72RA132BALEN 10

A. Input Characteristics:
1) Voltage: 240VAC
2) Frequency: 50/60 Hz.
3) Current: 32A Maximum
4) Load Capacity: 7.2KVA
5) Overload Protection: 4x 10A Thermal "Push To Reset" Circuit Breaker
6) Power Cord: 2.5M 2P+E 4mm2 "HAR" cord
7) Connector: IEC60309
B. Output Characteristics:
1) Voltage: 240VAC
2) Current: 10A PER OUTLET, 10A PER BREAKER
3) Outlets: 12x C13
C. Mechanical Characteristics:
1) Material: CRS/G40 Galv. Coating
2) Finish: Powder Coated
3) Storage Temp.: -13 to 149F (-25 to 65C)
D. Operating Environment:
1) Temperature: 32 to 122F (0 - 50C)
17.25 in / 438.2 mm
2) Relative Humidity: 0 to 95% (Non-Condensing)
3) Elevation: 0 to 10,000FT (0 to 3000 m)
E. Regulatory Conformance:
1) Safety Agency: CE, UL/cUL, UL60950-1, Recognized (Pending)
1.73 in / 43.9 mm
1.73 in / 43.9 mm
0.42 in / 10.6 mm
BRACKETS CAN BE MOUNTED IN ANY DIRECTION
TO ALLOW FOR 0U, 1U, OR SIDE MOUNT CONFIGURATIONS
0.28 in / 7.1 mm
0.63 in / 15.9 mm
1.25 in / 31.8 mm
2) RoHS: Compliant to Directive 2002/95/EC
CHANGE NOTICE
0
CN-000461-SPMS
REV
18.36 in / 466.4 mm
19.00 in / 482.6 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
carrs
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
DECIMAL .X ± .050
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
4/22/2010
ANGLES ± 030'
Spectrum
Management Systems
PDU,1U,4(3/C13),240,32A
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72RA132BALEN-10
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA