
Yes
Yes
Yes
Yes
1
2*
3
3
2
3**
UL489
(Amps)
5000
5000
5000
--5000
5000
Interrupt Capacity
EN60934
Icn
Inc
3000
10000
3000
10000
3000
5000
3000
5000
3000
10000
3000
10000
Notes:
* Breaking both sides of the line
**3rd pole to be neutral break
Time Delay
Delay Curve Number
Voltage
Description
21
50/60 Hz
Ultrashort
22
50/60 Hz
Short
24
50/60 Hz
Medium
26
50/60 Hz
Long
42
50/60 Hz
Hi-inrush, Short
44
50/60 Hz
Hi-inrush, Medium
46
50/60 Hz
Hi-inrush, Long
Impedance
Current (amps)
0.1-5.0
5.1-32.0
Tolerance (%)
+/-15
+/-25
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
4 | L-Series Circuit Breaker - General Specifications
Electrical
Current Metering
Environmental
Integrated current transformer. Measurement range: 1-32 Amps Voltage output: 10mV per Amp according to the formula below:
2(Amp) ≤ I ≤ 32(Amp)
V = 0.01× I ± 2%
V V10
I I10
V10
I10
0.85%
Environmental MIL-PRF-55629 and MIL-STD-202G
Operating Temp -40ºC to +85 ºC
Vibration
Withstands 0.06” excursion from
10-55 Hz and 10Gs 55-500 Hz at
rated current per MIL-PRF-55629
and MIL-STD-202G, Method 204D,
Test Condition A. Instantaneous and
ultra-short curves tested at 90% of
rated current.
Shock
Withstands 100 Gs, 6 ms saw tooth
while carrying rated current
per MIL-PRF-55629 and MIL-STD
202G, Method 213B, Test Condition
“I”. Instantaneous and ultra short
curves tested at 90% of rated
current.
Thermal Shock
MIL-PRF-55629 and MIL-STD
202G, Method 107G, Condition A
(5-cycles at -55ºC to +25ºC to
+85ºC to +25ºC).
Moisture Resistance
MIL-PRF-55629 and MIL-STD
202G, Method 106G, i.e., Ten 24
hour cycles at +25ºC to +65ºC, 80
98% RH.
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96hrs)
Where V=CT output in volts V10=CT output in volts with I=I10=10 (A); I=primary current in amperage (50/60 Hz). Phase shift between primary current and CT output is 0.25±0.25°. Maximum crest factor of primary current
is 1.73.
R1 shall be integrated in the breaker. R2 and R3 are provided by end user and external to the breaker. Connection:
below Load Terminal. 2-pin connector, Molex 35362-0250. Mating Connector housing – Molex PN35507-0200.
Dielectric Strength UL, CSA-1960V 50/60 Hz for one minute between all
electrically isolated terminals. Comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements Physical
from hazardous voltage to operator accessible surfaces and between main Number of Poles
1-3 poles
circuits of adjacent poles per Termination
Screw Terminals with the following Publications EN 60950 and VDE 0805
thread sizes: 10-32, 8-32, M5, M4
Termination Barrier
Standard for 2 & 3 poles
I~
Mounting
Threaded Insert: #6-32 UNC-2B, or (FROM I THOUGH 32 AMPS)
M3X0.5-6H B ISO (2 per Pole)
Actuator
Rocker, with or without guard
R2=14Ω±I%
Internal Circuit Config.
Series Trip
V
RI=28Ω±I%
Materials
Housing - Glass Filled Polyester
Rocker – Nylon 6/6
R3=14Ω±I%
Line/Load Terminals – Copper Alloy; Bright Acid Tin Plated
V=0,02 X (I)
I : 1400
CT
Weight
~107 Grams (~3.76 Ounces) per pole
Standard Color
Housing - Black, Rocker - Black
Insulation Resistance Minimum of 100 Megohms@500VDC
Mechanical
Overload
50 operations @ 600% of rated
Interrupt Capacity
See Table 1
Endurance
10,000 “On-Off” Operations @ 6 per
minute; 6000 cycles with rated Current and Voltage; 4000 cycles without electrical load.
Trip Free
Trips on overload even when actuator is forcibly held in the “On” position.
