© Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure ■ Overview The SITRANS P300 is a digital pressure transmitter for relative and absolute pressure. The conventional thread versions are available as process connections, as are flush-mounted versions. A large number of the flush-mounted versions are suitable for food and pharmaceutical applications, and satisfy the EHEDG and 3A hygiene requirements. The output signal is a load-independent direct current from 4 to 20 mA or a PROFIBUS PA or FOUNDATION signal, which is linearly proportional to the input pressure. Communication is via HART protocol or PROFIBUS PA interface. Convenient buttons for easy local operation of the basic settings of the pressure transmitter. The SITRANS P300 has a single-chamber stainless steel casing. The pressure transmitter is approved with "intrinsically safe" type of protection. It can be used in zone 1 or zone 0. ■ Benefits With appropriate parameter settings, it can also be used for the following additional measurement types: • Level • Volume • Mass The "intrinsically-safe" Ex version of the transmitter can be installed in hazardous areas (zone 1). The transmitters are provided with an EC type examination certificate and comply with the respective harmonized European standards of ATEX. Gauge pressure This variant measures aggressive, non-aggressive and hazardous gases, vapors and liquids. • High quality and service life • High reliability even under extreme chemical and mechanical loads • Extensive diagnosis and simulation functions • Minimum conformity error • Small long-term drift • Wetted parts made of high-grade materials (such as stainless steel, Hastelloy) • Measuring range 0.008 bar to 400 bar (0.1 psi to 5802 psi) • High measuring accuracy • Parameterization over control keys and HART or PROFIBUS PA or FOUNDATION Fieldbus ■ Application The pressure transmitter is available in versions for gauge pressure and for absolute pressure. The output signal is always a load-independent direct current from 4 to 20 mA or a PROFIBUS PA or FOUNDATION Fieldbussignal, which is linearly proportional to the input pressure. The pressure transmitter measures aggressive, non-aggressive and hazardous gases, as well as vapors and liquids. 1/50 It can be used for the following measurement types: • Gauge pressure • Absolute pressure Siemens FI 01 · 2015 US Edition The smallest span is 0.01 bar (0.15 psi), the largest is 400 bar (5802 psi). Level With appropriate parameter settings, the gauge pressure variant measures the level of aggressive, non-aggressive and hazardous liquids. For measuring the level in an open container you require one device; for measuring the level in a closed container, you require two devices and a process control system. Absolute pressure This variant measures the absolute pressure of aggressive, nonaggressive and hazardous gases, vapors and liquids. The smallest span is 0.008 bar a (0.12 psia), the largest is 30 bar a (435 psia). © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure ■ Design ■ Function The device comprises: • Electronics • Housing • Measuring cell Operation of electronics with HART communication 9 8 0.0.0.0.0 00 M 10 1 2 3 4 5 IA, UH μC 5 7 HART interface 4 EEPROM 6 Electronics 6 Sensor 3 1 2 3 4 5 2 Digital display Process connection Cable gland Rating plate Screw-on lid The housing has a screw-on lid (5) and, depending on the version, is with or without an inspection window. The electrical terminal housing, the buttons for operation of the device are located under this lid and, depending on the version, the display. The connections for the auxiliary power UH and the shield are in the terminal housing. The cable gland is mounted on the side of the housing. The measuring cell with the process connection (2) is located on the bottom of the housing. The measuring cell with the process connection may differ from the one shown in the diagram, depending on the device version. Example of attached measuring points sign Y99 = max. 10 char. Y16 = max. 27 char. pe Measuring cell 1 2 3 4 5 6 Perspective view of SITRANS P300 Y01 or Y02 = max. 27 char. Y15 = max. 16 char. EEPROM 1 .... to .... mbar Measuring point number (TAG No.) 1234 Measuring point text Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Digital-to-analog converter One non-volatile memory each in the measuring cell and electronics 7 HART interface 8 Three input keys (local operation) 9 Digital display 10 Diode circuit and connection for external ammeter IA Output current UH Power supply Pe Input variable Function diagram of electronics The input pressure is converted into an electrical signal by the sensor (1). This signal is amplified by the measuring amplifier (2) and digitalized in an analog-to-digital converter (3). The digital signal is analyzed in a microcontroller (4) and corrected according to linearity and thermal characteristics. In a digital-to-analog converter (5) it is then converted into the output current of 4 to 20 mA. A diode circuit provides reverse polarity protection. You can make an uninterrupted current measurement with a low-ohm ammeter at the connection (10). The data specific to the measuring cell, the electronic data and parameter settings are stored in two non-volatile memories (6). The first memory is linked to the measuring cell, the second to the electronics. The buttons (8) can be used to call up individual functions, socalled modes. If you have a device with a display (9), you can use this to track mode settings and other messages. The basic mode settings can be changed with a computer via the HART modem (7). Siemens FI 01 · 2015 US Edition 1/51 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Operation of electronics with PROFIBUS PA communication Operation of electronics with FOUNDATION Fieldbus communication 9 9 5 μC EEPROM 2 7 6 pe 1 2 3 4 5 6 7 Power supply unit Coupler 7 FF interface 12 EEPROM 6 Power supply 10 Power supply unit Coupler Electronics BusMaster 1 6 Sensor pe Measuring cell Measuring cell Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Electrical isolation One non-volatile memory each in the measuring cell and electronics PROFIBUS-PA interface 5 Power supply 10 11 6 Sensor 4 μC Electronics 1 3 PA interface Foundation Fieldbus 4 PROFIBUS DP 3 0.0.0.0.0 00 M PROFIBUS-PA M 2 8 0.0.0.0.0 00 EEPROM 8 EEPROM 1 8 9 10 11 12 Three input keys (local operation) Digital display Power supply DP/PA coupler or link Bus master pe Input variable 1 2 3 4 5 6 7 Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Electrical isolation One non-volatile memory each in the measuring cell and electronics FF interface 8 9 10 Three input keys (local operation) Digital display Power supply pe Input variable Function diagram of electronics Function diagram of electronics The input pressure is converted into