SIRIUS Innovations

SIRIUS Innovations.
System Information
SIRIUS
www.usa.siemens.com/sirius-innovations
SIRIUS Innovations.
Technical Information
In recent years, the well proven SIRIUS family was consistently and continuously
Contents
further developed and optimized, both at the product and system level.
Non-fused, electromechanical switching design up to 10 HP
4
The following pages outline the many variations of non-fused motor starter
S00 selection and ordering data:
Motor starter protector, contactor with overload relay
Motor starter protector, contactor with current monitoring relay
5
6
Non-fused, electronic switching design up to 10 HP
7
combinations and matching accessories of SIRIUS Innovations in sizes S00 and S0.
In addition, you will find details on the construction and the combinations of
individual products according to the desired switching and protection method.
For information on all of the combination possibilities – among other things
S00 selection and ordering data:
Motor starter protector, soft starter with current monitoring relay
Motor starter protector, solid-state switching device with current
monitoring relay
8
9
Non-fused, electromechanical switching design up to 30 HP
10
S00 selection and ordering data:
Motor starter protector, contactor, overload relay
Motor starter protector, contactor with current monitoring relay
11
12
Non-fused, electronic switching design up to 30 HP
12
S00 selection and ordering data:
Motor starter protector, soft starter with current monitoring relay
13
on motor starters visit www.usa.siemens.com/sirius-innovations.
Non-fused motor starters
Selection and ordering data:
Direct-on-line start (fully preassembled motor starters,
Compact Starter)
Reversing start (fully preassembled motor starters,
Compact Starter)
14
15
Communications
(IO-Link / AS-Interface Master, contactors, function modules
for 3RT2 contactor mounting and for PLC interface, Compact Starter)
16
Infeed systems
(Compact Starters, motor starters, 3-phase busbar,
8US busbar adapter)
19
Accessories
Selection and ordering data:
Motor starter protectors
Overload relays, current monitoring relays
Contactors
22
23
24
Combination of switching and protective devices
Electromechanical
controls
Fuse with contactor
and overload relay
Motor starter protector Motor starter protector Starter motor starter
for motor protection
for motor protection
protector, contactor
and contactor
with overload relay
and overload relay
function and contactor
Compact Starter
Motor starter protector
for motor protection,
contactor and current
monitoring relay
Motor starter protector for
motor protection with overload
relay function, contactor and
current monitoring relay
Short circuit
Switching
Overload /
Monitoring
M
M
M
M
Fuse-protected
Electronic
controls
Motor starter protector
for motor protection,
soft starter and current
monitoring relay
M
I
I
M
M
Non-fused
Starter motor starter
Fuse and soft starter
protector, soft starter
and current monitoring
relay
Fuse and solid-state
switching device
Fuse, solid-state
switching device and
current monitoring
relay
Motor starter protector
for motor protection
and solid-state
switching device
Motor starter protector for
motor protection, solid-state
switching device and current
monitoring device
M
M
Short circuit
Switching
Overload /
Monitoring
M
M
Non-fused
M
M
Fuse-protected
M
Non-fused
3
Design up to 10 HP (S00)
,
Starter combinations of motor starter protector and contactor
with overload relay
Non-fused, electromechanical switching design
Starter combinations of motor starter protector and
contactor with optional current monitoring relay
1
1
2
2
3
3
4
4
Type
1
Motor starter protector
2
Link module
3
4
Screw connection
Spring-loaded
connection
Type
1
Motor starter protector
2
Link module
Contactor (AC / DC)
3
Contactor (AC / DC)
Overload relay
4
Current monitoring relay
3RA1921-1DA00
3RA2911-2AA00
For order numbers of basic components see tabular overview on page 5
Screw connection
Spring-loaded
connection
3RA1921-1DA00
3RA2911-2AA00
For order numbers of basic components see tabular overview on page 6
4
For export applications
Starter combinations: motor starter
protector, contactor with overload relay
M
Motor starter protector for starter protection
Contactor
Three-phase
motor
400 V/ AC-3
Setting range of
thermal overload
release
CLASS 10
Auxiliary Order no.
contacts
[kW]
[A]
[A]
0.04
0.16
–
3RV2311-0AC
0
0.11 – 0.16 3RU2116-0A
0
0.06
0.2
–
3RV2311-0BC
0
0.14 – 0.2
0.06
0.25
–
3RV2311-0CC
0
0
0
3RB3016-1R
0.09
0.32
–
3RV2311-0DC
0
3RU2116-0B
0.18 – 0.25 3RU2116-0C
0.22 – 0.32 3RU2116-0D
0
(0,1 – 0,4 A)
0.09
0.4
–
3RV2311-0EC
0
0.28 – 0.4
3RU2116-0E
0
0.12
0.5
–
3RV2311-0FC
0
0.35 – 0.5
3RU2116-0F
0
0.18
0.63
–
3RV2311-0GC
0
0
0.18
0.8
–
3RV2311-0HC
0
0.45 – 0.63 3RU2116-0G
0.55 – 0.8 3RU2116-0H
0
3RB3016-1N
0.25
1
–
3RV2311-0JC
0
0.7 – 1
3RU2116-0J
0
(0,32 – 1,25 A)
0.37
1.25
–
3RV2311-0KC
0
1NC
3RT2015-
BB42
3RT2015-
AP02
0.9 – 1.25
3RU2116-0K
0
0.55
1.6
–
3RV2311-1AC
0
1NO
3RT2015-
BB41
3RT2015-
AP01
1.1 – 1.6
3RU2116-1A
0
0.75
2
–
3RV2311-1BC
0
1.4 – 2
3RU2116-1B
0
0.75
2.5
–
3RV2311-1CC
0
1.8 – 2.5
3RU2116-1C
0
3RB3016-1P
1.1
3.2
–
3RV2311-1DC
0
2.2 – 3.2
3RU2116-1D
0
(1 – 4 A)
1.5
4
–
3RV2311-1EC
0
2.8 – 4
3RU2116-1E
0
1.5
5
–
3RV2311-1FC
0
3.5 – 5
3RU2116-1F
0
2.2
6.3
–
3RV2311-1GC
0
4.5 – 6.3
3RU2116-1G
0
3RB3016-1S
3
8
–
3RV2311-1HC
0
5.5 – 8
3RU2116-1H
0
(3 – 12 A)
4
10
–
3RV2311-1JC
0
7 – 10
3RU2116-1J
0
9 – 12.5
3RU2116-1K
0
Order no.
7.5
12.5
16
Setting
range
CLASS 10
AC 230 V, 50/60 Hz
1NC
3RT2016-
BB42
3RT2016-
AP02
1NO
3RT2016-
BB41
3RT2016-
AP01
1NC
3RT2017-
BB42
3RT2017-
AP02
–
1NO
3RT2017-
BB41
3RT2017-
AP01
–
1NC
3RT2018-
BB42
3RT2018-
AP02
1NO
3RT2018-
BB41
3RT2018-
AP01
–
Order no.
Thermal
Order no.
Electronic
CLASS 10
Control supply voltage
0
3RV2311-1KA
3RV2311-4AA
0
–
1) Direct mounting on contactor, screw and
spring-loaded connection possible
2) Voltages on request
Order no.
DC 24 V
–
5.5
Overload relay 1)
Screw connection:
Spring-loaded connection:
1
2
Screw connection:
Spring-loaded
connection:
Ring lug terminal
connection2):
1
2
4
[A]
11 – 16
3RU2116-4A
Screw connection:
Spring-loaded
connection:
Ring lug terminal
connection:
0
0
0
0
0
0
3RB3016-1T
(4 – 16 A)
B Screw connection:
Spring-loaded
C connection:
B
E
J
5
For domestic applications
Starter combinations: motor starter protector,
contactor with optional current
monitoring relay
Three-phase
motor
460 V/AC-3
I
M
Motor starter protector for motor protection
Contactor
Setting range
Order no.
of thermal
overload release
CLASS 10
Aux.
contacts
Order no.
