CX-Series Circuit Breaker Datasheet

CX-Series
Circuit Breaker
UL 489 Listed & Ideal for 380VDC Applications
The CX-Series circuit breaker features a unique and innovative
arc-quenching configuration that allows the breaker to safely
handle high amperage and high DC voltage applications in a
compact package.
By using a patent pending magnetic flux boosting terminal
configuration, a strong magnetic field is created thus
motivating the arc into an enhanced arc chamber improving
the breaker’s overall performance and reliability.
The permanent magnets located at the entrance of the arc
chamber combined with the upper and lower arc runner
increase the magnetic blow out force and aid in motivating
the arc off of the contacts and into the arc chamber.
An enhanced arc chamber features arc splitter retainers with
integrated pressurizing walls, which facilitates heat transfer
from the arc thereby providing additional cooling and quick
transition into the magnetically induced splitter plates. In turn,
the twelve (12) splitter plates attract, segment and cool the arc
for full extinction.
Combined, these innovative features make the CX-Series
breaker the best in class, providing stable performance even
in the most demanding applications.
Resources:
Download 3D CAD Files
IGS
STP
Watch Product Video
Additional Features:
UL 489 & UL 489B Listed
TUV Certified IEC/EN 60947-2
ŠŠ Temperature stable hydraulic/magnetic overcurrent sensing
technology.
ŠŠ Optional relay trip circuit permitting remote operator system
shut down.
ŠŠ
ŠŠ
Applications:
Perfect fit for 380VDC Applications.
UL 489 Listed and ideal for integration into Information
Technologies’ power distribution equipment utilizing high
DC voltage input.
ŠŠ The CX-Series is UL 489B Listed and ideal for integration
into the combiner box or main disconnect of photovoltaic
renewable energy systems.
ŠŠ
ŠŠ
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: [email protected]
Application Support: [email protected]
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
2 | CX-Series Circuit Breaker - General Specifications
CX-Series Circuit Breaker
DESIGN FEATURES
HYDRAULIC/MAGNETIC
SENSING COIL
UPPER ARC RUNNER
Aids in motivating arc off of movable
contact and into arc chamber
PATENT PENDING MAGNETIC FLUX
BOOSTING TERMINAL CONFIGURATION
Design enhances motivation
of arc into arc chamber
LOWER ARC RUNNER
Aids in motivating arc
off of stationary contact
and into arc chamber
MAGNETS
ARC SPLITTER
RETAINER
w/ integrated
pressurizing walls
LARGE ARC GAP
To generate high
arc voltages
(12) ARC DEIONIZING
SPLITTER PLATES
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
CX-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Table A: Lists UL Listed (UL489) configuration and performance capabilities as a Molded Case Circuit Breaker
CX SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
CIRCUIT
CONFIGURATION
VOLTAGE
MAX CURRENT INTERRUPTING
NUMBER
RATING AMPS CAPACITY (AMPS) OF POLES
MAX. RATING FREQUENCY
SERIES
250
D.C.
15
5,000
1
250 / 500
D.C.
15
10,000
2
410 / 205
D.C.
50
10,000
2
Table B: Lists UL Recognized configurations and performance capabilities as a Component Supplementary Protector
CX SERIES TABLE B : UL1077 COMPONENT SUPPLEMENTARY PROTECTOR
VOLTAGE
CIRCUIT
CONFIGURATION
MAX.
RATING
SERIES
SWITCH ONLY1
MAX
INTERRUPTING
CURRENT
CAPACITY
RATING
AMPS
(AMPS)
FREQUENCY
NUMBER APPLICATION
OF POLES
CODE
300
D.C.
1 - 75
5,000
1
TC1, OL0, U3
300
D.C.
76 - 125
3,000
1
TC1, OL0, U3
440
D.C.
1 -30
10,000
2
TC1, OL0, U3
440
D.C.
31 - 63
5,000
2
TC1, OL0, U3
600
D.C.
1 - 75
5,000
2
TC1, OL0, U3
600
D.C.
76 - 115
3,000
2
TC1, OL0, U3
600
D.C.