Trip Indication
The operating actuator moves positively to the “Off” position when an overload causes the breaker to trip
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
L-Series Circuit Breaker - Ordering Scheme | 5
l 1 1
1
Series
2
Actuator
b 0
4
Circuit
3
Poles
24
5
Current
Metering
6
Frequency
& Delay
1 SERIES
L
2 actuator
1
Single Color Low Profile Rocker, Vertical Legend
2
Single Color Low Profile Rocker, Horizontal Legend
3
Single Color Push to Reset Low Profile Rocker, Vertical Legend
4
Single Color Push to Reset Low Profile Rocker, Horizontal Legend
3 Poles
1
One
2
Two
3
Three
4 Circuit
B
Series Trip (current)
415
517
420
522
425
527
430
435
440
445
450
455
460
465
470
475
480
485
490
495
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
9
Actuator
Color &
Legend
10
Mounting
11
Rating
610
710
611
711
612
712
613
614
615
616
617
618
620
622
624
625
630
632
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
32.000
12
Agency
Approval
8 TERMINAL
2
Screw Terminal, 8-32 (Bus Type)
4
Screw Terminal, 10-32 (Bus Type)
E Screw Terminal, M4 (Bus Type)
H Screw Terminal, M5 (Bus Type)
9 ACTUATOR COLOR & Legend
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
12 AGENCY APPROVAL
A Without approvals
G UL 489 Listed
3 UL 489 Listed, TUV Certified
7 CURRENT RATING (AMPERES)
AMPERES
8
Terminal
K g
11 MAX. APPLICATION RATING
C1 120/240 VAC (2 or 3 Pole only)
D 240 VAC
K 120 VAC
P 4 415Y/240 VAC (TUV only) 240 VAC 3 phase Delta
6 Frequency & Delay
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
42 50/60Hz Short, Hi-Inrush
44 50/60Hz Medium, Hi-Inrush
46 50/60Hz Long, Hi-Inrush
2100.100
215 0.150
2200.200
225 0.250
2300.300
235 0.350
2400.400
245 0.450
250 0.500
255 0.550
2600.600
265 0.650
2700.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
7
Current Rating
4 2 1
10 MOUNTING INSERTS 3
1 6-32 X .195 Threaded Inserts
A 6-32 X .195 Threaded Inserts with Terminal Barrier
2ISO M3 X 5 mm Threaded Inserts
BISO M3 X 5 mm Threaded Inserts with Terminal Barrier
5 Current Metering
0
Without Current Transformer
1 2 Integrated Current Transformer, 1 per unit
2
Integrated Current Transformer, 1 per pole
CODE
620
Notes:
1 3 Pole units available only when one of three poles is neutral
2 On Multi Pole units one current transformer is supplied on the actuator pole
3 Terminal barriers are required on multi poles breaker
4 Voltage rating P only available as a 3 pole device 20A max
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
6 | L-Series Circuit Breaker - Dimensional Specifications in. [mm]
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
L-Series Circuit Breaker - Time Delay | 7
Short - High Inrush AC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Ultrashort - AC
PERCENT OF RATED CURRENT
Medium - High Inrush AC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Short - AC
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
Long - High Inrush AC
TRIP TIME IN SECONDS
TRIP TIME IN SECONDS
Medium - AC
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
Long - AC
PERCENT OF RATED CURRENT
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
8 | Reps & Contact
Authorized North America Sales Representatives
Carling extensive sales representative network group is strategically located and ready to answer any
questions. Find your local representative by clicking on a group name on the map below or by visiting
www.carlingtech.com/findarep.
«
«
Matera
W. Canada
WA
TEMCO Northwest
ND
John Ammouneh
Alaska, Hawaii
«
NORTHERN
WI
MN
SD
Sierra
WY
NE
Omega Limited
NV
UT
CA
KS
CO
AZ
Sunbelt Components
DM Mexico
«
El Paco, Mexico
VA
NH
Norris
NY MA
CT
RI
PA
Pacent
NJ
DE
MD
TSI North
TSI
NC
SC
Pinnacle Marketing
MS
AL
SOUTHEAST
GA
LA
ProRep
Solutions
FL
«
«
Matrix
South America
L D. Allen
WV
KY
MO
AR
TX
Central America
IL
ME
VT
DM Assoc
East
DM OH
Assoc
OK
NM
Patricia Ortiz
IN
TN
Luscombe
Engineering
Signal
Enterprises
IA
Dy-tronix Inc.
Melody
Emery
MI
ID
Bridge Marketing
WEST
DM
Michigan
Hanna Lind Ltd.
MT
OR
Matera
E. Canada
MIDWEST
LATIN AMERICA
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
Locations | 9
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
East Region Sales Office, CT • [email protected]
Midwest Region Sales Office, IL • [email protected]
West Region Sales Office, CA • [email protected]
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Int + 852-2737-2277 • Fax: Int + 852-2736-9332
Email: [email protected]
Shenzhen, China • [email protected]
Shanghai, China • [email protected]
Pune, India • [email protected]
Kaohsiung, Taiwan • [email protected]
Yokohama, Japan • [email protected]
Europe / Middle East/Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Int + 44 1392-364422 • Fax: Int + 44 1392-364477
Email: [email protected]
GmbH, Germany • [email protected]
SAS, France • [email protected]
REV_CB_L_06_2014
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com