Order no.
Measurement
range
Control supply voltage
110/120 V AC,
DC 24 V
50/60 Hz
[HP]
[A]
[A]
—
0.16
0.11 – 0.16
3RV2011-0AA
0
—
0.2
0.14 – 0.2
3RV2011-0BA
0
—
0.25
0.18 – 0.25
3RV2011-0CA
0
—
0.32
0.22 – 0.32
3RV2011-0DA
0
—
0.4
0.28 – 0.4
3RV2011-0EA
0
—
0.5
0.35 – 0.5
3RV2011-0FA
0
—
0.63
0.45 – 0.63
3RV2011-0GA
0
—
0.8
0.55 – 0.8
3RV2011-0HA
0
—
1
0.7 – 1
3RV2011-0JA
0
0.5
1.25
0.9 – 1.25
3RV2011-0KA
0
1NC
3RT2015-
BB42 3RT2015-
AK62
0.75
1.6
1.1 – 1.6
3RV2011-1AA
0
1NO
3RT2015-
BB41 3RT2015-
AK61
0.75
2
1.4 – 2
3RV2011-1BA
0
1
2.5
1.8 – 2.5
3RV2011-1CA
0
1.5
3.2
2.2 – 3.2
3RV2011-1DA
0
2
4
2.8 – 4
3RV2011-1EA
0
3
5
3.5 – 5
3RV2011-1FA
0
3
6.3
4.5 – 6.3
3RV2011-1GA
0
5
8
5.5 – 8
3RV2011-1HA
0
1NC
3RT2016-
BB42 3RT2016-
AK62
5
10
7 – 10
3RV2011-1JA
0
1NO
3RT2016-
BB41 3RT2016-
AK61
7.5
12.5
9 – 12.5
3RV2011-1KA
0
10
16
11 – 16
2) Voltages on request
Max. 10 HP (S00)
Current monitoring relay
3RV2011-4AA
Screw connection:
Spring-loaded
connection:
Ring lug terminal
connection:
Max. 30 HP (S0)
0
1
2
4
1NC
3RT2017-
BB42 3RT2017-
AK62
3RT2017-
BB41 3RT2017-
AK61
1NC
3RT2018-
BB42 3RT2018-
AK62
1NO
3RT2018-
BB41 3RT2018-
AK61
Screw connection:
Spring-loaded
connection:
Ring lug terminal
connection2):
Motor starters
1
Order no.
Standard
(digital setting)
3RR2141-
3RR2241- F 30
[A]
1.6 – 16
1NO
Order no.
Basic (analog
setting)
Screw connection:
Spring-loaded
connection:
24V AC/DC:
24...240V AC/DC:
2
4
Communications
Infeed systems
A 30
1
2
A
W
Accessories
6
Design up to 10 HP (S00)
Non-fused, electronic switching design
Starter combinations: motor starter protector,
soft starter with optional current monitoring relay
(for stand-alone mounting)
Starter combinations: motor starter protector,
solid-state switching device with optional
current monitoring relay
Type
1
1
Motor starter
protector
2
Link module
3
Soft starter
4
Terminal bracket
for stand-alone
installation
2
5
3
Screw
connection
Spring-loaded
connection
Type
1
3RA2921-1BA00
3RU29 16-3AA01
3RA2911-2GA00
3RU29 16-3AC01
2
Link module
3
Soft starter
4
Terminal bracket
for stand-alone
installation
5
Current
monitoring
relay
Spring-loaded
connection
3RA2921-1BA00
—
3RU29 16-3AA01
3RU29 16-3AC01
See footnote 1) & 4) on the bottom of page 9 for
connection requirements.
3
4
4
5
5
For order numbers of basic components see tabular overview on page 8
Motor starter
protector
2
Current
monitoring
relay
For use of a 3RR2 current monitoring relay with a 3RW30/40
soft starter, a stand-alone adapter is necessary for the 3RR2.
During ramp-up and ramp-down time (phase angle control)
the monitoring relay may not be active:
3RW30: After ramp-up, activate the 3RR2 monitoring relay
via a timing relay
3RW40: Activate/de-activate the 3RR2 monitoring relay via
BYPASS output (ramp-up signal)
1
Screw
connection
For order numbers of basic components see tabular overview on page 9
7
Starter combinations: motor
starter protector, soft starter
with optional current monitoring
relay (for stand-alone mounting)
Three-phase
motor
460 V/AC-3
M
Motor starter protector
Soft starter 1)
Setting range
of thermal
overload
release
CLASS 10
Order no.
Rated
operating
current
Order no.
Current monitoring relay 2)
Order no.
Measurement
range
Order no.
Standard
(digital setting)
Control supply voltage
[HP]
[A]
[A]
—
0.16
0.11 – 0.16
3RV2011-0AA
—
0.2
0.14 – 0.2
3RV2011-0BA
0
—
0.25
0.18 – 0.25
3RV2011-0CA
0
—
0.32
0.22 – 0.32
3RV2011-0DA
0
—
0.4
0.28 – 0.4
3RV2011-0EA
0
—
0.5
0.35 – 0.5
3RV2011-0FA
0
—
0.63
0.45 – 0.63
3RV2011-0GA
0
—
0.8
0.55 – 0.8
3RV2011-0HA
0
—
1
0.7 – 1
3RV2011-0JA
0
0.5
1.25
0.9 – 1.25
3RV2011-0KA
0
0.75
1.6
1.1 – 1.6
3RV2011-1AA
0
0.75
2
1.4 – 2
3RV2011-1BA
0
1
2.5
1.8 – 2.5
3RV2011-1CA
0
1.5
3.2
2.2 – 3.2
3RV2011-1DA
0
2
4
2.8 – 4
3RV2011-1EA
0
3
5
3.5 – 5
3RV2011-1FA
0
3
6.3
4.5 – 6.3
3RV2011-1GA
0
5
8
5.5 – 8
3RV2011-1HA
0
5
10
7 – 10
3RV2011-1JA
0
7.5
12.5
9 – 12.5
3RV2011-1KA
0
12.5
3RW3017-
BB04
3RW3017-
BB14
10
16
11 – 16
3RV2011-4AA
0
17.6
3RW3018-
BB04
3RW3018-
BB14
1) Rated operating voltage 200 ... 480 V
2) In connection with a soft starter, current monitoring
relays must be used with a relay stand-alone mounting.
Screw connection type: 3RU2916-3AA01
Spring-loaded connection type: 3RU2916-3AC01
Order no.
Basic
(analog setting)
Screw connection:
Spring-loaded
connection:
Ring lug terminal
connection:
[A]
AC/DC 24 V
AC/DC 110 – 230 V
3.6
3RW3013-
BB04
3RW3013-
BB14
6.5
3RW3014-
BB04
3RW3014-
BB14
9
3RW3016-
BB04
3RW3016-
BB14
[A]
0
1
2
4
1.6 – 16
Screw connection:
Spring-loaded
connection:
1
2
3RR2141-
Screw connection:
Spring-loaded
connection:
24 V AC/DC:
24...240 V AC/DC:
A
30
3RR2241-
F
30
1
2
A
W
8
Starter combinations: motor
starter protector and solid-state
switching devices with optional
current monitoring relay
Three-phase
motor
460 V/AC-3
Motor starter protector
Solid-state contactor
Setting range of Order no.
thermal overload
release
CLASS 10
Rated operating
current
Current monitoring relay 1)
Order no.
Order no.