an electrical signal by the sensor (1). This signal is amplified by the measuring amplifier (2) and digitalized in an analog-to-digital converter (3). The digital signal is analyzed in a microcontroller (4) and corrected according to linearity and thermal characteristics. It is then made available at the PROFIBUS PA over an electrically isolated PROFIBUS PA interface (7). The data specific to the measuring cell, the electronic data and parameter settings are stored in two non-volatile memories (6). The first memory is linked to the measuring cell, the second to the electronics. The bridge output voltage created by the sensor (1, Figure "Function diagram of electronics") amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the FOUNDATION Fieldbus through an electrically isolated FOUNDATION Fieldbus interface (7). The buttons (8) can be used to call up individual functions, socalled modes. If you have a device with a display (9), you can use this to track mode settings and other messages. The basic mode settings (12) can be changed with a computer over the bus master. The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error messages and the operating modes on the display (9). The results with status values and diagnostic values are transferred by cyclic data transmission on the FOUNDATION Fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as National Instruments Configurator is required for this. Mode of operation of the measuring cells The process connections available include the following: • G½ • ½-14 NPT • Flush-mounted diaphragm: - Flanges to EN - Flanges to ASME - NuG and pharmaceutical connections 1/52 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Measuring cell for gauge pressure Measuring cell for gauge pressure, front-flush diaphragm 1 1 6 5 5 2 2 4 4 3 pe 1 2 3 4 5 6 pe Reference pressure Measuring cell Process connection Seal diaphragm Filling liquid Relative pressure sensor Pressure as input variable 1 2 3 4 5 pe Reference pressure Measuring cell Seal diaphragm Filling liquid Relative pressure sensor Pressure as input variable Measuring cell for gauge pressure, function diagram 3 pe The input pressure (pe) is transferred to the gauge pressure sensor (6) via the seal diaphragm (4) and the filling liquid (5), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure. Transmitters with spans 63 bar ( 926.1 psi) measure the input pressure compared to atmospheric, transmitters with spans of 160 bar ( 2352 psi) compared to a vacuum. Measuring cell for absolute pressure Measuring cell for gauge pressure, front-flush diaphragm, function diagram The input pressure (pe) is transferred to the gauge pressure sensor (6) via the seal diaphragm (4) and the filling liquid (5), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure. Transmitters with spans 63 bar ( 926.1 psi) measure the input pressure compared to atmospheric, transmitters with spans of 160 bar ( 2352 psi) compared to a vacuum. Measuring cell for absolute pressure, front-flush diaphragm 1 5 4 3 4 1 2 pe 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Absolute pressure sensor Pressure as input variable Measuring cell for absolute pressure, function diagram The input pressure (pe) is transferred to the absolute pressure sensor (5) via the seal diaphragm (3) and the filling liquid (4), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure. 3 1 2 3 4 pe Measuring cell Seal diaphragm Filling liquid Absolute pressure sensor Pressure as input variable 2 pe Measuring cell for absolute pressure, front-flush diaphragm, function diagram Siemens FI 01 · 2015 US Edition 1/53 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure The input pressure (pe) is transferred to the absolute pressure sensor (5) via the seal diaphragm (3) and the filling liquid (4), displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure. Adjustable parameters on SITRANS P300 with HART communication Parameters Input keys HART communication Start of scale x x Full-scale value x x Parameterization Electrical damping x x Depending on the version, there are a range of options for parameterizing the pressure transmitter and for setting or scanning the parameters. Start-of-scale value without applica- x tion of a pressure ("Blind setting") x Full-scale value without application of a pressure ("Blind setting") x x Zero adjustment x x current transmitter x x Fault current x x Parameterization using the input buttons (local operation) With the input buttons you can easily set the most important parameters without any additional equipment. Parameterization using HART communication Parameterization using HART communication is performed with a HART communicator or a PC. + 230 ... 1100 Ω SITRANS P transmitter Power supply HART communicator Communication between a HART communicator and a pressure transmitter When parameterizing with the HART communicator, the connection is made directly to the 2-wire cable. + 230 ... 500 Ω SITRANS P transmitter HART modem Power supply PC or laptop USB/RS 232 HART communication between a PC communicator and a pressure transmitter When parameterizing with a PC, the connection is made through a HART modem. The signals needed for communication in conformity with the HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method. 1/54 Siemens FI 01 · 2015 US Edition Disabling of buttons, write protection x x1) Type of dimension and actual dimension x x Input of characteristic x Freely-programmable LCD x Diagnostic functions x 1) Cancel apart from write protection Diagnostic functions for SITRANS P300 with HART communication • Zero correction display • Event counter • Limit transmitter • Saturation alarm • Slave pointer • Simulation functions • Maintenance timer Available physical units of display for SITRANS P300 with HART communication Table style: Technical specifications 2 Physical variable Physical dimensions Pressure (setting can also be made in the factory) Pa, MPa, kPa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, inH2O, inH2O (4 °C), mmH2O, ftH2O (20 °C), inHg, mmHg Level (height data) m, cm, mm, ft, in Volume m3, dm3, hl, yd3, ft3, in3, US gallon, lmp. gallon, bushel, barrel, barrel liquid Mass g, kg, t, lb, Ston, Lton, oz Temperature K, °C, °F, °R Miscellaneous %, mA © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Parameterization through PROFIBUS PA interface Physical dimensions available for the display Fully digital communication through PROFIBUS PA, profile 3.0, is particularly user-friendly. The PROFIBUS connects the SITRANS P300 PA to a process control system, e.g. SIMATIC PSC 7. Communication is possible even in a potentially explosive environment. Physical variable Physical dimensions Pressure (setting can also be made in the factory) Mpa, kPa, Pa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, mmH2O, mmH2O (4 °C), inH2O, inH20 (4 °C), ftH2O (20 °C), mmHg, inHg For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager). Level (height data) m, cm, mm, ft, in, yd Mass g, kg, t, lb, Ston, Lton, oz Parameterization through FOUNDATION Fieldbus interface Volume m3, dm3, hl, yd3, ft3, in3, US gallon, lmp. gallon, bushel, barrel, barrel liquid volume flow m3/s, m3/min, m3/h, m3/d, l/s, l/min, l/h, l/ d, Ml/d, ft3/s, ft3/min, ft3/h, ft3/d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d Mass flow g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h, kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h, lb/d, STon/s, STon/min, STon/h, STon/d, LTon/s, LTon/min, LTon/h, LTon/d Total mass flow t, kg, g, lb, oz, LTon, STon Temperature K, °C, °F, °R Miscellaneous % Fully digital communication through FOUNDATION Fieldbus is particularly user-friendly. Through the FOUNDATION Fieldbus the P300 is connected to a process control system. Communication is possible even in a potentially explosive environment. For parameterization through the FOUNDATION Fieldbus you need suitable software, e.g. National Instruments Configurator. Adjustable parameters for SITRANS P300 with PROFIBUS PA and FOUNDATION Fieldbus Adjustable parameters Input keys PROFIBUS PA and FOUNDATION Fieldbus interface Electrical damping x x Zero adjustment (correction of position) x x Buttons and/or function disabling x x Source of measured-value display x x Physical dimension of display x x Position of decimal point x x Bus address x x Adjustment of characteristic x x Input of characteristic x Freely-programmable LCD x Diagnostic functions x Hygiene version In the case of the SITRANS P300 with 7MF812.-... front-flush diaphragm, selected connections comply with the requirements of the EHEDG or 3A. You will find further details in the order form. Please note in particular that the seal materials used must comply with the requirements of 3A. Similarly, the filling liquids used must be FDA-compliant. Diagnostic functions for SITRANS P300 with PROFIBUS PA and FOUNDATION Fieldbus • Event counter • Slave pointer • Maintenance timer • Simulation functions • Display of zero correction • Limit transmitter • Saturation alarm Siemens FI 01 · 2015 US Edition 1/55 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure ■ Technical specifications SITRANS P300 for gauge and absolute pressure HART PROFIBUS PA and FOUNDATION Fieldbus Gauge pressure input Measured variable Gauge pressure Spans (infinitely adjustable) or nominal mea- Span (min. ... max.) suring range and max. permissible test pressure Max. perm. test pressure Nominal measuring range Max. perm. test pressure 0.01 ... 1 bar (0.15 ... 14.5 psi) 6 bar (87 psi) 1 bar (14.5 psi) 6 bar (87 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 10 bar (145 psi) 4 bar (58 psi) 10 bar (145 psi) 0.16 ... 16 bar (2.3 ... 232 psi) 32 bar (464 psi) 16 bar (232 psi) 32 bar (464 psi) 0.6 ... 63 bar (9.1 ... 914 psi) 100 bar (1450 psi) 63 bar (914 psi) 100 bar (1450 psi) 1.6 ... 160 bar (23.2 ... 2321 psi) 250 bar (3626 psi) 160 bar (2321 psi) 250 bar (3626 psi) 4.0 ... 400 bar (58 ... 5802 psi) 600 bar (8700 psi) 400 bar (5802 psi) 600 bar (8700 psi) Depending on the process connection, the span may differ from these values Depending on the process connection, the nominal measuring range may differ from these values Lower measuring limit • Measuring cell with silicone oil 30 mbar a (0.44 psia) Upper measuring limit • Measuring cell with silicone oil 100% of max. span 100 % of the max. nominal measuring range Absolute pressure input Measured variable Absolute pressure Spans (infinitely adjustable) or nominal mea- Span (min. ... max.) suring range and max. permissible test pressure Max. perm. test pressure Nominal measuring range Max. perm. test pressure 8 ... 250 mbar a (0.12...3.63 psia) 6 bar a (87 psia) 250 mbar a (3.63 psia) 6 bar a (87 psia) 43 ... 1300 mbar a (0.62...18.9 psia) 10 bar a (145 psia) 1.30 bar a (19 psia) 10 bar a (145 psia) 0.16 ... 5 bar a (2.3 ... 73 psia) 30 bar a (435 psia) 5 bar a (73 psia) 30 bar a (435 psia) 1 ... 30 bar a (14.5 ... 435 psia) 100 bar a (1450 psia) 30 bar a (435 psia) 100 bar a (1450 psia) Lower measuring limit • Measuring cell with silicone oil 0 mbar a (0 psia) Upper measuring limit • Measuring cell with silicone oil 100 % of max. span 100 % of the max. nominal measuring range Input of gauge pressure, with front-flush diaphragm Measured variable Gauge pressure, front-flush Spans (infinitely adjustable) or nominal mea- Span (min. ... max.) suring range and max. permissible test pressure Max. perm. test pressure Nominal measuring range Max. perm. test pressure 0.01 ... 1 bar (0.15 ... 14.5 psi) 6 bar (87 psi) 1 bar (14.5 psi) 6 bar (87 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 10 bar (145 psi) 4 bar (58 psi) 10 bar (145 psi) 0.16 ... 16 bar (2.32 ... 232 psi) 32 bar (464 psi) 16 bar (232 psi) 32 bar (464 psi) 0.6 ... 63 bar (9.14 ... 914 psi) 100 bar (1450 psi) 63 bar (914 psi) 100 bar (1450 psi) Lower measuring limit 100 mbar a (1.45 psia) Upper measuring limit • Measuring cell with silicone oil 1/56 Siemens FI 01 · 2015 US Edition 100% of max. span 100 % of the max. nominal measuring range © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure SITRANS P300 for gauge and absolute pressure HART PROFIBUS PA and FOUNDATION Fieldbus Input of absolute pressure, with front-flush diaphragm Measured variable Absolute pressure, front-flush Spans (infinitely adjustable) or nominal mea- Span (min. ... max.) suring range and max. permissible test pressure Max. perm. test pressure Nominal measuring range Max. perm. test pressure 43 ... 1300 mbar a (0.62 ... 18.85 psia) 10 bar a (145 psia) 1300 mbar a (18.85 psia) 10 bar a (145 psia) 0.16 ... 5 bar a (2.32 ... 72.5 psi a) 30 bar a (435 psia) 5 bar a (72.5 psia) 30 bar a (435 psia) 1 ... 30 bar a (14.5 ... 435 psia) 100 bar a (1450 psia) 30 bar a (435 psia) 100 bar a (1450 psia) Depending on the process connection, the span may differ from these values Lower measuring limit Depending on the process connection, the nominal measuring range may differ from these values 0 bar a (0 psia) Upper measuring limit • Measuring cell with silicone oil 100% of max. span 100 % of the max. nominal measuring range Output signal 4 ... 20 mA Digital PROFIBUS PA signal Physical bus - Output IEC 61158-2 Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping T63 (step width 0.1 s) Set to 2 s (0 ... 