1 - 115
----
2 or 3
---
Notes:
1 Requires inclusion of a relay trip voltage coil
Table C: Lists UL Listed (UL489B) configuration and performance capabilities as a Molded Case Switch
CX SERIES TABLE C : UL489B LISTED PHOTOVATIC MOLDED CASE SWITCH
VOLTAGE
CIRCUIT
CURRENT RATING INTERRUPTING
CONFIGURATION MAX RATING FREQUENCY POLES
(AMPS)
RATING (AMPS)
CONSTRUCTION
NOTES
600
DC
21
50 - 100
600
May have a third pole
that is a voltage
trip pole
600
DC
42
110 - 175
600
May have a fifth pole
that is a voltage
trip pole
SERIES
Notes:
1 Two poles in series.
2 Two poles in series in parallel with 2 poles in series.
Table D: TUV Certified Configuration to IEC / EN 60947-2. Low Voltage Switchgear and Controlgear - Circuit Breakers
CX-SERIES TABLE D : TUV IEC/EN 60947-2 LOW VOLTAGE SWITCH GEAR &
CONTROL GEAR / CIRCUIT BREAKER
CIRCUIT
CONFIGURATION
SERIES
VOLTAGE
MAX.
RATING
FREQUENCY
POLES
440
DC
2
CURRENT RATING
(AMPS)
1-63
INTERRUPTING
CAPACITY
ICS / ICU
(AMPS)
4,000
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
4 |
CX-Series Circuit Breaker - General Specifications
Electrical
Mechanical
Maximum Voltage
Overload 600 VDC
50 operations at 600% of rated current for UL489, and at 150% of rated current for UL1077.
RESISTANCEIMPEDANCE
PER POLE VALUES
RESISTANCE,
VALUES
fromfrom
LineLine
to Load
Terminals
to Load
Terminals
(ValuesBased
Based on
on Series Trip
(Values
Trip Circuit
CircuitBreaker)
Breaker)
1000
100
10
O
H
M
S
Current
(amps)
0.1 -5.0
Tolerance
(%)
15%
5.1-20.0
25%
20.1-125
35%
Environmental
1
0.1
0.01
0.001
0.01
Endurance
Max 10,000 ON-OFF operations @
6 per minute; 6000 with rated current & voltage, and 4,000 cycles mechanical.
Trip Free
Trips on overload even when actuator is forcibly held in the “On” position.
Trip Indication
The operating handle moves positively to the “Off” position when an overload causes the breaker
to trip.
0.1
1
10
AMPERE RATING
100-125
100
Physical
Number of Poles
Termination
Termination Barrier
Mounting
Actuator
Internal Circuit Config.
Materials
Weight
Standard Color
1- 2 poles, + Auxiliary Switch Pole.
10-32 or M5 Screw Terminals
1/4-20 or M6 Threaded Stud Terminals
Standard with multi-pole constructions
Threaded insert: #6-32 UNC-2B, or M3X0.5-6H B ISO (2 per pole)
Handle, 1 per pole.
Series Trip
Housing - Glass filled Polyester
Handle - Glass filled Polyester
Line/Load Terminals - Copper Alloy.
~150 Grams (~5.3 Ounces).
~150 Grams (~5.3 Ounces).
Housing - Gray.
Handle - White, Black, Red, Green, Blue, Yellow, Gray,
Shock
Vibration
Moisture Resistance
Salt Spray
Thermal Shock
Operating Temperature
Withstands 100 Gs, 6ms saw tooth while carrying rated current per MILPRF-55629 and MIL-STD-
202G, Method 213G, Test Condition “I”. Instantaneous and ultra short curves tested at 90% of rated current
Withstands 0.060” excursion from 10-55 Hz & 10 Gs 55-500 Hz, at rated current per MIL-PRF-55629 and MILSTD-202G, Method 240D, Test Cond. A. Instantaneous & ultrashort curves tested at 90% of rated current.
MIL-PRF-55629 and MIL-STD-
202G, Method 106G, i.e., Ten 24-
hour cycles at +25°C to +65°C, 80-
98% RH.
Method 101, Condition A (90-95% RH at 5% NaCl Solution, 96 hrs).
MIL-PRF-55629 and MIL-STD-
202G, Method 107G, Condition A (5-cycles at -55°C to +25°C to +85°C to +25°C).
-40°C to +85°C.