Measurement
range
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
Control supply voltage
M
[HP]
[A]
[A]
—
0.16
0.11 – 0.16
[A]
—
0.2
—
0.25
—
3RV2011-0AA
0
0.14 – 0.2
3RV2011-0BA
0
0.18 – 0.25
3RV2011-0CA
0
0.32
0.22 – 0.32
3RV2011-0DA
0
—
0.4
0.28 – 0.4
3RV2011-0EA
0
—
0.5
0.35 – 0.5
3RV2011-0FA
0
—
0.63
0.45 – 0.63
3RV2011-0GA
0
—
0.8
0.55 – 0.8
3RV2011-0HA
0
—
1
0.7 – 1
3RV2011-0JA
0
0.5
1.25
0.9 – 1.25
3RV2011-0KA
0
0.75
1.6
1.1 – 1.6
3RV2011-1AA
0
0
0.75
2
1.4 – 2
3RV2011-1BA
1
2.5
1.8 – 2.5
3RV2011-1CA
0
1.5
3.2
2.2 – 3.2
3RV2011-1DA
0
5.2
DC 24 V
AC 110 – 230 V, 50/60 Hz
3RF3405-
BB04
3RF3405-
2
4
2.8 – 4
3RV2011-1EA
0
5
3.5 – 5
3RV2011-1FA
0
3
6.3
4.5 – 6.3
3RV2011-1GA
0
5
8
5.5 – 8
3RV2011-1HA
0
5
10
7 – 10
3RV2011-1JA
0
9.2
3RF3410-
BB042)
3RF3410-
BB242)
7.5
12.5
9 – 12.5
0
12.5
3RF3412-
BB04
2)
3RF3412-
BB242)
10
16
11 – 16
0
16
3RF3416-
BB04
2)
3RF3416-
BB242)
1) In connection with a solid-state switching device, a
current monitoring relay of size S00 must be used with
the terminal bracket for stand-alone mounting.
Screw connection type: 3RU2916-3AA01
Spring-loaded connection type: 3RU2916-3AA01
2) Overall width 90 mm
3) Rated operating voltage Ue 48 ... 480 V
4) Can be directly mounted on solid-state contactor with
screw connection using a 3RF3900-0QA88 adapter
plug. Spring loaded connection types require the
terminal bracket for stand-alone mounting:
3RU2926-3AC01
3RV2011-4AA
Screw connection:
Spring-loaded connection:
Ring lug terminal
connection:
1
2
4
Screw connection:
Spring-loaded connection:
1
2
Solid-state reversing contactor
1.6 – 16
3RR2141-
A
4 – 16
3RR2142-
A 304)
30
3RR2241-
F
30
3RR2242-
F
304)
BB24
3
3RV2011-1KA
[A]
Screw connection:
Spring-loaded
connection:
24V AC/DC:
24...240V AC/DC:
3)
3.8
3RF3403-1BD04
5.4
3RF3405-1BD04
3RF3405-1BD24
7.4
3RF3410-1BD042)
3RF3410-1BD242)
1
2
A
W
3RF3403-1BD24
9
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor Starters
Communications
Infeed systems
Accessories
30 HP (S0) design
Non-fused, electromechanical switching design
Starter combinations:
motor starter protector, contactor
and overload relay
Starter combinations:
motor starter protector, contactor with
optional current monitoring relay
1
1
2
2
3
3
4
4
Type
Type
1
Motor starter protector
2
Link module1) 2)
3
Contactor
4
Overload relay
AC
DC
Screw connection
Spring-loaded connection
3RA2921-1AA00
3RA2921-1BA00
3RA2921-2AA00
3RA2921-2AA00
1
Motor starter protector
2
Link module1) 2)
3
Contactor
4
Current monitoring relay
AC
DC
Screw connection
Spring-loaded connection
3RA2921-1AA00
3RA2921-1BA00
3RA2921-2AA00
3RA2921-2AA00
1) Max. 32 A
2) No ring lug terminal link modules available
For order numbers of basic components see tabular overview on page 11
For order numbers of basic components see tabular overview on page 11
10
For export applications
Starter combinations:
motor starter protector,
contactor and overload relay
Three-phase
motor
400V/AC-3
M
Motor starter protector for
starter protection
Contactor
Thermal
overload
release
Aux.
contacts
[kW]
[A]
7.5
16
–
3RV2321-4AC
0
7.5
20
–
3RV2321-4BC
0
11
22
–
3RV2321-4CC
0
11
25
–
3RV2321-4DC
0
M
2) Max. 32 A
3) Max. 38 A
4) Voltages on request
Max. 10 HP (S00)
Order no.
Order no.
15
28
–
3RV2321-4NC
0
15
32
–
3RV2321-4EC
0
18.5
36
–
3RV2321-4PC
0
18.5
40
–
3RV2321-4FC
0
Screw connection:
1
1NO+1NC 3RT2025-
110 – 230 V AC/DC UC (AC 50/60 Hz/DC)
1NO+1NC 3RT20261NO+1NC 3RT20271NO+1NC 3RT2028-
Motor starter protector f. motor protection
Contactor
Three-phase
motor
460V/AC-3
Thermal
overload
release
Aux.
contacts
[HP]
[A]
[A]
10
16
11 – 16
3RV2021-4AA
0
10
20
14 – 20
3RV2021-4BA
0
15
22
17 – 22
3RV2021-4CA
0
15
25
20 – 25
3RV2021-4DA
0
20
28
23 – 28
3RV2021-4NA
0
20
32
27– 32
3RV2021-4EA
0
25
36
30 – 36
3RV2021-4PA
0
30
40
34 – 40
3RV2021-4FA
0
Order no.
BB40 3RT2026BB4 0 3RT2027BB4 0 3RT2028-
AP20 3RT2025-
AP20 3RT2026AP20 3RT2027AP20 3RT2028-
N
30
N
30
N
30
N
30
B
F
P
UC 21 ... 28 V:
UC 95 ... 130 V:
UC 200 ... 280 V:
Setting
Order no.
range
Thermal
CLASS 10
Setting
Order no.
range
Electronic
CLASS 10
[A]
[A]
11 – 16
3RU2126-4A
0
14 – 20
3RU2126-4B
0
17 – 22
3RU2126-4C
0
20 – 25
3RU2126-4D
0
23 – 28
3RU2126-4N
0
27 – 32
3RU2126-4E
0
30 – 36
3RU2126-4P
0
34 – 40
3RU2126-4F
0
Screw connection:
Spring-loaded connection:
Ring lug terminal
connection:
Order no.
Order no.
3RB3026 -1Q
0
10 – 40
3RB3026- 1V
0
Screw connection:
Spring-loaded
connection
B
E
J
Measure- Order no.
ment
Basic
range
(analog setting)
Order no.
Control supply voltage
120 V AC (60 Hz)
UC (AC 50/60 Hz/DC)
1NO+1NC 3RT2025-
BB40
3RT2025-
AK60 3RT2025-
N
30
1NO+1NC 3RT2026-
BB40
3RT2026-
AK60 3RT2026-
N
30
1NO+1NC 3RT2027-
BB40
3RT2027-
AK60 3RT2027-
N
30
1NO+1NC 3RT2028-
BB40
3RT2028-
AK60 3RT2028-
N
30
1
Screw connection:
Spring-loaded connection 3): 2
Ring lug terminal
4
connection 4):
B
UC 21 ... 28 V:
UC 95 ... 130 V: F
UC 200 ... 280 V: P
Communications
Order no.
Standard
(digital setting)
[A]
4 – 40
Motor Starters
B
C
6 – 25
Current monitoring relay
DC 24 V
1
Screw connection:
Spring-loaded connection 2): 2
Ring lug terminal
4
connection 2):
Max. 30 HP (S0)
BB40 3RT2025-
1
Screw connection:
Spring-loaded connection 3): 2
Ring lug terminal
4
connection 4):
Spring-loaded connection 2): 2
Order no.
