Data Sheet - SINAMICS G120E - Fasttrack

SINAMICS Drives
SINAMICS G120E Fasttrack enclosed drive
1 HP (0.75kW) to 200 HP (132 kW)
Introduction
This technical data sheet provides a short overview of
the most important characteristics of the SINAMICS
G120E Fasttrack enclosed drive. For more comprehensive
information of SINAMICS G120 drive components that are
used in this drive, please refer to Catalog D31.
Note: SINAMICS G120E is an enclosed drive listed to UL508C
(Power Conversion Equipment) per UL file # E319311, by
part number. Listing per UL508C implies that the drive is a
predesigned standard product that has been evaluated/ tested
by UL, and the product as manufactured by the factory may
not be modified by third parties.
SINAMICS G120E Fasttrack is a stand-alone variable speed
drive for single motor applications with variable or constant
torque loads. It is available with either the non-regenerative
PM240 or fully regenerative PM250 (efficient infeed) power
modules. The SINAMICS G120E enclosed drive includes a
disconnect switch and short circuit protection, and is offered
with a range of power circuit configurations as well as
various control units, in either a wall mount or floor standing
enclosure (depending on HP rating).
The SINAMICS G120E drive includes:
• NEMA 1 enclosure, with blowers (optional NEMA 12 ventilated with air filters)
• Circuit breaker disconnect with flange mount operator
handle, mechanically interlocked with the enclosure door
• UL listing per UL508C
• SCCR (short circuit current rating) 65 kA
• Power module PM240 (non-regenerative) or PM250
(fully regenerative)
• Input line reactor for PM240 (line reactor is not required
for PM250)
• Intelligent operator panel (IOP), door mounted
• CPT for internal 115V, 1 ph AC and if needed a DC power supply
• Windows based STARTER software – common to all models
of the SINAMICS family
Standard features
SINAMICS G120E Fasttrack is available from 1 to 200 HP in
a pre-engineered standard design for quick delivery times,
characterized by:
• Limited range of power circuit configurations and
control options
• “Do-it-yourself” drawing package for any configuration using the Document Configurator (provides list of drawings, bill of material and spare parts list) and published standard
drawings (outline dimensions and schematics).
June 2013
Product Specifications
Light Overload
High Overload
Output (at 460V,
60 Hz)
HP Base load Output
current 1)
(at 460V,
for 110%
60 Hz)
overload
A
HP
1 1.5 2 3
4 5
10
15
20 25
30
40
50
60
75 100
125
150
200
2.2
3.1
4.1
5.9
7.7
10.2
16
22
27
34
41
54
68
80
100
130
160
186
240
1)
2)
1
1.5
2
3
4
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
Base load
Rated
Approx. max.
Power current 1)
output
input current 2) module
for 150%
current1
PM240/PM250
frame size
overload
A
A
A
2.2
3.1
4.1
5.9
7.7
10.2
13.2
19
26
32
38
45
60
75
90
110
145
178
205
2.2
3.1
4.1
5.9
7.7
10.2
16
22
27
34
41
54
68
80
100
130
160
186
240
4.3
5.2
6.3
8.1
10.0
12.4
18.6
25
30
38/34
45/41
59/52
73/65
86/77
108/96
138/124
170/152
194
249
SINAMICS G120E
enclosed drive
with PM240
SINAMICS G120E
enclosed drive
with PM250
Model No.
Model No.
