Product features of OSRAM ECGs in combination with central batteries systems Manufacturer: Type / Description: OSRAM GmbH 81536 München Criteria: Operating voltage range DC: ECG product family: QUICKTRONIC PROFESSIONAL QTP8 CEAG-Data 186 V - 275 V at -10 °C Description Battery voltage range in operation with emergency current Fulfilled 176 V - 276 V initial lamp start above 198 V voltage range DC fulfilled Switching time: from AC to DC from DC to AC Switching time of device: 180 ms - 450 ms 180 ms - 450 ms In accordance with standard1): Typical switching time of CEAG devices YES DIN EN 60929 Electronic ballasts for fluorescent tube lamps, operating on alternating current YES 1) In accordance with standard : DIN EN 61347-2-3 (incl. annex J) Specific requirements for electronic ballasts for fluorescent lamps operated on alternating current YES 1) In accordance with standard : DIN EN 61000-3-2 1) In accordance with standard : DIN EN 61547 1) In accordance with standard : DIN EN 55015 (Measurement on AC and DC) 1) EMC standard for electromagentic compatibility (harmonic content) EMC standard for electromagnetic interference, especially for emergency lighting (immunity) EMC standard for critical values and measuring methods for radio shielding of electrical illumination appliances (interference) YES YES YES Designation after VDE 0108 is insignificant due to it not being an ECG standard Features: No-load current of ECG in DCoperation ( without or with a faulty illuminant ) Max. inrush current per ECG in AC-operation: CEAG-Data: Explanation: Manufacturer's statement: Nominal value of operation: 2L-CG-S: <10 mA / <28 mA 2L-CG (4-120 W): <10 mA 2L-CG (7-120 W): <25 mA 2L-CG (11-120 W): <41 mA Options for luminaire/EVG-monitoring units, CEAG-type: 2L-CG, according to catalog Maximum inrush current: SKU 4 x 1A (CG) => 60 A/ms per circuit SKU 2 x 3A (CG) => 120 A/ms per circuit SKU 1 x 6A (CG) => 180 A/ms SKU 2 x 3A CG-S => 250 A/ms per circuit SKU 1 x 6A CG-S => 250 A/ms Refers to a max. allowable inrush current of ECG within an electric circuit to consider the maximum contact load of the electric circuits' change-overs. see register "Overview" < 10 mA Nominal current in AC-operation: manufacturer-specific For ascertainment of max. quantity of ECG per electric circuit see register "Overview" Nominal current in DC-operation: manufacturer-specific dito see register "Overview" Luminous flux in DC-operation 186 V in relation to 230 V manufacturer-specific ECG for emergency lighting on battery operation - for planning > 75 % The OSRAM ECGs mentioned above fullfill the requirements from the DIN-EN standards on this page. Explicit approval was carried out on those standards mentioned in the identification. OSRAM as a manufacturer of electronic control gear is not liable for the faultless function of other components for emergency lighting. Luminaires for the operation as safety lighting must comply with norm DIN EN 60598-2-22. Form CEAG CEAG requirements overview Manufacturer: Type / Description: OSRAM GmbH 81536 München ECG type ECG product family: QUICKTRONIC PROFESSIONAL QTP8 Max. inrush current per ECG in AC operation Nominal current in ACoperation: Nominal current in DCoperation: QTP8 1x18 Ip = 14 A; TH = 140 µs 0.09 A 0.09 A QTP8 1x36 Ip = 16 A; TH = 155 µs 0.16 A 0.16 A QTP8 1x58 Ip = 20 A; TH = 210 µs 0.24 A 0.24 A QTP8 2x18 Ip = 17 A; TH = 155 µs 0.17 A 0.17 A QTP8 2x36 Ip = 20 A; TH = 210 µs 0.31 A 0.31 A QTP8 2x58 Ip = 28 A; TH = 230 µs 0.45 A 0.45 A QTP8 3x/4x18 Ip = 20 A; TH = 210 µs 0.26 A (3x18) 0.32 A (4x18) 0.26 A (3x18) 0.32 A (4x18)