100 s) According to IEC 60770-1 Measuring accuracy Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, measuring cell with silicone oil, room temperature 25 °C (77 °F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range) Error in measurement at limit setting incl. hysteresis and reproducibility Gauge pressure Absolute pressure Absolute pressure, front-flush Gauge pressure Absolute pressure Absolute pressure, front-flush Linear characteristic • r + 10 (0.0029 r + 0.071) % 0.1 % 0.2 % (0.0029 r + 0.071) % 0.1 % 0.2 % • 10 < r 30 (0.0045 r + 0.071) % 0.2 % 0.4 % (0.0045 r + 0.071) % 0.2 % 0.4 % • 30 < r 100 (0.005 r + 0.05) % - (0.005 r + 0.05) % - - Step response time T63 Long-term stability at 30 °C (54 °F) - approx. 0.2 s (0.25 r) %/5 years (0.1 r) %/year (0.25 r)/5 years (0.1 r) %/year Influence of ambient temperature • at -10 ... +60 °C (14 ... 140 °F) (0.08 r + 0.1) %1) (0.2 r + 0 3) % (0.08 r + 0.1) %1) • at -40 ... -10 °C and +60 ... +85 °C (-40 ... 14 °F and 140 ... 185 °F) (0.1 r + 0.15) %/10 K (0.2 r + (0.1 r + 0.15) %/10 K 0.3) %/10 K (0.2 r + 0 3) % (0.2 r + 0.3) %/10 K Influence of the medium temperature (only with front-flush diaphragm) • Temperature difference between medium temperature and ambient temperature 3 mbar/10 K (0.04 psi/10 K) Siemens FI 01 · 2015 US Edition 1/57 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure SITRANS P300 for gauge and absolute pressure HART PROFIBUS PA and FOUNDATION Fieldbus Rated conditions Installation conditions Ambient temperature • Measuring cell with silicone oil • Measuring cell with Neobee oil (FDA-compliant, with flush-mounted diaphragm) • Measuring cell with inert liquid (not with frontflush diaphragm) • Display readable • Storage temperature Observe the temperature class in areas subject to explosion hazard. -40 ... +85 °C (-40 ... +185 °F) -10 ... +85 °C (14 ... +185 °F) -20 ... +85 °C (-4 ... +185 °F) -30 ... +85 °C (-22 ... +185 °F) -50 ... +85 °C (-58 ... +185 °F) (for Neobee: -20 ... +85 °C (-4 ... +185 °F)) (for temperature oil: -10 ... + 85 °C (14 ... +165 °F)) Climatic class Condensation Degree of protection acc. to EN 60529 Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150 °C (302 °F) Electromagnetic Compatibility • Emitted interference and interference immunity Acc. to IEC 61326 and NAMUR NE 21 Medium conditions Temperature of medium • Measuring cell with silicone oil -40 ... +100 °C (-40 ... +212 °F) • Measuring cell with silicone oil (FDA-compliant, with flush-mounted diaphragm) • Measuring cell with Neobee oil "Measuring cell with Neobee oil (FDA-compliant, with flushmounted diaphragm) • Measuring cell with silicone oil, with temperature decoupler (only for gauge pressure version with flush-mounted diaphragm) -40 ... +150 °C (-40 ... +302 °F) • Measuring cell with Neobee oil, with temperature decoupler (only for gauge pressure version with flush-mounted diaphragm) • Measuring cell with inert liquid -10 ... +200 °C (14 ... +392 °F) • Measuring cell with high-temperature oil (only for gauge pressure version with flush-mounted diaphragm) -10 ... +250 °C (14 ... 482 °F) -10 ... +150 °C (-14 ... +302 °F) -40 ... +200 °C (-40 ... +392 °F) -20 ... +100 °C (-4 ... +212 °F) Design (standard version) Weight (without options) Enclosure material Material of parts in contact with the medium • Connection shank • Oval flange • Seal diaphragm • Measuring cell filling Process connection 1/58 Siemens FI 01 · 2015 US Edition Approx. 800 g (1.8 lb) Stainless steel, mat. no. 1.4301/304 Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 Stainless steel, mat. no. 1.4404/316L Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 •Silicone oil •Inert filling liquid •G½B to EN 837-1 •Female thread ½-14 NPT •Oval flange PN 160 (MAWP 2320 psi) with fastening thread: -7/16 -20 UNF to IEC 61518 •M10 as per DIN 19213 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure SITRANS P300 for gauge and absolute pressure HART PROFIBUS PA and FOUNDATION Fieldbus Design (version with front-flush diaphragm) Weight (without options) approx. 1 ... 13 kg (2.2 ... 29 lb) Enclosure material Stainless steel, mat. no. 1.4301/304 Material of parts in contact with the medium • Process connection Stainless steel, mat. no. 1.4404/316L • Seal diaphragm Stainless steel, mat. no. 1.4404/316L •Silicone oil •Inert filling liquid •FDA compliant fill fluid (Neobee oil) • Measuring cell filling Process connection •Flanges as per EN and ASME •F&B and pharmaceutical flanges Ra-values 0.8 µm (32 µ-inch)/welds Ra) 1.6 µm (64 µ-inch) (Process connections acc. to 3A; Ra-values 0.8 µm (32 µ-inch)/welds Ra 0.8 µm (32 µ-inch) Surface quality touched-by-media Power supply UH Terminal voltage on transmitter 10.5 ... 42 V DC for intrinsically safe operation: 10.5 ... 30 V DC Supplied through bus Separate power supply - Not necessary • Without Ex - 9 ... 32 V • With intrinsically-safe operation - 9 ... 24 V Bus voltage Current consumption • Max. basic current - 12.5 mA • Start-up current basic current - Yes • Max. fault current in the event of a fault - 15.5 mA Fault disconnection electronics (FDE) - Available Certificates and approvals Classification according to PED 97/23/EC For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3, paragraph 3 (sound engineering practice) In preparation Water, waste water Explosion protection Intrinsic safety "i" PTB 05 ATEX 2048 Ex II 1/2 G Ex ia/ib IIB/IIC T4, T5, T6 • Marking • Permissible ambient temperature - Temperature class T4 -40 ... +85 °C (-40 ... +185 °F) - Temperature class T5 -40 ... +70 °C (-40 ... +158 °F) - Temperature class T6 • Connection -40 ... +60 °C (-40 ... +140 °F) To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 To certified intrinsically-safe circuits with peak values: FISCO supply unit: Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W Linear barrier: Ui = 24 V, Ii = 250 mA, Pi = 1.2 W • Effective inner capacitance: Ci = 6 nF Ci = 1.1 nF • Effective internal inductance: Li = 0.4 mH Li 7 H Explosion protection to FM for USA and Canada (cFMUS) • Identification (DIP) or (IS); (NI) • Identification (DIP) or (IS) Certificate of Compliance 3025099 CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 3025099C CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC 4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III Siemens FI 01 · 2015 US Edition 1/59 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure SITRANS P300 for gauge and absolute pressure HART Dust explosion protection for zone 20/21/22 PROFIBUS PA and FOUNDATION Fieldbus PTB 05 ATEX 2048 Ex II 1D Ex ia D 20 T 120 °C Ex II 2D Ex ib D 21 T 120 °C Ex II 3D Ex ib D 21 T 120 °C • Marking • Permissible ambient temperature - Temperature class T4 -40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only -20 ... +85 °C (-4 ... +185 °F)) - Temperature class T5 -40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only-20 ... +70 °C (-4 ... +158 °F)) - Temperature class T6 -40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only -20 ... +60 °C (-4 ... +140 °F)) • Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW To certified intrinsically-safe circuits with peak values: Ui = 24 V, Ii = 380 