A6SL3710-1BJ12-2AU0
A6SL3710-1BJ13-1AU0
A6SL3710-1BJ14-1AU0
B
6SL3710-1BJ16-0AU0
B
6SL3710-1BJ17-7AU0
B
6SL3710-1BJ21-0AU0
C
6SL3710-1BJ21-8AU0
C
6SL3710-1BJ22-5AU0
C
6SL3710-1BJ23-2AU0
D
6SL3710-1BJ23-8AU0
D
6SL3710-1BJ24-5AU0
D
6SL3710-1BJ26-0AU0
E
6SL3710-1BJ27-5AU0
E
6SL3710-1BJ29-0AU0
F
6SL3710-1BJ31-1AU0
F
6SL3710-1BJ31-5AU0
F
6SL3710-1BJ31-8AU0
F+
6SL3710-1BJ32-0AU0
F+
6SL3710-1BJ32-5AU0
—
—
—
—
—
—
—
—
—
6SL3710-5BJ23-8AU0
6SL3710-5BJ24-5AU0 6SL3710-5BJ26-0AU0
6SL3710-5BJ27-5AU0
6SL3710-5BJ29-0AU0 6SL3710-5BJ31-1AU0 6SL3710-5BJ31-5AU0 6SL3710-5BJ31-8AU0 —
—
The output current is derated to allow for the temperature rise inside the enclosure at an (external) ambient temperature of 104°F (40°C).
The input current is based on the input current of the power module and includes an allowance of 2.0 A (≤60 HP) or 2.5 A (>60 HP) for auxiliary circuits.
The standard SINAMICS G120E base enclosed drive includes:
• NEMA 1 enclosure
• UL508C listing (file no. E319311)
• SCCR (short circuit current rating) 65 kA
• Power module PM240 (non-regenerative), unfiltered or
PM250 (fully regenerative) efficient infeed, unfiltered
• Input line reactor for PM240.
For PM250, a line reactor is not required and not provided.
• Circuit breaker disconnect with mechanical door interlock
• Intelligent operator panel (IOP), door mounted and wired
• Integral braking chopper (for PM240)
• Cable entry top or bottom, line and motor side
The SINAMICS G120E drive is supplied with a control unit, chosen
from the list below:
Please refer to catalog D31 for technical data of the various
SINAMICS G120 control units, including functionality, inputs and
outputs, as well as bus communications ports.
NOTE: Some of the control unit inputs and/or outputs may be used for options.
CU230P-2 is targeted at pump and fan applications.
CU240E-2 is a general purpose control unit.
CU250S-2 offers closed loop speed control and Easy Positioning
(EPos) functionality.
Fasttrack Standard Options
Predesigned standard options are available to tailor the SINAMICS G120E Fasttrack enclosed drive to customer specifications,
maintaining short ex factory delivery times.
Digital and analog
inputs and outputs
Option
protocols
Code Description
Mandatory Option: Control Unit
G80 CU230P-2 HVAC
6DI,3DO,4AI,2AO
G81
G82
G83
G84
G85
G86
G87
G88
G93
G94
G95
CU230P-2 DP
CU230P-2 PN
CU240E-2
CU240E-2 DP
CU250S-2 2)
CU250S-2 DI 2)
CU250S-2 PN 2)
CU240E-2 PN
CU240E-2 F
CU240E-2 DP-F
CU240E-2 PN-F
Bus
Communications
Always choose one CU option
RS485 - USS, Modbus RTU,
BACnet MS/TP
6DI,3DO,4AI,2AO
PROFIBUS DP
6DI,3DO,4AI,2AO PROFINET, EtherNet/IP
6DI,3DO,2AI,2AO, 1 FS-DI 1)
RS485 - USS, Modbus RTU
PROFIBUS DP
6DI,3DO,2AI,2AO, 1 FS-DI 1)
11DI,3DO,4DI/DO,2AI,2AO, 6 FS-DI 1) RS485 - USS, Modbus RTU
11DI,3DO,4DI/DO,2AI,2AO, 6 FS-DI 1) PROFIBUS DP
11DI,3DO,4DI/DO,2AI,2AO, 6 FS-DI 1) PROFINET, EtherNet/IP
PROFINET, EtherNet/IP
6DI,3DO,2AI,2AO, 1 FS-DI 1)
RS485 - USS, Modbus RTU
6DI,3DO,2AI,2AO, 3 FS-DI 1)
PROFIBUS DP
6DI,3DO,2AI,2AO, 3 FS-DI 1)
PROFINET, EtherNet/IP
6DI,3DO,2AI,2AO, 3 FS-DI 1)
Option
Code
Description
Power and General Options
L08 Output reactor
L13 Input contactor. Coil wired to terminals.