Control supply voltage
DC 24 V
For domestic applications
Starter combinations:
motor starter protector,
contactor with optional
current monitoring relay
I
Order no.
Overload relay
3RR2142- A
Screw connection:
Spring-loaded
connection:
24 V AC/DC:
24...240 V AC/DC:
Infeed systems
30
3RR2142-
F
30
1
2
A
W
11
Accessories
Design up to 30 HP (S0)
Non-fused, electronic switching design
Starter combinations:
motor starter protector,
3RW30 soft starter with
optional current monitoring
relay (for stand-alone
mounting)
Starter combinations:
3RW40 soft starter (integrated
electronic overload relay) with
optional current monitoring
relay (for stand-alone mounting)
Type
1
1
Motor starter
protector
2
Link module
3
Soft starter
Screw
connection
Spring-loaded
connection
Type
Motor starter
protector
2
Link module
3
Soft starter
4
Terminal bracket
for stand-alone
installation
5
Current
monitoring
relay
Spring-loaded
connection
3RA2921-1BA00
3RA2911-2GA00
3RU29 26-3AA01
3RU29 26-3AC01
1
3RA2921-1BA00
3RA2911-2GA00
4 Terminal bracket
for stand-alone
installation
2
5
3
1
Screw
connection
3RU29 26-3AA01
3RU29 26-3AC01
2
Current
monitoring
relay
For use of a 3RR2 current monitoring relay with a 3RW30/40 soft
starter, a stand-alone adapter is necessary for the 3RR2. During
ramp-up and ramp-down time (phase angle control) the monitoring
relay may not be active:
3RW30: After ramp-up, activate the 3RR2 monitoring relay via a
timing relay
3RW40: Activate/de-activate the 3RR2 monitoring relay via BYPASS
output (ramp-up signal)
4
3
4
5
5
1) Only suitable up to 32 A
For order numbers of basic components see tabular overview on page 13
For order numbers of basic components see tabular overview on page 13
12
For domestic applications
Starter combinations: motor starter protector,
3RW30 soft starter with optional current
monitoring relay (for stand-alone mounting)
Motor starter protector for motor protection
Soft starter1)
Three-phase
motor
460 V/AC-3
Setting range,
thermal
overload
release
CLASS 10
Rated
Order no.
operating
current
[HP]
[A]
[A]
15
22
17 – 22
Order no.
Current monitoring relay
Order no.
Measurement
range
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
Control supply voltage
M
3RV2021-4CA
0
15
25
20 – 25
3RV2021-4DA
0
20
28
23 – 28
3RV2021-4NA
0
20
32
27 – 32
3RV2021-4EA
0
25
36
30 – 36
3RV2021-4PA
0
30
40
34 – 40
3RV2021-4FA
0
30
40
34 – 40
3RV2021-4FA
0
[A]
AC/DC 24 V
25
3RW3026-
BB04
AC/DC 110 – 230 V
3RW3026-
BB14
32
3RW3027-
BB04
3RW3027-
BB14
38
3RW3028-
BB04
3RW3028-
BB14
45
3RW3036-
BB04
3RW3036-
BB14
[A]
3RR2142-
4 – 40
A 30 3RR2242-
F 30
For export applications
Starter combinations: motor starter protector,
3RW40 soft starter (integrated electronic
overload relay) with optional current monitoring
relay (for stand-alone mounting)
Three-phase
motor
400 V/AC-3
[kW]
M
[A]
Motor starter protector for starter protection
Soft starter 1)
Setting range
of thermal
overload
release
CLASS 10
Rated
Order no.
operating
current
5.5
12.5
–
3RV2311-1KC
0
7.5
16
–
3RV2321-4AC
0
7.5
20
–
3RV2321-4BC
0
11
22
–
3RV2321-4CC
0
11
25
–
3RV2321-4DC
0
15
28
–
3RV2321-4NC
0
15
32
3RV2321-4EC
0
18.5
36
3RV2321-4PC
0
18.5
40
3RV2321-4FC
0
Max. 30 HP (S0)
Current monitoring relay
Order no.
Measurement
range
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
Control supply voltage
[A]
1) Note: In connection with a soft starter, a current
monitoring relay must be used with the terminal
bracket for stand-alone mounting.
Screw connection type: 3RU2926-3AA01
Spring-loaded connection type: 3RU2926-3AC01
Max. 10 HP (S00)
Order no.
Screw connection:
Spring-loaded
connection:
1
2
[A]
AC/DC 24 V
AC/DC 110 – 230 V
12.5
3RW4024-
BB04
3RW4024-
BB14
25
3RW4026-
BB04
3RW4026-
BB14
[A]
4 – 40
32
3RW4027-
BB04
38
3RW4028-
BB02
Screw connection:
Spring-loaded
connection:
Motor starters
3RW4027-
3RR2142-
A 30 3RR2242-
F 30
BB14
–
1
Screw connection:
Spring-loaded
connection:
24 V AC/DC:
24...240 V AC/DC:
2
Communications
Infeed systems
1
2
A
W
13
Accessories
Non-fused motor starters
Direct-on-line starter,
fully preassembled,
electromechanical
3RA21 direct-on-line starter
M
3RA61 Compact Starter
Three-phase
motor
400 V/AC-3
Setting range
of thermal
overload
release
[kW]
[A]
[A]
0.06
0.20
0.14 – 0.2
3RA2110-0B
15-1
S00
0.06
0.25
0.18 – 0.25
3RA2110-0C
15-1
S00
0.09
0.32
0.22 – 0.32
3RA2110-0D
15-1
S00
0.09
0.40
0.28 – 0.4
3RA2110-0E
15-1
S00
0.12
0.50
0.35 – 0.5
3RA2110-0F
15-1
S00
0.18
0.63
0.45 – 0.63
3RA2110-0G
15-1
S00
0.18
0.80
0.55 – 0.8
3RA2110-0H
15-1
S00
0.25
1.0
0.7 – 1
3RA2110-0J
15-1
S00
0.37
1.25
0.9 – 1.25
3RA2110-0K
15-1
S00
0.55
1.6
1.1 – 1.6
3RA2110-1A
15-1
S00
0.75
2.0
1.4 – 2
3RA2110-1B
15-1
S00
0.75
2.5
1.8 – 2.5
3RA2110-1C
15-1
S00
1.1
3.2
2.2 – 3.2
3RA2110-1D
15-1
S00
1.5
4.0
2.8 – 4
3RA2110-1E
15-1
S00
1.5
5.0
3.5 – 5
3RA2110-1F
15-1
S00
2.2
6.3
4.5 – 6.3
3RA2110-1G
15-1
S00
3
8
5.5 – 8
3RA2110-1H
16-1
S00
4
10
7 – 10
3RA2110-1J
16-1
S00
5.5
12.5
9 – 12.5
3RA2110-1K
17-1
S00
7.5
16
11 – 16
3RA2120-4A
26-0
S0
7.5
20
14 – 20
3RA2120-4B
26-0
S0
11
22
17 – 22
3RA2120-4C
27-0
S0
11
25
20 – 25
3RA2120-4D
27-0
S0
15
32
27 – 32
3RA2120-4E
27-0
S0
1) CPS: Control and protective switching
device, IEC/EN 60947-6-2
2) If used in the 3RA68 Infeed system, please
use 3 instead of 2. If used with AS-i
module, please use “4” instead of “2”.