mA, Pi = 5.32 mW • Effective inner capacitance: Ci = 6 nF Ci = 5 nF • Effective internal inductance: Li = 0.4 H Li = 10 H PTB 05 ATEX 2048 Type of protection Ex nA/nL/ic (Zone 2) • Marking II 2/3 G Ex nA T4/T5/T6 II 2/3 G Ex nL IIB/IIC T4/T5/T6 • Permissible ambient temperature - Temperature class T4 -40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only -20 ... +85 °C (-4 ... +185 °F)) - Temperature class T5 -40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only -20 ... +70 °C (-4 ... +158 °F)) - Temperature class T6 -40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only -20 ... +60 °C (-4 ... +140 °F)) • Ex nA/nL connection To certified intrinsically-safe circuits with peak values: Um = 45 V To certified intrinsically-safe circuits with peak values: Um = 32 V • Ex ic connection To certified intrinsically-safe circuits with peak values: Ui = 45 V To certified intrinsically-safe circuits with peak values: Ui = 32 V • Effective inner capacitance: Ci = 6 nF Ci = 5 nF • Effective internal inductance: Li = 0.4 mH Li = 20 H 1) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 r + 0.08) %/28 °C (50 °F). 1/60 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure HART Communication HART communication 230 ... 1100 Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with master class 2 (max.) 4 The address can be set using Configuration tool or local operation (standard setting Address 126) FOUNDATION Fieldbus communication Function blocks 3 function blocks analog input, 1 function block PID • Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 ... 100 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic for flow measurement Yes Cyclic data usage • Output byte • Input byte 5 (one measured value) or 10 (two measured values) 0.1 or 2 (totalizer mode and reset function for dosing) • Internal preprocessing Device profile PROFIBUS PA Profile for Process Control Devices Version 3.0, class B Function blocks 2 • PID Standard FOUNDATION Fieldbus function block • Physical block 1 resource block Transducer blocks 1 transducer block Pressure with calibration, 1 transducer block LCD • Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping adjustable 0 … 100 s - Simulation function Input /Output - Failure function parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively • Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively • Physical block 1 Transducer blocks 2 • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Specification of a container characteristic with Max. 30 nodes - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function Siemens FI 01 · 2015 US Edition 1/61 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure Selection and Ordering data Article No. Selection and Ordering data SITRANS P300 pressure transmitters for relative and absolute pressure, single-chamber measuring housing, rating plate inscription in English Article No. SITRANS P300 pressure transmitters for relative and absolute pressure, single-chamber measuring housing, rating plate inscription in English 4 ... 20 mA/HART 7MF 8 0 2 3 - 4 ... 20 mA/HART 7MF 8 0 2 3 - PROFIBUS PA 7MF 8 0 2 4 - PROFIBUS PA 7MF 8 0 2 4 - FOUNDATION Fieldbus (FF) 7MF 8 0 2 5 - FOUNDATION Fieldbus (FF) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid Measuring cell cleaning normal Cleanliness level 2 to DIN 25410 77777 - 7777 Display • Without display, with keys, closed lid • With display and keys, closed lid11) 1 3 max. span (min. ... max.) 0.01 ... 1 bar (0.145 ... 14.5 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 0.16 ...16 bar (2.32 ... 232 psi) 0.63 ... 63 bar (9.14 ... 914 psi) B C D E 1.6 ... 160 bar 4 ... 400 bar 2.5 ... 250 mbar a 13 ... 1300 mbar a (23.2 ... 2320 psi) (58 ... 5802 psi) (0.04 ... 3.63 psia) (0.19 ... 18.86 psia) F G Q S 0.05 ... 5 bar a 0.3 ... 30 bar a (0.7 ... 72.5 psia) (4.35 ... 435 psia) T U • With display and keys, lid with Makrolon pane (setting on HART devices: mA, with PROFIBUS PA and FOUNDATION Fieldbus equipment: pressure units)11) • With display and keys (setting acc. to specifications, Order code "Y21" or "Y22" required), lid with Makrolon pane11) • With display and keys, lid with glass pane (setting on HART devices: mA, with PROFIBUS and FOUNDATION Fieldbus equipment: pressure units)11) • With display and keys (setting acc. to specifications, Order code "Y21" or "Y22" required), lid with glass pane11) Process connection • Connection shank G½B to EN 837-1 • Female thread ½-14 NPT • Stainless steel oval flange with process connection (Oval flange has no female thread) 6) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 - Mounting thread M12 to DIN 19213 • Male thread M20 x 1.5 • Male thread ½ -14 NPT Non-wetted parts materials • Stainless steel, deep-drawn and electrolytically polished Version • Standard versions Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" • Zone 20/21/227) • Ex nA/nL (Zone 2)8) • with FM "intrinsic safety" (cFMUS) Electrical connection / cable entry • Screwed gland M20x1.5 (polyamide)9) • Screwed gland M20x1.5 (metal) • Screwed gland M20x1.5 (stainless steel) • M12 connectors (metal), without cable socket) • M12 connectors (stainless steel), without cable • Screwed gland ½-14 NPT metal thread 10) • Screwed gland ½-14 NPT stainless steel thread 1/62 Siemens FI 01 · 2015 US Edition 1 2 4 5 6 7 Power supply units see Chap. 7 "Supplementary Components". Wetted parts materials Seal diaphragm Measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version for diaphragm seal1) 2) 3) 4) 5) 7MF 8 0 2 5 77777 - 7777 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation A B C Y 0 1 2 3 4 5 6 4 1 A B C E M A B C F G H J 1) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate 3.1 is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 3) The diaphragm seal is to be specified with a separate order number and must be included with the transmitter order number, for example 7MF802.-..Y..-.... and 7MF4900-1...-.B 4) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 5) Remote seal for direct mounting only available in combination with process connection ½-14 NPT. 6) M10 fastening thread: Max. span 160 bar (2320 psi) 7/16-20 UNF and M12 fastening thread: Max. span 400 bar (5802 psi) 7) Only available together with electrical connection option A 8) Only available together with electrical connection options B, C or G. 9) Only together with HART electronics. 10) Without cable gland. 11) Display cannot be turned. © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Selection and Ordering data Article No. Selection and Ordering data SITRANS P300 pressure transmitters for relative and absolute pressure with front-flush membrane, single-chamber measuring housing, rating plate inscription in English Article No. SITRANS P300 pressure transmitters for relative and absolute pressure with front-flush membrane, single-chamber measuring housing, rating plate inscription in English 4 ... 