GPC41 Instructions

GPC41 SERIES
INSTALLATION INSTRUCTIONS
CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
Internet: www.condorpower.com
MODEL NUMBERS: GPC41-X, where X represents the output voltage which may be any number from 5 thru 28. May be
followed by suffix –XXX where XXX may be any number from 001 thru 999 to indicate value added configurations that have
no impact on safety and/or suffix G to indicate compliance to RoHS.
RATINGS:
Input: 100-240 V ac, 1.3 A, 50/60 Hz
Output: 6 A or 40 W maximum or see table for standard output voltage models.
Model
GPC41-5
GPC41-12
GPC41-15
GPC41-24
GPC41-28
Output
+5 V dc 6.0 A
+12 V dc 3.3 A
+15 V dc 2.7 A
+24 V dc 1.7 A
+28 V dc 1.4 A
Watts
30
40
40
40
40
Notes:
1. Maximum operating ambient temperature for rated output is 50 ºC.
2. Maximum Relative Humidity 96 %, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under
non-condensing conditions before application of power.
SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole responsibility that all
models listed above are in conformity with the applicable requirements of EN 60950-1 following the
provisions of the Low Voltage Directive 73/23/EEC. All models are Certified to be in compliance with the
applicable requirements of UL 60950-1, CSA 60950-1 (L3M1), and EN 60950-1, for Pollution Degree 2
environment and Class I TN-S power systems. The output of these supplies meet the requirements for SELV and are not an
energy hazard.
WARNING! RISK OF FIRE!: EXTERNAL PRIMARY OVERCURRENT PROTECTION must be provided in series
with the phase conductor in the end application. A 2.5 A, 250 V rated fuse with an I2t rating >20 is recommended. The fuse
current rating must not exceed 2.5 A. A blown fuse is an indication of catastrophic failure of circuit component(s). Repair
must be performed by Condor authorized personnel.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring traces and heatsinks.
GROUNDING: Protection Class I requires that the ground terminal be bonded to Protective Earth in the end application.
Using this terminal for the primary system earthing terminal is not recommended. The Power Supply may be attached to
system ground by soldering a grounded wire directly to a 0.098 inch hole marked with a ground symbol near T1.
Alternatively, #4 screws (max 0.22 inch head diameter) and metal spacers (3/16 inch diameter, 1/4 inch minimum length)
should be used to mount the power supply to grounded metal surfaces (Protective Earth). When mounting surfaces are not
grounded or spacers are non-metallic, electrically connect the two metallic mounting pads on the pwb together.
MAINTAINING ISOLATION: The creepage distance between primary and ground is 4 mm minimum; between primary and
secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled. The output common is
bypassed to ground using a 0.001 uF 1 kV capacitor. The required creepage and clearance distances from primary circuits to
ground and secondary circuits must be maintained after installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the applicable safety
standards, must not be exceeded after installation to preserve the intended safety. The output power, ambient air temperature
and the availability, amount, direction and/or restriction of airflow influence the temperatures of these components.
CONNECTIONS:
J1 Pin AC Input
1
Line
2
Neutral
J2 Pin DC Output
MATING CONNECTORS
1
Output (+)
J1 AMP Housing 640250-2
2
Output (+)
Contact 640706-1
3
Common
J2 AMP Housing 640250-4
4
Common
Contact 640706-1
CAUTION: Do not exceed 5 A per contact.
Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are
carried out by other than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the supply is not in accordance with these installation
instructions and the applicable UL, CSA, and IEC/EN safety standards.
41-34223-0001 Rev. F 09/28/05