Setting range
of thermal
overload
release
Coordination
type 2 CPS1)
[A]
Screw connection (for mounting onto DIN rail):
Spring-loaded connection (for mounting onto DIN rail):
Screw connection (busbar adapter):
Spring-loaded connection (busbar adapter):
A
E
D
H
24 V DC:
120 V AC:
B B 4
A K 6
0.1 – 0.4
3RA6120-
A
3
0.32 – 1.25
3RA6120-
B
3
1–4
3RA6120-
C
3
3– 12
3RA6120-
D
3
8 – 32
3RA6120-
E
3
Without terminals:
With screw connection:
With spring-loaded
connection:
24 V AC/DC
42 ... 70 V AC/DC
110 ... 240 V AC/DC
0
1
0
2
2
2
B
E
P
2)
2)
14
Reversing starter,
fully preassembled
3RA62 Compact Starter
3RA22 reversing starter
M
Setting range
of thermal
overload
release
Three-phase
motor
400 V/AC-3
Setting
range
of thermal
overload
release
[kW]
[A]
[A]
0.06
0.20
0.14 – 0.2
3RA2210-0B
15-2
S00
0.06
0.25
0.18 – 0.25
3RA2210-0C
15-2
S00
0.09
0.32
0.22 – 0.32
3RA2210-0D
15-2
S00
0.09
0.40
0.28 – 0.4
3RA2210-0E
15-2
S00
0.12
0.50
0.35 – 0.5
3RA2210-0F
15-2
S00
0.18
0.63
0.45 – 0.63
3RA2210-0G
15-2
S00
0.18
0.80
0.55 – 0.8
3RA2210-0H
15-2
S00
0.25
1.0
0.7 – 1
3RA2210-0J
15-2
S00
0.37
1.25
0.9 – 1.25
3RA2210-0K
15-2
S00
0.55
1.6
1.1 – 1.6
3RA2210-1A
15-2
S00
0.75
2.0
1.4 – 2
3RA2210-1B
15-2
S00
0.75
2.5
1.8 – 2.5
3RA2210-1C
15-2
S00
1.1
3.2
2.2 – 3.2
3RA2210-1D
15-2
S00
1.5
4.0
2.8 – 4
3RA2210-1E
15-2
S00
1.5
5.0
3.5 – 5
3RA2210-1F
15-2
S00
2.2
6.3
4.5 – 6.3
3RA2210-1G
15-2
S00
3
8
5.5 – 8
3RA2210-1H
16-2
S00
4
10
7 – 10
3RA2210-1J
16-2
S00
5.5
12.5
9 – 12.5
3RA2210-1K
17-2
S00
7.5
16
11 – 16
3RA2220-4A
26-0
S0
7.5
20
14 – 20
3RA2220-4B
26-0
S0
11
22
17 – 22
3RA2220-4C
27-0
S0
11
25
20 – 25
3RA2220-4D
27-0
S0
15
32
27 – 32
3RA2220-4E
27-0
S0
1) CPS: Control and protective switching
device, IEC/EN 60947-6-2
2) If used in the 3RA68 Infeed system, please
use 3 instead of 2. If used with AS-i
module, please use “4” instead of “2”.
Coordination
type 2 CPS 1)
[A]
Screw connection (for mounting onto DIN rail) S00:
Screw connection (for mounting onto DIN rail) S0:
Spring-loaded connection (for mounting onto DIN rail) S00:
Spring-loaded connection (for mounting onto DIN rail) S0:
Screw connection (busbar adapter):
Spring-loaded connection (busbar adapter):
A
B
E
F
D
H
24 V DC:
120 V AC:
B B 4
A K 6
0.1 – 0.4
3RA6250-
A
3
0.32 – 1.25
3RA6250-
B
3
1–4
3RA6250-
C
3
3– 12
3RA6250-
D
3
8 – 32
3RA6250-
E
3
Without terminals:
With screw connection:
With spring-loaded
connection:
24 V AC/DC
42 ... 70 V AC/DC
110 ... 240 V AC/DC
0
2
0
1
2
2
2)
2)
B
E
P
15
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor starters
Communications
Infeed systems
Accessories
Communications – general information and contactors
Interfacing motor starters to the control system requires function modules for IO-Link or AS-i which are mounted
on contactors (24V DC) with a communication interface. Depending on the version, they communicate with an
IO-Link interface group or any AS-i Master.
Motor
Starter
Protection
Typical layout in the
environment of IO-Link
Contactor
IO-Link
PROFIBUS
PROFINET/Ethernet
Version
Order no.
ET200S electronic module, 4SI IO-Link (with 4 ports
for 4 motor starters each)
6ES7 138-4GA50-0AB0
ET200S electronic module, 4SI SIRIUS (with 4 ports
for 4 motor starters each)
3RK1005-0LB00-0AA0
ET200S terminal module (15mm wide)
IO-Link
– With screw terminal
TM-E15S26-A1 6ES7
– With spring-loaded terminal
TM-E15C26-A1 6ES7
– With Fast Connect
TM-E15N26-A1 6ES7
Mounting principle of function modules on contactors
S00 contactor with communication interface
Typical layout in the
environment of AS-Interface
AS-Interface
Three-phase motor
460 V/AC-3
AS-Interface
Order no.
[HP]
[A]
CP343-2P communication processor for interfacing
SIMATIC S7-300 to AS-Interface (AS-i Spec.3.0) for
max. 62 motor starters
6GK7343-2AH11-0XA0
3
7
Front connector, 20-pin with screw contacts
6ES7392-1AJ00-0A00
Front connector, 20-pin with spring-loaded contacts
6ES7392-1BJ00-0AA0
Version
5
DP/AS-i LINK Advanced, gateway between PROFIBUS
DP and AS-Interface
– Single master for max. 62 motor starters
6GK1415-2BA10
– Double master for max. 124 motor starters
6GK1415-2BA20
IE/AS-i LINK PN IO, gateway between PROFINET and
AS-Interface
Single master for max. 62 motor starters
6GK1411-2AB10
Double master for max. 124 motor starters
6GK1411-2AB20
AS-Interface power supply unit IP20
– 120/230 V AC 3A
3RX9501-0BA00
– 24 V DC 3A
3RX9501-1BA00
– 120/230 V AC 5A
3RX9502-0BA00
– 120/230 V AC 8A
3RX9503-1BA00
9
Auxiliary
contacts
Control supply voltage
Order no.
DC 24 V
1NC
3RT2015- BB42-0CC0
1NO
3RT2015- BB41-0CC0
1NC
3RT2016- BB42-0CC0
1NO
3RT2016- BB41-0CC0
3RT2017- BB42-0CC0
7.5
12
1NC
1NO
3RT2017- BB41-0CC0
10
16
1NC
3RT2018- BB42-0CC0
1NO
3RT2018- BB41-0CC0
S0 contactor with communication interface
7.5
12
1NO+1NC
3RT2024- BB40-0CC0
10
12
1NO+1NC
3RT2025- BB40-0CC0
15
25
1NO+1NC
3RT2026- BB40-0CC0
20
32
1NO+1NC
3RT2027- BB40-0CC0
25
38
1NO+1NC
3RT2028- BB40-0CC0
Screw connection:
Spring-loaded connection:
1
2
16
Function modules for mounting on 3RT2 contactors and for interfacing with the control system
Parallel
wiring
Direct-on-line start
Reversing start
Wye-delta start
Order no.
Order no.
On-delay
3RA2811-
CW10
Wiring kit for contactors
S00
Off-delay
(with auxiliary voltage)
DW10
Wiring kit for contactors with screw
connection
S0
3RA2812-
Order no.
3RA2816-0EW20
Function module 4)
3RA2913-2AA
Wiring kit for contactors 1)
S00
3RA2913-2BB
Wiring kit for contactors 1)
S0
3RA2923-2BB
3RA2923-2AA
IO-Link
Direct-on-line start 1)
Reversing start 1) 2) 3)
2)
Wye-delta start 1) 2) 4)
Order no.
Function module
Order no.
AA00
3RA2711-
Function module
3RA2711-
Order no.