L24 Input line reactor 5% nominal impedance (for PM240 only)
L27 Input fuses
L28 Two contactor manual bypass (output/bypass contactors with o/l)
L96 Input surge protective device
M12 NEMA 12 filters
N75 Expanded voltage range (380 V – 480 V supply system)
FS DI = Fail Safe Digital Input. 1 FS DI requires use of 2 DI.
CU250S-2 additionally has inputs for speed feedback and position encoders
Note: If required for the PM240, brake resistors are available as loose components. Refer to catalog D31 for SINAMICS G120 components.
Please consult factory for additional/custom options.
1)
2)
Design Data
FLOOR MOUNT ENCLOSURE
WALL MOUNT ENCLOSURE
Spacing to adjacent units or wall
6” (1-20 HP) or 12” (25-60 HP)
SINAMICS
AIR OUT
SINAMICS
AIR OUT
HN
94” /
2377 mm
AIR IN
AIR IN
DN
WN
SIDE VIEW
FRONT VIEW
AIR IN
24” /
30” /
610 mm
762 mm
SIDE VIEW
FRONT VIEW
Note:
•To assure proper air circulation, please allow minimum 6” (1-20 HP) respectively 12” (25-60 HP) space between adjacent wall mount drive enclosures or
to a side wall.
• Dimensions are nominal for enclosure, tolerance 0.5” (12 mm), excluding protruding components. Please refer to drawings for exact details.
SINAMICS G120E
Output
Noise
Cooling Heat loss
Weight approx.
Drive enclosure
Enclosed drive
(Light level LpA
air flow
Nominal size
Overload) (1m) at demand
(at 460V, 60 Hz) 60 Hz
Model No.
HP
dB(A)
cfmkW lb
kg
inch
mm
WN x DN x HN
Wall mount enclosure
6SL3710-1BJ12-2AU0 1
45 77 0.14 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ13-1AU0 1.5 45 770.15 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ14-1AU0
2
45 77 0.15 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ16-0AU0 3
62 115 0.18 230 104 20 x 16 x 48 508 x 440 x 1219 6SL3710-1BJ17-7AU0 4
62 115 0.19 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ21-0AU0 5
62 115 0.24 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ21-8AU0 10 64 182 0.38 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ22-5AU0 15 64 182 0.44 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-1BJ23-2AU0 20 64 1820.47 230 104 20 x 16 x 48 508 x 440 x 1219
6SL3710-xBJ23-8AU0 25 65 318 0.58 330 150 26 x 20 x 60 660 x 508 x 1524
6SL3710-xBJ24-5AU0 30 65 318 0.68 330 150 26 x 20 x 60 660 x 508 x 1524
6SL3710-xBJ26-0AU0 40 65 318 0.85 330 150 26 x 20 x 60 660 x 508 x 1524
6SL3710-xBJ27-5AU0 50 67
360 1.27 330 150 26 x 20 x 60 660 x 508 x 1524
6SL3710-xBJ29-0AU0 60 67 360 1.49 330 150 26 x 20 x 60 660 x 508 x 1524
WN x DN x HN
Floor mount enclosure
6SL3710-xBJ31-1AU0 75 69 5041.90 720 327 30 x 24 x 94 762 x 610 x 2377
6SL3710-xBJ31-5AU0 100 69 504 2.40 720
327 30 x 24 x 94 762 x 610 x 2377
6SL3710-xBJ31-8AU0 125 69 504 2.80 720
327 30 x 24 x 94
762 x 610 x 2377
6SL3710-1BJ32-0AU0 150 69 504 2.83 760 345 30 x 24 x 94 762 x 610 x 2377
6SL3710-1BJ32-5AU0 200 69 504 2.93 760 345 30 x 24 x 94 762 x 610 x 2377
x = 1 for PM240 non-regenerative power module
x = 5 for PM250 fully regenerative power module
Technical Data
Electrical data
Supply voltages and output ranges
Supply systems
Line frequency
Output frequency
Power factor fundamental, approx.
