UL Report for MSP 3RV1021 Type E Combo.pdf

File E156943
Project 97ME21192
January 13, 1998
REPORT
on
INDUSTRIAL CONTROL EQUIPMENT - COMBINATION MOTOR CONTROLLERS
Siemens Energy and Automation Inc.
Canton, Georgia USA
Copyright © 1998 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File El56943
Vol. 1
Sec. 11
and Report
Page l
Issued: 1998-01-13
Revised: 2004-02-27
DESCRIPTION
PRODUCT COVERED:
USL, CNL - Open Type Self-Protected Combination Motor Controller, Cat.
No. 3RV1021 followed by combination of 0, 1 or 4 and a letter
A,B,C,D,E,F,G,H,J or K followed by Al or A3, followed by 0,1,2,3,4,5 or 8, may
be followed by additional numbers and letters.
3RV1928-1H, 3RV1925-5EB Line Terminal Adaptor.
GENERAL:
These devices are open type manual combination motor controllers. They
are intended to provide motor disconnection means, motor branch-circuit
short-circuit and ground fault protection, motor control, and motor overload
protection. These devices are suitable for use as Service Equipment.
These devices may also be used with Siemens Listed type 3RT contactors and 3RW
solid state controllers. When used, the contactors and solid state
controllers have the same horsepower rating as the 3RV1021 devices with which
they may be used.
These devices are provided with line terminal adapters, cat. no.
3RV1928-1H or cat. No. 3RV1925-5EB fastened onto existing line side terminal
blocks of combination motor controller. The adapters may be factory or fieldinstalled. (See “Marking” section.) These devices may be used with insulated
busbar systems, Cat. No. 3RV1915, with the 3RV1925-5EB adapter. In these
application, the incoming line terminal to the busbar systems has spacings not
less than 2 in. (50.8 mm) measured over surface, and 1 inch (25.4 mm) through
air.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE'S USE)
CNL - Indicates investigated to Canadian National Standards(s) C22.2 No.
14-M91
Note: CNL = Canadian National Standards - Listed
USL - United States Standards - Listed
RATINGS:
Voltage
50/60 Hz
Maximum HP ratings
1-phase
3-phase
2-poles
3-poles
115-120
2@
---200-208
3@
7-1/2@
230-240
5@
7-1/2@
460-480
---15@
575-600
---20@
These devices are suitable for Design E motors.
@ - Suitable for controlling motors with a maximum motor nameplate full
load current of 12.5 A at 600 V ac, and 22 A at 480 V ac.
Torque of line terminal adapter = 2.5-3 Nm.
These devices are suitable for use on circuits capable of delivering the
following maximum short circuit currents.
File E156943
Vol. 1
Sec. 11
and Report
RMS. Symmetrical Amperes
30 kA
65 kA
65 kA
Page 2
Issued: 1-13-98
Revised: 2004-02-27
Voltage
600 Y/347 V ac
480 Y/277 V ac
240 V ac
The trip rating is 125% of the dial setting (thermal range).
NOMENCLATURE:
3RV1021
I
-
1A
II
A
III
1
IV
I.
Basic type, Size 50
3RV1021 - 3 main contacts
II.
Setting Ranges
8
V
-
1B
VI
P0
VII
Suffix
from
to (A)
0A
0B
0C
0D
0E
OF
OG
OH
OJ
OK
1A
1B
1C
1D
1E
1F
1G
1H
1J
1K
4A
4B
4C
0.11
0.14
0.18
0.22
0.28
0.35
0.45
0.55
0.7
0.9
1.1
1.4
1.8
2.2
2.8
3.5
4.5
5.5
7
9
11
14
17
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.8
1
1.25
1.6
2
2.5
3.2
4
5
6.3
8
10
12.5
16
20
22
III.
Tripping Class
A
setting range with instantaneous tripping 12 x 1n, Class 10 overload
relay.