DS III - 7MF4133,7MF4134,7MF4135 Gauge/Abs pressure transmitter front-flush diaphragm catalog specifications

© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
■ Technical specifications
SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm
HART
PROFIBUS PA and FOUNDATION Fieldbus
Input of gauge pressure, with front-flush
diaphragm
Measured variable
Gauge pressure, front-flush
Spans (infinitely adjustable) or nominal measur- Span (min. ... max.)
ing range and max. permissible test pressure
Max. perm. test pressure
Nominal measuring
range
Max. perm. test pressure
0.01 ... 1 bar
(0.15 ... 14.5 psi)
6 bar
(87 psi)
1 bar
(14.5 psi)
6 bar
(87 psi)
0.04 ... 4 bar
(0.58 ... 58 psi)
10 bar
(145 psi)
4 bar
(58 psi)
10 bar
(145 psi)
0.16 ... 16 bar
(2.32 ... 232 psi)
32 bar
(464 psi)
16 bar
(232 psi)
32 bar
(464 psi)
0.6 ... 63 bar
(9.14 ... 914 psi)
100 bar
(1450 psi)
63 bar
(914 psi)
100 bar
(1450 psi)
Lower measuring limit
Upper measuring limit
100 mbar a (1.45 psia)
100 % of max. span
100 % of the max. nominal measuring range
Input of absolute pressure, with front-flush
diaphragm
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure
Absolute pressure, front-flush
Span (min. ... max.)
Max. perm. test
pressure
Nominal measuring
range
Max. perm. test
pressure
43 ... 1300 mbar a
(0.62 ... 18.85 psia)
10 bar a
(145 psia)
1300 mbar a
(18.85 psia)
10 bar a
(145 psia)
0.16 ... 5 bar a
(2.32 ... 72.5 psia)
30 bar a
(435 psia)
5 bar a
(72.5 psia)
30 bar a
(435 psia)
1 ... 30 bar a
(14.5 ... 435 psia)
100 bar a
(1450 psia)
30 bar a
(435 psia)
100 bar a
(1450 psia)
Lower measuring limit
Upper measuring limit
0 bar a (0 psia)
100 % of max. span
100 % of the max. nominal measuring range
Output signal
4 ... 20 mA
Digital PROFIBUS PA and FOUNDATION Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or optionally
set to 22.0 mA
-
• Without HART
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
-
• With HART
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
-
Physical bus
-
IEC 61158-2
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the other with max.
supply voltage.
Output
Load
Electrical damping (step width 0.1 s)
Set to 2 s (0 ... 100 s)
Acc. to IEC 60770-1
Measuring accuracy
Reference conditions
(All error data refer always refer to the set span)
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm,
silicone oil filling, room temperature 25 °C (77 °F)
Span ratio r = max. span/set span
Nominal measuring range ratio r = nominal
measuring range/set measuring range
Error in measurement at limit setting incl.
hysteresis and reproducibility
Gauge pressure,
front-flush
Absolute pressure,
front-flush
Gauge pressure,
front-flush
Absolute pressure,
front-flush
• Linear characteristic
- r  10
 (0.0029  r + 0.071) %  0.2 %
 (0.0029  r + 0.071) %  0.2 %
- 10 < r  30
 (0.0045  r + 0.071) %  0.4 %
 (0.0045  r + 0.071) %  0.4 %
- 30 < r  100
 (0.005  r + 0.05) %
 (0.005  r + 0.05) %
Long-term stability
(temperature change  30 °C ( 54 °F))
1/106
Siemens FI 01 · 2015 US Edition
 (0.25  r) % per 5
years
-
 (0.25  r) % per 5
years
-
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm
HART
PROFIBUS PA and FOUNDATION Fieldbus
Gauge pressure,
front-flush
Absolute pressure,
front-flush
Gauge pressure,
front-flush
Absolute pressure,
front-flush
• at -10 ... +60 °C (14 ... 140 °F)
 (0.1  r + 0.2) %1)
 (0.2  r + 0.3) %
 (0.1  r + 0.2) %1)
 (0.2  r + 0.3) %
• at -40 ... -10 °C and 60 ... 85 °C
(-40 ... +14 °F and 140 ... 185 °F)
 (0.1  r + 0.15) %/10 K  (0.2  r + 0.3) %/10 K  (0.1  r + 0.15) %/10 K  (0.2  r + 0.3) %/10 K
Influence of ambient temperature
Influence of mounting position
Measured Value Resolution
0.1 mbar (0.04 inH2O) per 10° inclination
-
3  10-5 of nominal measuring range
Influence of the medium temperature
• Temperature difference between medium
temperature and ambient temperature
3 mbar/10 K (0.04 psi/10 K)
Rated conditions
Installation conditions
Ambient temperature
Observe the temperature class in areas subject to explosion hazard.
• Measuring cell with silicone oil
-40 ... +85 °C (-40 ... +185 °F)
• Measuring cell with Neobee oil (with front-flush
diaphragm)
-10 ... +85 °C (14 ... +185 °F)
• Measuring cell with inert liquid (not with frontflush diaphragm)
-20 ... +85 °C (-4 ... +185 °F)
• Transmitter
(with 4-wire connection, observe temperature
values of supplementary 4-wire electronics)
-40 ... +85 °C (-40 ... +185 °F)
• Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
(in the case of Neobee: -20 ... +85 °C (-4 ... +185/°F))
(for high temperature oil: -10 ... + 85 °C (14 ... 185 °F))
• Climatic class
- Condensation
Degree of protection (to IEC 60529)
Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics
IP66 (optional IP66/IP68), NEMA 4X