20 mA/HART 7MF 8 1 2 3 - 4 ... 20 mA/HART 7MF 8 1 2 3 - PROFIBUS PA 7MF 8 1 2 4 - PROFIBUS PA 7MF 8 1 2 4 - FOUNDATION Fieldbus (FF) 7MF 8 1 2 5 - FOUNDATION Fieldbus (FF) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid FDA compliant fill fluid • Neobee oil 77777 - 7777 Display • Without display, with keys, closed lid Measuring cell cleaning normal Cleanliness level 2 to DIN 254101) 1 3 normal 4 (0.15 ... 14.5 psi) (0.58 ... 58 psi) (2.32 ... 232 psi) (9.14 ... 914 psi) B C D E 13 ... 1300 mbar a2) 0.05 ... 5 bar a2) 0.03 ... 30 bar a2) (0.19 ... 18.9 psia)2) (0.7 ... 72.5 psia)2) (4.35 ... 435 psia)2) S T U Wetted parts materials Seal diaphragm Measuring cell Stainless steel Stainless steel Process connection • Flange version with Order code M.., N.., R.. or Q.. (see "Further designs") Non-wetted parts materials • Stainless steel, deep-drawn and electrolytically polished Version • Standard versions Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" • Zone 20/21/224) • Ex nA/nL (Zone 2)5) • with FM "intrinsic safety" (cFMUS) Electrical connection / cable entry • Screwed gland M20x1.5 (polyamide)6) • Screwed gland M20x1.5 (metal) • Screwed gland M20x1.5 (stainless steel) • M12 connectors (without cable socket) • M12 connectors (stainless steel), without cable socket) • Screwed gland ½-14 NPT metal thread 7) • Screwed gland ½-14 NPT stainless steel thread 7) 1 2 • With display and keys, closed lid8) max. span 0.01 ... 1 bar 0.04 ... 4 bar 0.16 ... 16 bar 0.63 ... 63 bar Stainless steel Hastelloy3) 7MF 8 1 2 5 77777 - 7777 • With display and keys, lid with Makrolon pane (setting on HART devices: mA, with PROFIBUS PA and FOUNDATION Fieldbus equipment: pressure units)8) 4 • With display and keys (setting acc. to specifications, Order code "Y21" or "Y22" required), lid with Makrolon pane8) 5 • With display and keys, lid with glass pane (setting on HART devices: mA, with PROFIBUS PA and FOUNDATION Fieldbus equipment: pressure units)8) 6 • With display and keys (setting acc. to specifications, Order code "Y21" or "Y22" required), lid with glass pane8) 7 Power supply units see Chap. 7 "Supplementary Components" Included in delivery of the device: • Brief instruction (Leporello) • CD-ROM with detailed documentation A B 7 4 1 A 1) Not suitable for oxygen applications. 2) Not with temperature decoupler P00 and P10, not for process connections R01, R02, R04, R10 and R11, and can only be ordered in conjunction with silicone oil. 3) Only available for flanges with options M.., N.. and Q.. 4) Only together with electrical connection option A. 5) Only available together with electrical connection options B, C or G. 6) Only together with HART electronics. 7) Without cable gland. 8) Display cannot be turned. B C E M A B C F G H J Siemens FI 01 · 2015 US Edition 1/63 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 for gauge and absolute pressure Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Selection and Ordering data HART PA Pressure transmitter with mounting A02 bracket (2 shackles, 4 nuts, 4 U-plates, 1 angle) made of: made completely of stainless steel, for wall or pipe mounting Cable socket for M12 plug • Stainless steel A51 Rating plate inscription (instead of English) • German • French • Spanish • Italian B10 B12 B13 B14 English rating plate Pressure units in inH20 and/or psi Order code FF Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Sanitary process connection according DIN 11851 (Dairy connection with slotted union nut) Certified to 3A6) • DN 50, PN 25 • DN 80, PN 25 N04 N06 Tri-Clamp connection according DIN 32676/ISO 2852 Certified to 3A6) • DN 50/2", PN 16 • DN 65/3", PN 10 N14 N15 N28 B21 Varivent connection Certified to 3A and EHEDG6) • Type N = 68 for Varivent housing DN 40 ... 125 und 1½" ... 6", PN 40 Temperature decoupler up to 200 °C7) for front-flush diaphragm version C11 P00 Quality inspection certificate (Five-step factory calibration) to IEC 60770-21) Inspection certificate2) Acc. to EN 10204-3.1 C12 Temperature decoupler up to 250 °C Measuring cell filling: High-temperature oil (Silicone oil) P10 Factory certificate Acc. to EN 10204-2.2 C14 Degree of protection IP65/IP68 (only for M20x1.5 and ½-14 NPT) D12 Bio-Control sanitary process connection Certified to 3A and EHEDG6) • DN 50, PN 16 • DN 65, PN 16 Q53 Q54 Degree of protection IP6k9k (only for M20x1.5) D46 Sanitary process connection to DRD • DN 50, PN 40 M32 Export approval Korea E11 Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF8...-.....-.B..) E45 Ex Approval Ex ia/ib NEPSI E55 SMS socket with union nut • 2“ • 2½“ • 3“ M67 M68 M69 SMS threaded socket • 2“ • 2½“ • 3“ M73 M74 M75 IDF socket with union nut ISO 2853 • 2“ • 2½“ • 3“ M82 M83 M84 IDF threaded socket ISO 2853 • 2“ • 2½“ • 3“ M92 M93 M94 Sanitary process connection to NEUMO Bio-Connect screw connection Certified to 3A and EHEDG6) • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 • DN 2", PN 16 • DN 2½", PN 16 • DN 3", PN 16 • DN 4", PN 16 Q05 Q06 Q07 Q08 Q13 Q14 Q15 Q16 Sanitary process connection to NEUMO Bio-Connect flange connection Certified to 3A and EHEDG6) • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 • DN 2", PN 16 • DN 2½", PN 16 • DN 3", PN 16 • DN 4", PN 16 Q23 Q24 Q25 Q26 Q31 Q32 Q33 Q34 Only for SITRANS P300 with front-flush diaphragm (7MF81..-...) Flange to EN 1092-1, Form B1 • DN 25, PN 403) • DN 25, PN 1004) • DN 40, PN 40 • DN 40, PN 100 • DN 50, PN 16 • DN 50, PN 40 • DN 80, PN 16 • DN 80, PN 40 M11 M21 M13 M23 M04 M14 M06 M16 Flanges to ASME B16.5 • 1", class 1504) • 1½", class 150 • 2", class 150 • 3", class 150 • 4", class 150 • 1", class 3004) • 1½", class 300 • 2", class 300 • 3", class 300 • 4", class 300 M40 M41 M42 M43 M44 M45 M46 M47 M48 M49 Threaded connector to DIN 3852-2, form A, thread to ISO 228 • G ¾"-A, front-flush4) R01 • G 1"-A, front-flush4) R02 R04 • G 2"-A, front-flush4) Tank connection5) Sealing is included in delivery • TG 52/50, PN 40 • TG 52/150, PN 40 1/64 Siemens FI 01 · 2015 US Edition R10 R11 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Selection and Ordering data HART PA FF Order code Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. HART PA Measuring range to be set Specify in plain text (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi Y01 8) Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Y15 Measuring point text (entry in device variable) Max. 27 characters, specify in plain text: Y16: ........................................... Y16 Entry of HART TAG Y17 Setting of the display in pressure units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Y21 Setting of the display in nonpressure units9) Specify in plain text: Y22: ..... up to ..... l, m3, m, USg, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Y22 + Y01 Preset bus address (possible between 1 ... 