BA00
Function module
3RA2711-
CA00
Wiring kit for contactors
S00
3RA2913-2AA
Wiring kit for contactors
S00
3RA2913-2BB
Wiring kit for contactors
S0
3RA2923-2AA
Wiring kit for contactors
S0
3RA2923-2BB
AS-Interface
Direct-on-line start 1)
Reversing start 1) 2) 3)
2)
Star-delta start 1) 2) 4)
Order no.
Function module
Order no.
AA00
3RA2712-
Screw connection:
Spring-loaded connection:
Function module
3RA2712-
Order no.
BA00
Function module
3RA2712-
CA00
Wiring kit for contactors
S00
3RA2913-2AA
Wiring kit for contactors
S00
3RA2913-2BB
Wiring kit for contactors
S0
3RA2923-2AA
Wiring kit for contactors
S0
3RA2923-2BB
1
2
Screw connection:
Spring-loaded connection:
1
2
1
2
Screw connection:
Spring-loaded connection:
The above shown contactor assemblies can be combined with motor starter protector, overload and current monitoring relay (see the descriptions on previous pages)
1) The wiring modules for control circuit are not required when using function modules with communications interface
2) The contactor upon which the basic module is fitted must be selected as a communication contactor (see page 16)
3) Consisting of 1 basic module and 1 interface module
4) Consisting of 1 basic module and 2 interface modules
17
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor starters
Communications
Infeed systems
Accessories
Communications – Compact Starter
IO-Link
Setting range
of thermal
overload release
M
3RA64 direct-on-line starter 2) 3RA65 reversing starter 2)
Accessories for Compact Starter with IO-Link and 3RA27 function module
Coordination type 2 / CPS
Ribbon cable, 14-pin, 8 cm,
for small gaps between two contactors
3RA2711-0EE02
Module connector, 14-pin, 21 cm,
for wider gaps between two contactors
3RA2711-0EE03
Operator panel,
(incl. enabling module and blanking cover)
3RA6935-0A
Connecting cable for
control module, 2 meters
3RA6933-0A
1)
Coordination type 2 / CPS
[A]
24 V DC
0.1 – 0.4
3RA6400-
AB42
3RA6500-
AB42
0.32 – 1.25
3RA6400-
BB42
3RA6500-
BB42
1–4
3RA6400-
CB42
3RA6500-
CB42
3 – 12
3RA6400-
DB42
3RA6500-
DB42
8 – 32
3RA6400-
EB42
3RA6500-
EB42
1)
24 V AC/DC
AS-Interface
+
M
=
Setting range
of thermal
overload release
[A]
3RA61 direct-on-line starter
3RA62 reversing starter
Accessories for AS-Interface
Coordination type 2 / CPS1)
Coordination type 2 / CPS1)
AS-i addressing unit
AC/DC 24 V
AC/DC 24
AS-Interface add-on modules for 3RA6 Compact Starter (24 V DC )
0.1 – 0.4
3RA6120-
AB34
3RA6250-
AB34
Without additional inputs/outputs
3RA6970-3A
0.32 – 1.25
3RA6120-
BB34
3RA6250-
BB34
With two local inputs
3RA6970-3B
1–4
3RA6120-
CB34
3RA6250-
CB34
With two free external inputs
3RA6970-3C
3 – 12
3RA6120-
DB34
3RA6250-
DB34
With one free external input and output each
3RA6970-3D
8 – 32
3RA6120-
EB34
3RA6250-
EB34
With two free external outputs
3RA6970-3E
1) CPS: Control and protective
Screw connection:
switching device,
Spring-loaded
IEC/EN 60947-6-2
connection:
2) For 3RA6 Compact Starter
accessories for IO-Link or for
use in the infeed system, please
refer to the Compact Starter
brochure: GCBR-A840P-0110
3RK1904-2AB01
1
2
18
3RA68 Infeed system (Compact Starter)
Type
1
2
1
3
4
5
8
Terminal type
Order no.
Screw-type infeed 4-2 AWG left with permanently
attached triple expansion module
Screw connection
3RA6812-8AB
Screw-type infeed 4-2 AWG left with permanently
attached triple expansion module
Spring-loaded
connection
3RA6812-8AC
Screw-type infeed 0-2/0 AWG left with permanently
attached triple expansion module
Screw connection
3RA6813-8AB
Screw-type infeed 0-2/0 AWG left with permanently
attached triple expansion module
Spring-loaded
connection
3RA6813-8AC
3-phase infeeds
3RA6830-5AC
Spring-loaded infeed 4-2 AWG
left or right up to 63 A
9
Expansion modules
NSB0_01878
6
3
Double expansion module with 2 slots
Screw connection
2
Triple expansion module with 3 slots
Screw connection
3RA6823-0AB
Double expansion module with 2 slots
Spring-loaded connection
3RA6822-0AC
Triple expansion module with 3 slots
Spring-loaded connection
3RA6823-0AC
4
5
10
Expansion plug
3RA6890-1AB
Expansion plug between 2 expansion
modules already included in the
delivery scope of the expansion
modules
7
7
Items 6 and 9 already included in the scope of delivery
6
3RA6822-0AB
PE infeed
PE supply 4-2 AWG
Screw connection
3RA6860-6AB
PE supply 4-2 AWG
Spring-loaded connection
3RA6860-5AC
PE tap-off 10-8 AWG
Screw connection
3RA6870-4AB
PE tap-off 10-8 AWG
Spring-loaded connection
3RA6870-3AC
PE tap-offs
PE expansion plug
3RA6890-0EA
Adapter for SIRIUS 3RV1 motor starter protector
10
Adapter 45 mm for 3RV1
for motor starter protector with screw connection
3RA6890-0BA
Expansion plug for SIRIUS 3RV29 Infeed system
3RA6890-1AA
Terminal block to integrate 1-, 2- or 3-pole
components
Spring-loaded
onnection
3RV2917-5D
19
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor Starters
Communications
Infeed systems
Accessories
3RV29 Infeed system (motor starter protector and motor starter)
85
55
11
7
3b
3
3a
22
Type
44
1
2
Version
Size for
3RV20,
3RV23
motor starter
protectors
Order no.
3-phase busbars
with infeed on the left
incl. end cover
3RV2917-6A
For 2 motor starter
protectors
S00, S0
3RV2917-1A
with infeed on the right
incl. end cover
3RV2917-6A
For 2 motor starter
protectors
S00, S0
3RV2917-1E
For system expansion
incl. expansion plug
3RV2917-5BA00
For 2 motor starter
protectors
S00, S0
3RV2917-4A
For system expansion
incl. expansion plug
3RV2917-5BA00
For 3 motor starter
protectors
S00, S0
3RV2917-4B
Connector
8
For contacting the motor
starter protectors
Screw
connection
1 pc.
S00
10 pcs. S00
Spring-loaded 1 pc.
S00
connection
10 pcs. S00
3RV2917-5AA00
Screw
connection
3RV1927-5CA00
1 pc.
S0
10 pcs. S0
Spring-loaded 1 pc.
S0
connection
10 pcs. S0
5
3RV2917-5CA00
3RV2917-5C
3RV2917-5A
3RV1927-5C
3RV2927-5AA00
3RV2927-5A
Accessories
66
97
6
Contactor base for building up direct-on-line or
reversing starters
9
Terminal block to integrate 1-, 2- or 3-pole
components
7
1 pc.
S00, S0
3RV2927-7AA00
3RV2917-5D
DIN rail, 45 mm, to integrate other
devices into the system, such as
5SY motor starter protectors
3RV1917-7B
Wider expansion plug
3RV2917-5E
Spare parts
3
4
Expansion plug
3RV2917-5BA00
End cover
3RV2917-6A
20
3-phase comb busbars / 8US busbar adapters for supply
Type
1
1
2
2
1
Size
Order no.
3-phase comb busbars
For supplying several 3RV2
motor starter protectors
(screw-connected) mounted
side by side on DIN rails,
safe to touch
For 2 motor starter protectors
For 3 motor starter protectors
Modular
spacing
45 mm
Modular
spacing
55 mm
Modular
spacing
63 mm
S00, S0
3RV1915-1AB
3RV1915-2AB
3RV1915-3AB
S00, S0
3RV1915-1BB
3RV1915-2BB
–
For 4 motor starter protectors
S00, S0
3RV1915-1CB
3RV1915-2CB
3RV1915-3CB
For 5 motor starter protectors
S00, S0
3RV1915-1DB
3RV1915-2DB
–
Connection from the top
S00, S0
3RV2925-5AB
Connection from the bottom
S00, S0
3RV2915-5B
2 3-phase supply terminals
3-phase supply terminals to build up “type E starters”
Connection from the top
S00, S0
3RV2925-5EB
S00, S0
3RV1915-6AB
Accessories
Cover caps for connecting lugs
Touch protection for unassigned slots
Type
3
3
Size
4
Order no.
200 mm
8US1251-5DS10
260 mm
8US1251-5DT10
260 mm
8US1251-5NT10
260 mm
8US1251-5DT11
260 mm
8US1251-5NT11
200 mm
8US1250-5AS10
260 mm
8US1250- 5AT10
200 mm
8US1998-2BJ10
Busbar adapter for 60 mm system
For motor starters
Rated current 25A for screw connection
For motor starters
Rated current 25 A for screw connection
For motor starters
Rated current 32 A for screw connection
For motor starters
Rated current 25 A for spring-loaded connection
For motor starters
Rated current 32 A for spring-loaded connection
4
Version
(Length)
S00/S0
S00/S0
S00/S0
S00/S0
S00/S0
Accessories
Support
for side mounting on busbar adapter, 45 mm wide
Support
for side mounting on busbar adapter, 45 mm wide
Side module
to widen the busbar adapter, 9 mm wide
Spacer
Fixes the motor starter onto the busbar adapter
Vibration/shock kit
To compensate strain from higher vibration and shock
8US1998-1BA10
8US1998-1CA10
21
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor Starters
Communications
Infeed systems
Accessories
Accessories for 3RV2 motor starter protector (S00, S0)
Type
8
1
Version
Order no.
Order no.
Screw connection Spring-loaded
connection
Order no.
Ring lug terminal
connection
Accessories for 3RV2 motor starter protector, size S00, S0
1
Auxiliary and Signalling Contacts
Front mounted auxiliary block
3
2
2
4
5
1CO
3RV2901-1D
–
–
1NO + 1NC
3RV2901-1E
3RV2901-2E
3RV2901-4E
2NO
3RV2901-1F
3RV2901-2F
–
Auxiliary switch suited for electronic components
1CO
3RV2901-1G
–
–
Side mounted auxiliary block
with 2 contacts
1NO + 1NC
3RV2901-1A
3RV2901-2A
3RV2901-4A
2NO
3RV2901-1B
3RV2901-2B
–
2NC
3RV2901-1C
3RV2901-2C
–
3
Side mounted auxiliary block with 4 contacts 2NO +2NC
3RV2901-1J
–
–
4
Signaling switch
3RV2921-1M
3RV2921-2M
3RV2921-4M
20 – 70V AC/DC
3RV2902-1DB0
3RV2902-2DB0
3RV2902-4DB0
210 – 240 V AC
3RV2902-1DP0
3RV2902-2DP0
–
120 V AC
3RV2902-1AF0
–
–
400 V AC
3RV2902-1AV0
3RV2902-2AV0
3RV2902-4AV0
230...240 V AC
3RV2922-1CP0
3RV2922-2CP0
–
400...440 V AC
3RV2922-1CV0
3RV2922-2CV0
–
415...480 V AC
3RV2922-1CV1
3RV2922-2CV1
3RV2922-4CV1
Isolator module
3RV2928-1A
–
–
Terminal block type E
for higher creepage distances and air clearances
3RV2928-1H
–
–
Phase barriers
for higher creepage distances and air clearances
3RV2928-1K
–
–
Auxiliary release
5
6
6
Shunt trip1)
Undervoltage release1)
Undervoltage release
with 2 NO leading auxiliary contacts
Terminals for “Combination Motor Controller Type E”
8
Type
Version 2)
Order no.
Extension shaft
130 mm
3RV2926-0B
Extension shaft
330 mm
3RV2926-0K
Extension shaft
130 mm
3RV2926-0C
Extension shaft
330 mm
3RV2926-0L
For motor starter protector ( + Side mounted auxiliary block)
54 mm
3RV1923-1CA00
For motor starter protector ( + Side mounted auxiliary block + auxiliary release)
72 mm
3RV1923-1DA00
Molded-plastic housing with EMERGENCY STOP
rotary door-coupling operating mechanism
For motor starter protector ( + Side mounted auxiliary block)
54 mm
3RV1923-1FA00
For motor starter protector ( + Side mounted auxiliary block + auxiliary release)
72 mm
3RV1923-1GA00
Rotary door-coupling operating mechanisms
Rotary door-coupling operating mechanism (black) with
EMERGENCY STOP rotary door-coupling operating mechanism (red/yellow) with
Molded-plastic housing
1) More versions on request
2) Only available as screw-connected versions
22
Accessories for 3RU21 thermal overload relay, 3RB30/31 electronic overload relay,
3RR21 analog current monitoring relay and 3RR22 digital current monitoring relay (S00,S0)
Version
For size
Order no.
Can be combined with the following overload
and current monitoring relays
3RU2
3RB3
3RR21
3RR22
Terminal bracket for stand-alone mounting
For mounting the overload relays separately
S00
3RU2916-3A
01
For screw and snap-on mounting on TH 35 DIN rail
S0
3RU2926-3A
01
Reset slide, holder and funnel
S00, S0
3RU2900-1A
Reset slide, holder and funnel
S00, S0
3RB3980-0A
Push-button with elongated stroke (12 mm),
IP65, Ø 22 mm
S00, S0
3SB3000-0EA11
Extension tappet to even out the spacing between a pushbutton and the reset button of the relay
S00, S0
3SX1335
Mechanical RESET consisting of:
Cable release with holder for RESET for bores Ø 6.5 mm in the control panel
Length 400 mm
S00, S0
3RU2900-1B
Length 400 mm
S00, S0
3RB3980-0B
Length 600 mm
S00, S0
3RU2900-1C
Length 600 mm
S00, S0
3RB3980-0C
For covering the setting components
S00, S0
3RV2908-0P
For covering the setting components
S00, S0
3RB3984-0
For covering the setting components
S00, S0
3RR2940
24 ... 30 V AC/DC
S00, S0
3RU1900-2AB71
110 ... 127 V AC/DC
S00, S0
3RU1900-2AF71
220 ... 250 V AC/DC
S00, S0
3RU1900-2AM71
Sealable cover for 3RB20/21, transparent
Modules for remote reset, electrical
A
Screw connection:
Spring-loaded connection: C
23
Max. 10 HP (S00)
Max. 30 HP (S0)
Motor starters
Communications
Infeed systems
Accessories
Accessories for 3RT201 contactors (S00)
5
13
1
6
2
2
8
7
3
8
3
1
4
4
1
11
Front mounting auxiliary
contacts for
Version
3RT2 contactors
Standard
see tabular overview on page 5ff.