• Electromagnetic Compatibility
- Emitted interference and interference immunity
Medium conditions
Acc. to IEC 61326 and NAMUR NE 21
The max. medium temperature of the front-flush process connections is to be taken into account in
accordance with the relevant connection standards (e. g. DIN 32676, DIN 11851 etc.).
Temperature of medium
• Measuring cell with silicone oil
-40 ... +100 °C (-40 ... +212 °F)
• Measuring cell with silicone oil (with front-flush
diaphragm)
-40 ... +150 °C (-40 ... +302 °F)
• Measuring cell with Neobee oil (with front-flush
diaphragm)
-10 ... +150 °C (14 ... 302 °F)
• Measuring cell with silicone oil, with temperature decoupler (only for gauge pressure version with front-flush diaphragm)
-40 ... +200 °C (-40 ... +392 °F)
• Measuring cell with Neobee oil, with temperature decoupler (only for gauge pressure
version with flush-mounted diaphragm)
-10 ... +200 °C (14 ... 392 °F)
• Measuring cell with inert filling liquid
-20 ... +100 °C (-4 ... +212 °F)
• Measuring cell with high-temperature oil (only
for gauge pressure version with front-flush diaphragm)
-10 ... +250 °C (14 ... 482 °F)
Design
Weight (without options)
Enclosure material
Wetted parts materials
 1.5 kg ( 3.3 lb)
Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819
Measuring cell filling
Silicone oil or inert filling liquid
Process connection
• Flanges as per EN and ASME
• F&B and pharmaceutical flanges
Surface quality touched-by-media
Ra-values  0.8 µm (32 µ-inch)/welds Ra)  1.6 µm (64 µ-inch)
(Process connections acc. to 3A; Ra-values  0.8 µm (32 µ-inch)/welds Ra)  0.8 µm (32 µ-inch)
Siemens FI 01 · 2015 US Edition
1/107
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm
HART
PROFIBUS PA and FOUNDATION Fieldbus
Supplied through bus
Power supply UH
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
-
Separate 24 V power supply necessary
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
Bus voltage
Current consumption
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Certificates and approvals
Classification according to PED 97/23/EC
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3,
paragraph 3 (sound engineering practice)
Explosion protection
• Intrinsic safety "i"
PTB 13 ATEX 2007 X
Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
- Marking
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To certified intrinsically-safe circuits with peak
values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW; Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
PTB 99 ATEX 1160
• Explosion-proof "d"
- Marking
Ex II 1/2 G Ex d IIC T4/T6 Gb
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Permissible ambient temperature
- Connection
To circuits with values: UH = 10.5 ... 45 V DC
To circuits with values: UH = 9 ... 32 V DC
PTB 01 ATEX 2055
• Dust explosion protection for zone 20
- Marking
Ex II 1 D IP65 T 120 °C
Ex II 1/2 D IP65 T 120 °C
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
120 °C (248 °F)
- Connection
To certified intrinsically-safe circuits with peak
values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
PTB 01 ATEX 2055
• Dust explosion protection for zone 21/22
- Marking
Ex II 2 D IP65 T 120 °C
- Connection
To circuits with values: UH = 10.5 ... 45 V DC;
Pmax = 1.2 W
• Type of protection "n" (zone 2)
To circuits with values: UH = 9 ... 32 V DC;
Pmax = 1 W
PTB 13 ATEX 2007 X
Ex II 2/3 G Ex nA II T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc
- Marking
- Connection (Ex nA)
Um = 45 V
Um = 32 V
- Connections (Ex ic)
To circuits with values:
Ui = 45 V
FISCO supply unit ic:
Uo = 17.5 V, Io = 570 mA
Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
1/108
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm
HART
PROFIBUS PA and FOUNDATION Fieldbus
Certificates and approvals (continued)
• Explosion protection acc. to FM
- Identification (XP/DIP) or (IS); (NI)
• Explosion protection to CSA
- Identification (XP/DIP) or (IS)
1)
Certificate of Compliance 3008490
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6;
CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Certificate of Compliance 1153651
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD
T4...T6; CL II, DIV 2, GP FG; CL III
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) % / 28 °C (50 °F).
Hygiene version
In the case of SITRANS P DSIII with 7MF413x front-flush diaphragm, selected connections comply with the requirements of EHEDG.
Siemens FI 01 · 2015 US Edition
1/109
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local
operation (standard setting
address 126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION
Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input /Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Register (totalizer)