126) Specify in plain text: Y25: ..................... Y25 Sanitary process connection to NEUMO Bio-Connect clamp connection Certified to 3A and EHEDG6) • DN 50, PN 16 • DN 65, PN 10 • DN 80, PN10 • DN 100, PN 10 • DN 2½", PN 16 • DN 3", PN 10 • DN 4", PN 10 Q39 Q40 Q41 Q42 Q48 Q49 Q50 Sanitary process connection to NEUMO Bio-Connect S flange connection Certified to 3A and EHEDG • DN 2", PN 16 Q72 Aseptic threaded socket to DIN 11864-1 Form A Certified to 3A and EHEDG • DN 50, PN 25 • DN 65, PN 25 • DN 80, PN 25 • DN 100, PN 25 N33 N34 N35 N36 Aseptic flange with notch to DIN 11864-2 Form A Certified to 3A and EHEDG • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 N43 N44 N45 N46 Factory mounting of valve manifolds, see accessories. Only Y01, Y15, Y16, Y17, Y21, Y22 and Y25 can be factory preset Aseptic flange with groove to DIN 11864-2 Form A Certified to 3A and EHEDG • DN 50, PN 16 N43 + P11 • DN 65, PN 16 N44 + P11 N45 + • DN 80, PN 16 P11 • DN 100, PN 16 N46 + P11 Aseptic clamp with groove to DIN 11864-3 FormA Certified to 3A and EHEDG • DN 50, PN 25 • DN 65, PN 25 • DN 80, PN 16 • DN 100, PN 16 N53 N54 N55 N56 FF Max. 8 characters, specify in plain text: Y17: ........................................... = available Ordering example Item line: 7MF8023-1DB24-1AB7-Z B line: A02 + Y01 + Y21 C line: Y01: 1 ... 10 bar (14.5 ... 145 psi) C line: Y21: bar (psi) 1) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate 3.1 is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 3) Special seal in Viton included in the scope of delivery 4) Cannot be combined with Order codes P00 and P10. Can only be ordered with silicone oil measuring cell filling. 5) The weldable socket can be ordered under accessories. 6) 3A certification only if used in conjunction with 3A-compliant sealing rings. 7) Certified to 3A and EHEDG. The maximum permissible temperatures of the medium depend on the respective cell fillings (see medium conditions). 8) Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. 9) Preset values can only be changed over SIMATIC PDM. Siemens FI 01 · 2015 US Edition 1/65 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure ■ Dimensional drawings approx. 78 (3.07) approx. 28 (1.1) H2 = approx. 80 (3.15) H1 = approx. 120 (4.72) ø 91 (3.58) approx. 66 (2.6) SITRANS P300, with oval flange, dimensions in mm (inch) Ø approx. 69 (2.72) approx. 125 (4.92) 82 approx. 41 (1.61) ° 90 (3.54) approx. 118 (4.65) approx. 66 (2.6) approx. 28 (1.1) 1 approx. 105 (4.13) Ø 50...60 (1.97...2.36) 72 (2.83) approx. 131 (5.16) 90 (3.54) SITRANS P300, process connection M20 x 1.5, with mounted mounting bracket, dimensions in mm (inch) 1/66 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Ø 91 (3.58) 26,5 (1.0 4) H1 = approx. 120 (4.72) 69 (2.72) 26 (1.02) 66 (2.6) 50 (1.97) H2 = approx. 49 (1.93) Temperature decoupler ° 82 SITRANS P300, front-flush, dimensions in mm (inch) The diagram shows a SITRANS P300 with an example of a flange. In this drawing the height is subdivided into H1 and H2. H1 = Height of the SITRANS P300 up to a defined cross-section H2 = Height of the flange up to this defined cross-section Only the height H2 is indicated in the dimensions of the flanges. Siemens FI 01 · 2015 US Edition 1/67 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Flanges as per EN and ASME Sanitary process screw connection to NEUMO Bio-Connect Flange to EN Order DN code H2 Order DN code M11 M21 M13 M23 M04 M14 M06 M16 D 25 25 40 40 50 50 80 80 PN D H2 40 100 40 100 16 40 16 40 115 mm (4.5“) 140 mm (5.5“) 150 mm (5.9“) 170 mm (6.7“) 165 mm (6.5“) 165 mm (6.5“) 200 mm (7.9“) 200 mm (7.9“) Approx. 52 mm (2“) H2 EN 1092-1 D H2 Order DN code M40 M41 M42 M43 M44 M45 M46 M47 M48 M49 1“ 1½“ 2“ 3“ 4“ 1“ 1½“ 2“ 3“ 4“ H2 PN D 150 150 150 150 150 300 300 300 300 300 110 mm (4.3“) Approx. 130 mm (5.1“) 52 mm (2“) 150 mm (5.9“) 190 mm (7.5“) 230 mm (9.1“) 125 mm (4.9“) 155 mm (6.1“) 165 mm (6.5“) 210 mm (8.1“) 255 mm (10.0“) H2 D DIN 11851 (milk pipe union with slotted union nut) N04 N06 50 80 PN D H2 25 25 92 mm (3.6“) 127 mm (5.0“) Approx. 52 mm (2“) D Q23 Q24 Q25 Q26 Q31 Q32 Q33 Q34 50 65 80 100 2“ 2½“ 3“ 4“ Order DN code Connections to DIN Order DN code D H2 16 16 16 16 16 16 16 16 82 mm (3.2“) 105 mm (4.1“) 115 mm (4.5“) 145 mm (5.7“) 82 mm (3.2“) 105 mm (4.1“) 105 mm (4.1“) 145 mm (5.7“) Approx. 52 mm (2“) PN D H2 16 16 16 16 16 16 16 16 110 mm (4.3“) 140 mm (5.5“) 150 mm (5.9“) 175 mm (6.9“) 100 mm (3.9“) 110 mm (4.3“) 140 mm (5.5“) 175 mm (6.9“) Approx. 52 mm (2“) Sanitary process connection to NEUMO Bio-Connect clamp connection H2 NuG and pharmaceutical connections H2 50 65 80 100 2“ 2½“ 3“ 4“ Order DN code ASME B16.5 D Q05 Q06 Q07 Q08 Q13 Q14 Q15 Q16 PN Sanitary process connection to NEUMO Bio-Connect flange connection Flanges to ASME D Q39 Q40 Q41 Q42 Q47 Q48 Q49 Q50 50 65 80 100 2“ 2½“ 3“ 4“ PN D 16 10 10 10 16 16 10 10 77.4 mm (3.0“) Approx. 90.9 mm (3.6“) 52 mm (2“) 106 mm (4.2“) 119 mm (4.7“) 77.4 mm (3.0“) 90.9 mm (3.6“) 106 mm (4.2“) 119 mm (4.7“) H2 Sanitary process connection to NEUMO Bio-Connect S flange connection Order DN code Order DN code H2 N14 N15 50 65 PN D H2 16 10 64 mm (2.5“) 91 mm (3.6“) Approx. 52 mm (2“) H2 Tri-Clamp nach DIN 32676 Q72 2“ PN D H2 16 125 mm (4.9“) Approx. 52 mm (2“) D Threaded connection G¾", G1" and G2" acc. to DIN 3852 D D H2 Varivent connection R01 ¾“ 60 37 mm (1.5“) R02 1“ 60 48 mm (1.9“) R04 2“ 60 78 mm (3.1“) Approx. 45 mm (1.8“) Approx. 47 mm (1.9“) Approx. 52 mm (2“) H2 Order DN code PN Other connections Order DN code H2 N28 PN D H2 40 84 mm (3.3“) Approx. 52 mm (2“) D 40 ... 125 D Sanitary process connection to DRD Order DN code H2 1 M32 50 PN D H2 40 105 mm (4.1“) Approx. 52 mm (2“) D 1/68 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Tank connection TG 52/50 and TG52/150 PN D H2 Order DN code PN D H2 Approx. 63 mm (2.5“) Approx. 170 mm (6.7“) N33 N34 N35 N36 50 65 80 100 25 25 25 25 78 x 1/6“ 95 x 1/6“ 110 x ¼“ 130 x ¼“ Approx. 52 mm (2“) 25 40 63 mm (2.5“) R11 25 40 63 mm (2.5“) H2 R10 D H2 Order DN code Aseptic threaded socket to DIN 11864-1 Form A D SMS socket with union nut M67 M68 M69 PN 2“ 25 2½“ 25 3“ 25 D H2 84 mm (3.3“) 100 mm (3.9“) 114 mm (4.5“) Approx. 52 mm (2“) Aseptic flange with notch to DIN 11864-2 Form A H2 H2 Order DN code D D SMS threaded socket H2 M73 M74 M75 PN 2“ 25 2½“ 25 3“ 25 H2 70 x 1/6 mm 85 x 1/6 mm 98 x 1/6 mm Approx. 52 mm (2“) D D IDF socket with union nut H2 Order DN code M82 M83 M84 PN 2“ 25 2½“ 25 3“ 25 D H2 77 mm (3“) 91 mm (3.6“) 106 mm (4.2“) Approx. 52 mm (2“) H2 H2 M92 M93 M94 2“ 25 2½“ 25 3“ 25 D H2 50 65 80 100 16 16 16 16 94 113 133 159 Approx. 52 mm (2“) N43 N44 N45 N46 H2 Order DN code PN D H2 N43 + 50 P11 N44 + 65 P11 N45 + 80 P11 N46 + 100 P11 16 94 Approx. 