Communication
see page 16
5
3RH2911-1AA10
–
–
3RH2911-1AA01
–
–
2-pole auxiliary contact block,
cable entry from the top
1NO + 1NC
3RH2911-1LA11
–
–
2NO
3RH2911-1LA20
–
–
1-pole auxiliary contact block,
cable entry from the bottom
1NO
3RH2911-1BA10
–
–
1NC
3RH2911-1BA01
–
–
2-pole auxiliary contact block,
cable entry from the bottom
1NO + 1NC
3RH2911-1MA11
–
–
2NO
3RH2911-1MA20
–
–
4-pole auxiliary contact blocks1),
(in compliance with DIN EN 50 012
and DIN EN 50 005)
1NC
3RH2911-1HA01
3RH2911-2HA01
3RH2911-4HA01
2NC
3RH2911-1HA02
3RH2911-2HA02
3RH2911-4HA02
1NO + 1NC
3RH2911-1HA11
3RH2911-2HA11
3RH2911-4HA11
2NO + 2NC
3RH2911-1HA22
3RH2911-2HA22
3RH2911-4HA22
1NO
3RH2911-1HA10
3RH2911-2HA10
3RH2911-4HA10
2NO
3RH2911-1HA20
3RH2911-2HA20
3RH2911-4HA20
1NO + 1NC
3RH2911-1NF11
3RH2911-2NF11
–
2NO
3RH2911-1NF20
3RH2911-2NF20
–
2NC
3RH2911-1NF02
3RH2911-2NF02
–
Auxiliary contact blocks suitable for
electronic components
(2-pole)
(in compliance with DIN EN 50 005)
6
7
8
Order no. Ring lug
terminal connection
1NO
9
10
Order no.
Spring-loaded connection
1NC
1-pole auxiliary contact block,
cable entry from the top
12
8
Order no.
Screw connection
see page 17 (Function modules for mounting on contactors and for interfacing the control system)
Size-specific accessories for 3RT201 contactors (S00)
Auxiliary contact blocks for side
mounting
(in compliance with DIN EN 50 012
and DIN EN 50 005)
2NO
3RH2911-1DA20
3RH2911-2DA20
–
1NO + 1NC
3RH2911-1DA11
3RH2911-2DA11
3RH2911-4DA11
2NC
3RH2911-1DA02
3RH2911-2DA02
–
Auxiliary contact block suited for electronic
components for side mounting (on the right)
(in compliance with DIN EN 50 012 and
DIN EN 50 005)
1NO + 1NC
–
3RH2911-2DE11
–
Soldering pin adapter for contactors
with 4-pole auxiliary contact block
For 4 contactors
(pack)
3RT1916-4KA2
–
–
10
Soldering pin adapter for contactors
For 4 contactors
(pack)
3RT1916-4KA1
–
–
11
Surge suppressor, e.g. varistor (230V AC)
without LED
AC 127–240 V
3RT2916-1BD00
3RT2916-1BD00
3RT2916-1BD00
with LED
AC 127–240 V
3RT2916-1JL00
3RT2916-1JL00
3RT2916-1JL00
AC-3/400 V: 20 A
3RT1916-4RD01
–
–
3RT1900-4RE01
–
–
3RA2913-3K
–
–
9
12
13
1) More auxiliary contact blocks on request
Terminal module for contactor with
screw connection
3-phase supply terminal
Adapter
Plug
Conductor crosssection: 6 mm
24
Accessories for 3RT202 contactors (S0)
5
Version
Order no.
Order no.
Screw connection Spring-loaded
connection
Standard
see tabular overview on page 5ff.
Communication
see page 16
1-pole auxiliary contact block,
cable entry from the top
1NO
3RH2911-1AA10
–
–
3RH2911-1AA01
–
–
2-pole auxiliary contact block,
cable entry from the top
1NO + 1NC
3RH2911-1LA11
–
–
2NO
3RH2911-1LA20
–
–
1-pole auxiliary contact block,
cable entry from the bottom
1NO
3RH2911-1BA10
–
–
1NC
3RH2911-1BA01
–
–
3
2-pole auxiliary contact block,
cable entry from the bottom
1NO + 1NC
3RH2911-1MA11
2NO
3RH2911-1MA20
4
4-pole auxiliary contact block1),
(in compliance with DIN EN 50
012 and DIN EN 50 005)
1NC
3RH2911-1HA01
3RH2911-2HA01
3RH2911-4HA01
2NC
3RH2911-1HA02
3RH2911-2HA02
3RH2911-4HA02
1NO + 1NC
3RH2911-1HA11
3RH2911-2HA11
3RH2911-4HA11
2NO + 2NC
3RH2911-1HA22
3RH2911-2HA22
3RH2911-4HA22
1NO
3RH2911-1HA10
3RH2911-2HA10
3RH2911-4HA10
2NO
3RH2911-1HA20
3RH2911-2HA20
3RH2911-4HA20
1NO + 1NC
2NO
2NC
3RH2911-1NF11
3RH2911-1NF20
3RH2911-1NF02
3RH2911-2NF11
3RH2911-2NF20
3RH2911-2NF02
–
–
–
Front mounting auxiliary
contacts for
13
5
1
5
9
2
1
12
1
2
4
5
10
Comment
3RT2 contactors
3
6
13
11
7
Auxiliary contact blocks suitable
for electronic components (2-pole)
(in compliance with DIN EN 50 005)
8
5
6
7
8
9
10
11
12
see page 17 (Function modules for mounting on contactors and for interfacing the controller)
Size-specific accessories for 3RT2 contactors
Auxiliary contact blocks
acc. to DIN EN 2NO
for side mounting (on the right)
50 005
1NO + 1NC
(in compliance 2NC
with DIN EN 50
012 and DIN EN
50 005)
Auxiliary contact block for side
acc. to DIN EN 1NO + 1NC
mounting (on the right), suitable 50 005
for electronic components
Overvoltage limiter, e.g. varistor
(230V AC)
without LED
AC 127–240 V
with LED
AC 127–240 V
Terminal module for contactor
Adapter
AC-3/400 V:
with screw connection
25 A
Plug
Pneumatic delay block
(in compliance with DIN EN 50
005) 1NO + 1NC
13
Max. 10 HP (S00)
0.1 – 30 s
1 – 60 s
0.1 – 30 s
1 – 60 s
Coil terminal module
Connection from the top
Connection from the bottom
Diagonal connection
1) More auxiliary contact blocks on request
Max. 30 HP (S0)
Order no.
Ring lug terminal
connection
Motor Starters
Communications
On-delay
Off-delay
3RH2921-1DA20
3RH2921-1DA11
3RH2921-1DA02
3RH2921-2DA20
3RH2921-2DA11
3RH2921-2DA02
–
3RH2921-4DA11
–
–
3RH2921-2DE11
–
3RT2926-1BD00
3RT2926-1JL00
3RT1926-4RD01
3RT1900-4RE01
3RT2926-2PA01
3RT2926-2PA11
3RT2926-2PR01
3RT2926-2PR11
3RT2926-1BD00
3RT2926-1JL00
–
3RT2926-1BD00
3RT2926-1JL00
–
–
–
–
–
–
–
–
–
3RT2926-4RA11
3RT2926-4RB11
3RT2926-4RC11
3RT2926-4RA12
3RT2926-4RB12
–
–
–
–
Infeed systems
Accessories
25
26
26
27
27
Siemens Industry, Inc.
Industry Automation Division
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800 -241- 4453
[email protected]
www.usa.siemens.com/sirius-innovations
Subject to change without prior notice.
Order No: PWSA-A1070-0411
All rights reserved.
Printed in USA
©2011 Siemens Industry, Inc.
The information in this brochure only includes general
descriptions and/or performance characteristics, which
do not always apply in the form described in a specific
application, or which may change as products are
developed. The required performance characteristics are
only binding if they are expressly agreed at the point of
conclusion of the contract.
All product names may be trademarks or product names
of Siemens AG or supplier companies; use by third parties
for their own purposes could constitute a violation of the
owner‘s rights.