Can be reset, preset, optional
direction of counting, simulation
function of register output
• Analog input
- Failure mode
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
1/110
Siemens FI 01 · 2015 US Edition
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Selection and Ordering data
Article No.
Pressure transmitter for gauge and absolute
pressure, front-flush diaphragm,
SITRANS P DS III HART
77777 - 7777
7MF 4 1 3 3 -
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Inert liquid
FDA compliant fill fluid
• Neobee oil
Measuring cell cleaning
normal
grease-free to
cleanliness level 2
1
3
normal
4
Measuring span (min. ... max.)
0.01 ... 1 bar
(0.15 ... 14.5 psi)
0.04 ... 4 bar
(0.58 ... 58 psi)
0.16 ... 16 bar
(2.32 ... 232 psi)
0.63 ... 63 bar
(9.14 ... 914 psi)
B
C
D
E
43 ... 1300 mbar a1)
0.16 ... 5 bar a1)
1 ... 30 bar a1)
S
T
U
(0.62 ... 18.85 psia)1)
(0.7 ... 72.5 psia)1)
(4.35 ... 435 psia)1)
1)
Not with temperature decoupler P00 and P10, not for process connections R02,
R04, R10 and R11, and can only be ordered in conjunction with silicone oil.
2)
Only available for flanges with options M.., N.. and Q..
3)
Without cable gland, with blanking plug
4)
Configurations with HAN and M12 connectors are only available in Ex ic.
5)
Only in connection with IP65.
6)
Only in connection with Ex approval A, B or E.
7)
Only in connection with Ex approval A, B, E or F.
8)
M12 delivered without cable socket
Wetted parts materials
Seal diaphragm
Connection shank
Stainless steel
Hastelloy2)
Stainless steel
Stainless steel
Process connection
• Flange version with Order code M.., N.., R.. or Q..
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting
A
B
7
0
3
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)" 3)
- „Ex nA/ic (Zone 2)“4)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"3)
Electrical connection/cable entry
• Inner thread M20 x 1.5
• Female thread ½-14 NPT
• Han 7D plug (plastic housing) incl. mating
connector6)
• M12 connectors (stainless steel)7) 8)
1
2
A
B
D
E
F
S
NC
B
C
D
F
Display
• Without display
• Without visible display
(display concealed, setting: mA)
0
1
• With visible display (setting: mA)
6
• With customer-specific display
(setting as specified, Order code "Y21" or "Y22"
required)
7
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
Siemens FI 01 · 2015 US Edition
1/111
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Selection and Ordering data
Article No.
Selection and Ordering data
Pressure transmitter P for gauge and absolute
pressure, front-flush diaphragm:
SITRANS P DS III with PROFIBUS PA (PA)
7MF 4 1 3 4 -
SITRANS P DS III with PROFIBUS PA (PA)
SITRANS P DS III with FOUNDATION Fieldbus (FF)
7MF 4 1 3 5 -
SITRANS P DS III with FOUNDATION Fieldbus (FF)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Inert liquid
FDA compliant fill fluid
• Neobee oil
Measuring cell cleaning
normal
grease-free to
cleanliness level 2
normal
Nominal measuring range
1 bar
(14.5 psi)
4 bar
(58 psi)
16 bar
(232 psi)
63 bar
(914 psi)
1300 mbar a1)
(18.85 psia)1)
5 bar a1)
(72.5 psia)1)
30 bar a1)
(435 psia)1)
77777 - 7777
Stainless steel
Stainless steel
Process connection
• Flange version with Order code M.., N.., R.. or
Q..
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"3)
- „Ex nA/ic (Zone 2)“4)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"3)
(Available soon)
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel)6) 7)
1/112
Siemens FI 01 · 2015 US Edition
7MF 4 1 3 4 7MF 4 1 3 5 77777 - 7777
Display
• Without display
• Without visible display
(display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting
as specified, Order code "Y21" required)
1
3
4
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
B
C
D
E
S
T
U
Wetted parts materials
Seal diaphragm
Connection shank
Stainless steel
Hastelloy2)
Article No.
Pressure transmitter P for gauge and absolute
pressure, front-flush diaphragm:
A
B
7
0
3
1
2
A
B
D
E
F
S
NC
B
C
F
1)
Not with temperature decoupler P00 and P10, not for process connections
R01, R02, R04, R10 and R11, and can only be ordered in conjunction with
silicone oil.
2)
Only available for flanges with options M.., N.. and Q..
3)
Without cable gland, with blanking plug
4)
5)
Configurations with HAN and M12 connectors are only available in Ex ic.
Only in connection with IP65.
6)
Only in connection with Ex approval A, B, E or F.
7)
M12 delivered without cable socket
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Cable sockets for M12 connectors
(metal (CuZn))
Rating plate inscription (instead of German)
• English
• French
• Spanish
• Italian
• Cyrillic (russian)
Selection and Ordering data
HART PA
A30
A31
A32
A33