*Manufacturer reserves the right to change product specification without prior notice.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
CX-Series Circuit Breaker UL489 – Ordering Scheme | 5
C X 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Aux/Alarm
Switch
14
6
Frequency
& Delay
2 ACTUATOR
X
Handle, one per pole
3 POLES
1
One
2
Two
5 AUXILIARY/ALARM SWITCH
0
w/o Aux Switch
10
Mounting
Inserts
295
410
512
415
517
420
522
425
527
430
435
440
445
450
455
0.95
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.50
4.00
4.50
5.00
5.50
5
6
B
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
6.00
6.50
7.00
7.50
8.00
8.50
9.00
9.50
10.00
10.50
11.00
11.50
12.00
12.50
13.00
614 14.00
615 15.00
616 16.00
61717.00
61818.00
62020.00
62222.00
62424.00
62525.00
63030.00
63535.00
64040.00
64545.00
65050.00
12 G
11
Rating
12
Agency
Approval
Screw Terminal, M5
Stud, M6
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
M3 Thread
11 MAX. APPLICATION RATING
12 250 VDC
13 250/500 VDC 1
15 205/410 VDC
7 CURRENT RATING (AMPERES)
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
9
Actuator
Color &
Legend
10 MOUNTING INSERTS
A
6-32 Thread
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
AMPERES
2 2 A
8
Terminal
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
4 CIRCUIT
B
Series Trip (current)
CODE
7
Current Rating
8 TERMINAL
2
Screw Terminal, 10-32
3
Stud, 1/4-20
1 SERIES
C
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
620
12 AGENCY APPROVAL
A
Without Approvals
G
UL 489 Listed
1
UL 489 Listed, TUV to IEC60947-2
S
Notes:
1 Only Available with 250/500 VDC up to 15 amps.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
6 | CX-Series Switch UL489B – Ordering Scheme
C X 2
1
Series
2
Actuator
S 0
4
Circuit
3
Poles
1 SERIES
C
4
5
Four
Five
4 CIRCUIT
S Switch Only
5 RELAY TRIP VOLTAGE COIL RATING1,2
0
w/o Relay Trip Voltage Coil
A
12 VDC
B
24 VDC
C
32 VDC
D
48 VDC
6 FREQUENCY & DELAY
03
DC Switch Only
7 CURRENT RATING (AMPERES) 1,3
2-Pole Section
810 50A - 100A
4-Pole Section
917 110A - 175A
03
6
Frequency
& Delay
810
7
Current Rating
3 2 A
8
Terminal
9
Actuator
Color &
Legend
06 14
10
Mounting
Inserts
11
Rating
12
Agency
Approval
8 TERMINAL4,5
3
Stud, 1/4-20
6
Stud, M6
A Stud, 1/4-20, w/ 10-32 Screw Terminals on Voltage Pole
B Stud, M6, w/ M5 Screw Terminals on Voltage Pole
2 ACTUATOR
X Handle, one per pole
3 POLES1,2
2
Two
3
Three
5
Relay Trip
9 HANDLE COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
10 MOUNTING INSERTS
A
6-32 Thread
B
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
M3 Thread
11 MAX. APPLICATION RATING
06 600VDC
12 AGENCY APPROVAL
A
Without approvals
14 UL489B Listed
Notes:
1 2 Pole Unit is required for ratings between 50A - 100A.
4 Pole Unit is required for ratings between 110A - 175A.
2 A Relay Trip Voltage Coil Pole may be added to either the 2 or 4 Pole construction.
The addition of this extra pole dictates a change in the designation for the number of poles in selection 3.
3 For Current Ratings between 50A - 100A select current code 810 (100A).
For Current Ratings between 101A - 175A select current code 917 (175A).
4 Voltage Pole must have screw terminals.
Switch Pole must have stud terminals.
5 On 3 Pole Unit, Voltage Pole to be located at P1 as standard.
On 5 Pole Unit, Voltage Pole to be located at P3 as standard.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
CX-Series Circuit Breaker UL1077 – Ordering Scheme | 7
C X 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Aux/Alarm
Switch
14
6
Frequency
& Delay
2 ACTUATOR
X
Handle, one per pole
4 CIRCUIT
A 1
Switch Only (no coil)
B
Series Trip (current)
1
G
Relay Trip (voltage)
76 CURRENT RATING (AMPERES)
420
522
425
527
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
710
10
Mounting
Inserts
10 C
11
Rating
12
Agency
Approval
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
11 MAX. APPLICATION RATING
10 300VDC
114 440 VDC w/o factory installed terminal bus
144 440VDC with factory installed terminal bus
065 600VDC
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
1.500
1.750
9
Actuator
Color &
Legend
10 MOUNTING INSERTS
A
6-32 Thread w/o terminal bus
B
M3 Thread w/o terminal bus
5 AUXILIARY SWITCH
0
w/o Aux Switch3
AMPERES
6 2 B
8
Terminal
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
3 POLES
1
One
2
Two
3
Three
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
415
517
7
Current Rating
8 TERMINAL
2 Screw Terminal, 10-32
3 Stud, 1/4-20
5 Screw Terminal, M5
6 Stud, M6
1 SERIES
C
CODE
660
2.000
2.250
2.500
2.750
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
611
711
612
712
613
614
615
616
617
618
620
622
624
625
630
635
640
650
660
665
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
60.000
65.000
670
675
680
685
690
695
810
911
912
70.000
75.000
80.000
85.000
90.000
95.000
100.000
115.000
125.000
12 AGENCY APPROVAL
A
Without approvals
C
UL 1077 Recognized
W
UL 1077 Recognized & TUV Certified IEC/ EN 60947-29
Notes:
1 Only available when tied to a protected pole
Requires special P/N consult factory for details
2 Voltage trip circuit coil not rated for continuous duty - use instantaneous delay code 10
3 Contacts Rated for 20A @ 80 VDC
4 440VDC Rating available in two different wiring configurations, see next page for more details
5 600 VDC only available with factory installed terminal bus (see next page for more details)
6 Single pole units available up to 125A, multi pole units limited to 115A Max.
(see next page for more details)
7 3 Pole units must include one Auxiliary switch pole (circuit code A or G) - Requires Special Part Number. (see next page for more details)
8 Screw Terminals are limited to 50A max.
9 Agency approval code W only available with 440 VDC rating & circuit code B.
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
8 | CX-Series Circuit Breaker UL489 – Form & Fit Drawings
0.265
[6.73]
0.380
[9.65]
0.380
[9.65]
1.052
[26.72]
0.755
[19.18]
MAXIMUM
0.579
[14.72]
0.265
[6.73]
0.755
[19.18]
MAXIMUM
0.579
[14.72]
1.719
[43.66]
+0.050
3.094 –0.020
78.59 +1.27
–0.50
2.062+0.020
[52.37+0.50]
+0.050
3.094 –0.020
78.59 +1.27
–0.50
2.062+0.020
[52.37+0.50]
1.052
[26.72]
0.380
[9.65]
2.259+0.020
[57.38+0.50]
0.502
[12.75]
2.259+0.020
[57.38+0.50]
0.502
[12.75]
1.719
[43.66]
30.0º
0.755
[19.18]
MAXIMUM
0.124
[3.16]
30.0º
0.124
[3.16]
0.265
[6.73]
0.626+0.020
[15.90+0.50]
2.264+0.020
[57.51+0.50]
1.719
[43.66]
1.017
[25.82]
1.515
[38.48]
MAXIMUM
0.502
[12.75]
1.843+0.020
[46.81+0.50]
0.579
[14.72]
2.264+0.020
+0.050
[57.51+0.50]
3.094 –0.020
1.017
[25.82]
78.59 +1.27
–0.50
2.062+0.020
[52.37+0.50]
30.0º
1.052
[26.72]
1.843+0.020
[46.81+0.50]
2.259+0.020
[57.38+0.50]
0.626+0.020
[15.90+0.50]
0.124
[3.16]
3.672
[93.268]
SHOWN WITH STUD
TERMINAL CONFIGURATION
1.843+0.020
[46.81+0.50]
SHOWN WITH STUD
TERMINAL CONFIGURATION
2.264+0.020
[57.51+0.50]
0.626+0.020
[15.90+0.50]
2.259
[57.38]
1.515
[38.48]
MAXIMUM
3.672