52 mm (2“) 16 113 16 133 16 159 Order DN code PN D H2 50 65 80 100 25 25 16 16 77.5 91 106 130 Approx. 52 mm (2“) N53 N54 N55 N56 IDF threaded socket PN D Aseptic clamp with groove to DIN 11864-3 Form A D Order DN code PN Aseptic flange with groove to DIN 11864-2 Form A D H2 Order DN code Order DN code D 64 mm (2.5“) Approx. 77.5 mm (3.1“) 52 mm (2“) 91 mm (3.6“) D Siemens FI 01 · 2015 US Edition 1/69 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology 1 SITRANS P300 Accessories/Spare parts Selection and Ordering data Article No. Mounting bracket and fastening parts kit made of stainless steel 7MF8997-1AA Lid without window gasket not included 7MF8997-1BA Lid with glass window gasket not included 7MF8997-1BD NBR enclosure sealing 7MF8997-1BG Measuring point label unlabeled 7MF8997-1CA Cable gland • metal • plastic (blue) 7MF8997-1EA 7MF8997-1EB Weldable sockets for PMC connection • PMC Style Standard: Thread 1½" • PMC Style Minibolt: front-flush 1" 7MF4997-2HA 7MF4997-2HB Gaskets for PMC connection (packing unit = 5 units) • PTFE seal for PMC Style Standard: Thread 1½" • Gasket made of Viton for PMC Style Minibolt: front-flush 1" Weldable socket for TG 52/50 and TG 52/150 connection • TG 52/50 connection • TG5 2/150 connection Seals for TG 52/50 and TG 52/150 made of silicone Seals for flange connection with front-flush diaphragm Material FPM (Viton), 10 units • DN 25, PN 40 (M11) • DN 25, PN 100 (M21) • 1", class 150 (M40) • 1", class 300 (M45) Selection and Ordering data Article No. Operating Instructions1) Spare parts / Accessories 7MF4997-2HC 7MF4997-2HD 7MF4997-2HE 7MF4997-2HF 7MF4997-2HG 7MF4997-2HH 7MF4997-2HJ 7MF4997-2HK 7MF4997-2HL • for SITRANS P300 series with HART - German - English - French - Spanish - Italian - Leporello German/English A5E00359580 A5E00359579 A5E00359578 A5E00359576 A5E00359577 A5E00359581 • for SITRANS P300 series with PROFIBUS PA - German - English - French - Spanish - Italian - Leporello German/English A5E00414587 A5E00414588 A5E00414589 A5E00414590 A5E00414591 A5E00414592 Compact operating instructions • English, german, spanish, french, italian, dutch • English, estonian, latvian, lithuanian, polish, romanian • English, bulgarian, czech, finnish, slovakian, slovenian • English, danish, greek, portuguese, swedish, hungarian • Korean The compact operating instructions are available in 21 EU languages on the product CD supplied with each transmitter. They can also be downloaded from the SITRANS P web page. Brief instructions (Leporello) • for SITRANS P300 with HART - German/English • for SITRANS P300 with PROFIBUS PA - German/English • for SITRANS P300 with FOUNDATION Fieldbus - German/English A5E03434626 A5E03434631 A5E03434645 A5E03434656 A5E03693760 A5E00359581 A5E00414592 A5E01176733 CD with SITRANS P documentation • German, English, French, Spanish, Italian including compact operating instructions in 21 EU languages A5E00090345 Certificates (order only via SAP) instead of Internet download • hard copy (to order) A5E03252406 • on CD (to order) A5E03252407 HART modem with USB interface 7MF4997-1DB Power supply units see Chap. 7 "Supplementary Components". 1) 1/70 Siemens FI 01 · 2015 US Edition You can download these operating instructions free-of-charge from our Internet site at www.siemens.com/sitransp. © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 - Factory-mounting of valve manifolds on transmitters ■ Overview The SITRANS P300 transmitter for gauge and absolute pressure can be delivered factory-fitted with the following valve manifolds: • 7MF9011-4EA and 7MF9011-4FA valve manifolds for gauge pressure and absolute pressure transmitters ■ Design The 7MF9011-4EA valve manifolds are sealed with gaskets made of PTFE between transmitter and the valve manifold as standard. Soft iron, stainless steel and copper gaskets are also available for sealing purposes if preferred. The 7MF9011-4FA valve manifolds are sealed with PTFE sealing tape between the transmitter and the valve manifold. Once installed, the complete unit is checked under pressure for leaks (compressed air 6 bar (87 psi))and is certified leak-proof with a test report to EN 10204 - 2.2. All valve manifolds should preferably be secured with the respective mounting brackets. The transmitters are mounted on the valve manifold and not on the unit itself. If you order a mounting bracket when choosing the option "Factory mounting of valve manifolds", you will receive a mounting bracket for the valve manifold instead of a bracket for mounting the transmitter. If you order an acceptance test certificate 3.1 to EN 10204 when choosing the option "Factory mounting of valve manifolds", a separate certificate is provided for the transmitters and the valve manifolds respectively. ■ Selection and Ordering data 7MF9011-4FA valve manifold on gauge and absolute pressure transmitters Add -Z to the Article No. of the transmitter Order and add Order codes code SITRANS P300 7MF802.-...1.-... With process connection female thread ½-14 NPT in-sealed with PTFE sealing tape Delivery incl. high-pressure test certified by test report to EN 10204-2.2 T03 Further designs: Delivery includes mounting brackets and mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) A02 Supplied acceptance test certificate to EN 10204- 3.1 for transmitters and mounted valve manifold C12 7MF9011-4EA valve manifold on gauge and absolute pressure transmitters Add -Z to the Article No. of the transmitter Order and add Order codes code SITRANS P300 7MF802.-...0.-... T02 with process connection collar G½ A to EN 837-1 with gasket made of PTFE between valve manifold and transmitter Alternative sealing material: • Soft iron A70 • Stainless steel, Mat. No. 14571 A71 • copper A72 Delivery incl. high-pressure test certified by test report to EN 10204-2.2 Further designs: Delivery includes mounting brackets and mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) A02 Supplied acceptance test certificate to EN 10204- 3.1 for transmitters and mounted valve manifold C12 Siemens FI 01 · 2015 US Edition 1/71 1 © Siemens AG 2015 Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 - Factory-mounting of valve manifolds on transmitters ■ Dimensional drawings 195 (7.7) 160 (6.3) 7MF9011-4EA valve manifold with mounted gauge pressure and absolute pressure transmitters, dimensions in mm (inch) 160 (6.3) 7MF9011-4FA valve manifold with mounted gauge pressure and absolute pressure transmitters 1/72 Siemens FI 01 · 2015 US Edition 270 (10.6) 7MF9011-4EA valve manifold with mounted gauge pressure and absolute pressure transmitters 270 (10.6) 270 (10.6) Valve manifolds mounted on SITRANS P300 270 (10.6) 1 180 (7.1) 7MF9011-4FA valve manifold with mounted gauge pressure and absolute pressure transmitters, dimensions in mm (inch)