Drive efficiency
Short circuit current rating
Control method
Fixed speeds
Skipped frequency ranges
Braking operation
Mechanical data
Type of enclosure and color
Type of cooling
Noise level LpA (1 m)
Environmental protection
Compliance with standards
UL listing
Ambient conditions
Ambient temperature
460 V to 480 V (optionally 380 V to 480 V) 3 ph AC, ±10%, 1 to 200 HP
Grounded or ungrounded supplies
47 Hz to 63 Hz
0 Hz to 266 Hz (650 Hz with derating)
0.95
93 to 97%
SCCR 65kA
V/Hz control, V/Hz with flux current control (FCC), Vector control, sensorless or (with CU250) closed loop with encoder
16 fixed frequencies
4, programmable
PM240 with integral brake chopper for dynamic braking, with CU250S-2 DC & compound braking. PM250 fully regenerative.
NEMA 1, optionally NEMA 12 (ventilated), ANSI 61 gray
Forced air ventilation
45 to 69 dB(A) at 60 Hz line frequency
Nickel plated busbars, varnish coated electronic boards
Listed to UL508C, file no. E319311
Operation
Storage
Transport
32°F to 104°F (0°C to +40°C)
-13°F (-25°C) to 131°F (+50°C)
-13°F (-25°C) to 158°F (+70°C)
Up to +122°F/+50°C with derating
Above -40°F (-40 °C) for 24 hours
Relative humidity (non-condensing) 5% to 95%
5% to 95%
5% to 95% at 40°C
Installation altitude
Up to 3,300 ft (1000 m) above sea level without reduction in performance, > 3,300 ft see derating data
Engineering Information
Overload ratings
The SINAMICS G120E drive may be operated
with both variable torque and constant
torque loads at either light or high overload
duties. The criterion for overload is that the
drive is operated with its base load current
before and after the overload occurs.
Light overload duty is based on 110% base
load current for 60 sec or 150% for 3 sec,
repeated every 300 sec.
Light overload
High overload duty is based on 150% base
load current for 60 sec or 200% for 3 sec,
repeated every 300 sec.
Motor and drive sizing
Service Factor must be considered for
motors operating at Service Factors beyond
1.0. Please consult factory for assistance
sizing the drive.
For motors with ratings larger than the
drive, please consult factory as nuisance
tripping may occur if drive is not
properly sized.
In sensorless vector control, the rated
motor current (FLA) must be at least 1⁄4 of
the rated drive output current. With lower
motor currents, operation is possible in
Volts/Hz control mode only.
Intelligent operator panel (IOP)
The SINAMICS IOP makes it easy to operate,
commission and diagnose faults on the
drive. Up to two process values can be
displayed on the screen either graphically
or numerically. Process values can be
displayed in the appropriate technological
units. The user language can be selected.
Due to the large plain text display, menu
prompting and application wizards,
commissioning of drives is very quick.
Siemens Industry, Inc.
Drive Technologies
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
usa.siemens.com/drives
Subject to change without prior notice.
Order No: DRBR-G120E-0613
Printed in USA
©2013 Siemens Industry, Inc.
Parameters are displayed in plain text,
explanatory help texts are provided and
there is a parameter filter function. The
user is interactively navigated through
commissioning of common applications
such as pumps, fans, compressors and
conveyors using application wizards.
The IOP has a dedicated key to toggle
between local (from IOP) and remote
control.
Fault diagnosis is in a user-friendly
fashion using plain text display of faults
and alarms. Explanatory help texts are
provided by pressing the INFO key.
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
terms of contract.
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the rights
of the owners.