A. Input Characteristics: 1) Voltage: 240VAC 2) Frequency: 50/60 Hz. 3) Current: 32A Maximum 4) Load Capacity: 7.2KVA 5) Overload Protection: 4x 10A Thermal "Push To Reset" Circuit Breaker 6) Power Cord: 2.5M 2P+E 4mm2 "HAR" cord 7) Connector: IEC60309 B. Output Characteristics: 1) Voltage: 240VAC 2) Current: 10A PER OUTLET, 10A PER BREAKER 3) Outlets: 12x C13 C. Mechanical Characteristics: 1) Material: CRS/G40 Galv. Coating 2) Finish: Powder Coated 3) Storage Temp.: -13 to 149F (-25 to 65C) D. Operating Environment: 1) Temperature: 32 to 122F (0 - 50C) 17.25 in / 438.2 mm 2) Relative Humidity: 0 to 95% (Non-Condensing) 3) Elevation: 0 to 10,000FT (0 to 3000 m) E. Regulatory Conformance: 1) Safety Agency: CE, UL/cUL, UL60950-1, Recognized (Pending) 1.73 in / 43.9 mm 1.73 in / 43.9 mm 0.42 in / 10.6 mm BRACKETS CAN BE MOUNTED IN ANY DIRECTION TO ALLOW FOR 0U, 1U, OR SIDE MOUNT CONFIGURATIONS 0.28 in / 7.1 mm 0.63 in / 15.9 mm 1.25 in / 31.8 mm 2) RoHS: Compliant to Directive 2002/95/EC CHANGE NOTICE 0 CN-000461-SPMS REV 18.36 in / 466.4 mm 19.00 in / 482.6 mm DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: carrs TOLERANCES UNLESS OTHERWISE SPECIFIED: DECIMAL .X ± .050 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 DATE 4/22/2010 ANGLES ± 030' Spectrum Management Systems PDU,1U,4(3/C13),240,32A THIRD ANGLE PROJECTION SHEET: 1 OF 1 72RA132BALEN-10 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA