GNT30 SERIES INSTALLATION INSTRUCTIONS CONDOR DC POWER SUPPLIES INC. 2311 STATHAM PKWY OXNARD, CA 93033 + 805-486-4565 RATINGS: Input: 100-240 V ac, 0.75 50/60 Hz Output: 40°C Ambient 50°C Ambient Convection Convection Cooled Cooled GNT30-5 5 V dc/4.0 A 5 V dc/3.2A GNT30-15 15 V dc/2.0 A 15 V dc/1.06 A GNT30-28 28 V dc/1.07 A 28 V dc/0.8 A Notes: 1. 2. 50°C Ambient 150 LFM Airflow 5 V dc/6.0A 15 V dc/2.0 A 28 V dc/1.07 A 40°C Ambient Convection Cooled 12 V dc/2.5 A 24 V dc/1.25 A 48 V dc/0.625 A GNT30-12 GNT30-24 GNT30-48 50°C Ambient Convection Cooled 12 V dc/1.66 A 24 V dc/0.83 A 48 V dc/0.416 A 50°C Ambient 150 LFM Airflow 12 V dc/2.5 A 24 V dc/1.25 A 48 V dc/0.625 A Maximum Operating Relative Humidity 96 %, no condensation. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before application of power. CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of UL//EN/IEC 60601-1 1st. Ed., CSA 22.2 No. 601.1 and EN/IEC/UL/ 60950-1 1st Ed., CSA 22.2 No 60950-1-03. MEDICAL CLASSIFICATION: (In accordance with sub- clause 5 of EN 60601-1) (5.1) Protection against electric shock = Class I (5.2) Degree of protection against electric shock = Not acceptable for applied part without additional isolation (contact factory for details) (5.3) Protection against harmful ingress of water = Ordinary (no protection) (5.5) Have not been evaluated for use in the presence of a flammable anaesthetic mixture with air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment by the OEM. (5.6) Mode of operation = Continuous SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole responsibility that all models listed above are in conformity with the applicable requirements of EN 60950 following the provisions of the Low Voltage Directive 73/23/EEC. All models are Certified to be in compliance with the applicable requirements of UL/IEC/UL 60950-1 1st Ed., CAN/CSA 22.2 No. 60950-1. (Level 3). They are certified for Pollution Degree 2 environment and Class I TN-S power systems. All DC outputs are SELV under normal and single fault conditions. GROUNDING: Protection Class I requires that the ground terminal be bonded to Protective Earth in the end application. grounding is not recommended. A separate dedicated grounding point should be used. Use of this terminal for system OUTPUTS: The output is entedned for Protectively Earthed Signal Output and Intermediate Circuits only. The outputs are not acceptable for patient connection without additional isolation. The output is SELV under normal and single fault conditions. OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some applications where an overvoltage condition could result in a hazard as defined in applicable safety standards, redundant or additional overvoltage protection may be required. Consult factory for details. TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the applicable safety standards, must not be exceeded after installation to preserve the intended safety. The output power, ambient air temperature and the availability, amount, direction and/or restriction of airflow influence the temperatures of these components. FUSING: Fuses for both Line and Neutral are provided in the power supply. A blown fuse is an indication of catastrophic failure of circuit component(s). Repair must be performed by Condor authorized personnel. WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring traces and heatsinks. ISOLATION: The creepage distance between primary and ground is 4 mm minimum; between primary and secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled. The output common is bypassed to ground using a 1000 pF, “Y” capacitor. The required creepage and clearance distances from primary circuits to ground and secondary circuits must be maintained after installation to preserve the intended safety. OVERLOAD PROTECTION: All outputs are protected against overload and short circuit. Recovery is automatic upon removal of the fault. CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary circuits. The components providing isolation from primary to secondary cannot be tested while installed in the power supply without overstressing basic (primary to ground) insulation. All isolating components are individually 100 % tested at 4800 V ac prior to installation. WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit component(s). Refer to fuse marking on the power supply for rating. Repair must be performed by Condor authorized personnel. EXPLANATION OF SYMBOLS J1 - AC Input J2 (TB2) - DC Output Alternating Current Direct Current Attention, Consult Accompanying Documents Pin No. 1 2 Designation Pin No. Designation AC Line AC Neutral Pin 1 and 2 (1) Pin 3 and 4 (2) V Return V+ Attention, Dangerous Voltages Earth (Ground) Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA, and EN/IEC safety standards. 41-35450-1A 10/14/04