[93.268]
2.259
[57.38]
&
(205/410 VDC)
1.515
[38.48]
MAXIMUM
&
(205/410 VDC)
0.744
[18.90]
0.744
&[18.90]
(205/410 VDC)
SHOWN WITH STUD
TERMINAL CONFIGURATION
1.017
[25.82]
3.672
[93.268]
2.259
[57.38]
2.736
SHOWN WITH SCREW
[69.49]
TERMINAL CONFIGURATION
(WITH SCREW TERMINAL)
2.946
1.520
[74.83]
2.736
SHOWN WITH SCREW [38.61]
(WITH STUD
TERMINAL)
[69.49]
TERMINAL CONFIGURATION
0.760
0.078 TYP
3.276
(WITH SCREW
TERMINAL)
[19.30]
[1.98]
[83.21]
2.946
1.520
(UNFOLDED
BARRIER)
[74.83]
[38.61]
(WITH STUD TERMINAL)
0.760
0.078 TYP
3.276
1.062
[19.30]
[1.98]
[83.21]
[26.97]
TOLERANCES +.005[.12]
(UNFOLDED BARRIER)
2.7362.062
SHOWN WITH SCREW
[52.37]
[69.49]
TERMINAL CONFIGURATION
0.744
1.062
[18.90]
(WITH SCREW TERMINAL)
0.750 TYP
[26.97]
TOLERANCES +.005[.12]2.946
[19.05]
1.520
CX1
0.625
[74.83]
2.062[15.88]
[38.61]
CX2
(WITH STUD TERMINAL)
[52.37]
0.760
3.276
[19.30]
0.750 TYP
[83.21]
[19.05]
CX1
0.625
(UNFOLDED BARRIER)
[15.88]
CX2
1.062
[26.97]
TOLERANCES +.005[.12]
0.078 TYP
[1.98]
2.062
[52.37]
0.625
[15.88]
CX1
CX2
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
0.750 TYP
[19.05]
CX-Series Circuit Breaker UL489B – Form & Fit Drawings | 9
OPTIONAL VOLTAGE POLE
SEE NOTE 1
POLE 1
CX3
POLE 2
CX2
POLE 3
CX3 - 2 POLE SWITCH (CX2)SHOWN
WITH OPTIONAL VOLTAGE POLE
50A-100A DEVICE, 600VDC
POLE 1
OPTIONAL VOLTAGE POLE
SEE NOTE 2
POLE 2
SEE NOTE 3
POLE 3
POLE 4
POLE 5
CX5 - 4 POLE SWITCH (CX4)SHOWN
WITH OPTIONAL VOLTAGE POLE
101A-175A DEVICE, 600VDC
Notes:
1 3 pole configuration supplied with voltage coil on pole 1. Optional location pole 3. Consult factory.
2 5 pole configuration supplied with voltage coil in center pole. (Pole 3)
3 Line & Load connections requires bus connection as shown.
Minimum cross selection .127 in2 (81.94 mm2)
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
10 | CX-Series Circuit Breaker UL1077 – Form & Fit Drawings
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
CX-Series Circuit Breaker - Delay Curves | 11
Instantaneous - DC 10
Ultrashort - DC 11
Short - DC 12
Medium - DC 14
Long - DC 16
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
12 | Reps & Contact
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
«
«
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
Michigan
TEMCO Northwest
WA
ND
Alaska, Hawaii
«
Sierra
WY
NE
Omega Limited
NV
UT
CA
KS
CO
AZ
NM
AR
Sunbelt Components
Mexico
LD. Allen
NH
Norris
NY MA
CT
RI
PA
Pacent
NJ
DE
MD
WV
TSI North
TSI
VA
NC
SC
Pinnacle Marketing
MS
AL
GA
SOUTHEAST
LA
ProRep
Solutions
LATIN AMERICA
Americas
DM
Assoc
KY
MO
«
«
South America
DM Mexico
IL
ME
VT
DM Assoc
OH East
OK
TX
Matrix
IN
TN
Luscombe
Engineering
Signal
Enterprises
IA
Dy-tronix Inc.
Melody
Emery
MI
ID
Bridge Marketing
WEST
WI
MN
SD
OR
NORTHERN
Hanna Lind Ltd.
MT
FL
Europe
Middle East
Africa
Asia-Pacific
Oceania
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
Notes | 13
Email: [email protected] • Application Support: [email protected]
Phone: (860) 793–9281 • Fax: (860) 793–9231• www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: [email protected]
Northern Region Sales Office: [email protected]
Southeast Region Sales Office: [email protected]
Midwest Region Sales Office: [email protected]
West Region Sales Office: [email protected]
Latin America Sales Office: [email protected]
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: [email protected]
Shenzhen, China: [email protected]
Shanghai, China: [email protected]
Pune, India: [email protected]
Kaohsiung, Taiwan: [email protected]
Yokohama, Japan: [email protected]
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: [email protected]
Germany: [email protected]
France: [email protected]
www.carlingtech.com
REV_03_2015