A50


FF

Order code
Further designs
Add "-Z" to Article No. and specify Order code.
HART PA
FF
Explosion-proof "Intrinsic safety" to NEPSI E552)
(China)
(only for transmitter 7MF4...-.....-.B..)



Explosion protection "Explosion-proof" to E562)
NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)



E572)



Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E582)
to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E702)



Ex protection "Zone 2" to NEPSI (China)
(only for transmitter 7MF4...-.....-.E..)
B11
B12
B13
B14
B16















English rating plate
Pressure units in inH20 and/or psi
B21



Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11



Two coats of lacquer on casing and cover
(PU on epoxy)
G10



Inspection certificate
Acc. to EN 10204-3.1
C12



Transient protector 6 kV (lightning protec- J01
tion)



Factory certificate
Acc. to EN 10204-2.2
C14



Functional safety (SIL2)
C20
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration

Functional safety (PROFIsafe)
Certificate and PROFIsafe protocol
C211)

Functional safety (SIL2/3)
C23
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration

Device passport Russia
C99

Setting of upper limit of output signal to
22.0 mA
D05

Degree of protection IP66/IP68
(only for M20x1.5 and ½-14 NPT)
D12
Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included





D59



Oxygen application
E10
(In the case of oxygen measurement and inert
liquid max. 100 bar (1450 psi) at 60°C (140 °F))



Export approval Korea
E11



CRN approval Canada
(Canadian Registration Number)
E22



Dual seal
E24



Explosion-proof "Intrinsic safety" (Ex ia) to E252)
INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.B..)



"Flameproof" explosion protection accord- E262)
ing to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.D..)



Explosion-proof "Intrinsic safety" (Ex ia +
Ex d) to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.P..)
E282)


Ex Approval IEC Ex (Ex ia)
(only for transmitter 7MF4...-.....-.B..)
E452)



Ex Approval IEC Ex (Ex d)
(only for transmitter 7MF4...-.....-.D..)
E462)



(For price request please contact the technical
support
www.siemens.com/automation/support-request.)
Flanges to EN 1092-1, Form B1
• DN 25, PN 403)
• DN 25, PN 1003)
• DN 40, PN 40
• DN 40, PN 100
• DN 50, PN 16
• DN 50, PN 40
• DN 80, PN 16
• DN 80, PN 40
M11
M21
M13
M23
M04
M14
M06
M16
























Flanges to ASME B16.5
• Stainless steel flange 1" class 1503)
• Stainless steel flange 1½" class 150
• Stainless steel flange 2" class 150
• Stainless steel flange 3" class 150
• Stainless steel flange 4" class 150
• Stainless steel flange 1" class 3003)
• Stainless steel flange 1½" class 300
• Stainless steel flange 2" class 300
• Stainless steel flange 3" class 300
• Stainless steel flange 4" class 300
M40
M41
M42
M43
M44
M45
M46
M47
M48
M49






























Threaded connector to DIN 3852-2,
form A, thread to ISO 2284)
• G ¾"-A, front-flush
• G 1"-A, front-flush
• G 2"-A, front-flush
R01
R02
R04









Tank connection5)
Sealing is included in delivery
• TG 52/50, PN 40
• TG 52/150, PN 40
R10
R11






Sanitary process connection according
DIN 11851 (Dairy connection with slotted
union nut)
• DN 50, PN 25
• DN 80, PN 25
N04
N06






Tri-Clamp connection according
DIN 32676/ISO 2852
• DN 50/2", PN 16
• DN 65/3", PN 10
N14
N15






N28



Varivent connection
Certified to EHEDG
• Type N = 68 for Varivent housing
DN 40 ... 125 und 1½" ... 6", PN 40
Siemens FI 01 · 2015 US Edition
1/113
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Temperature decoupler up to 200 °C6)
for version with front-flush diaphragm
Selection and Ordering data
HART PA
Further designs
Add "-Z" to Article No. and specify Order code.
Aseptic threaded socket to DIN 11864-1
Form A
approved according to EHEDG
• DN 50, PN 25
• DN 65, PN 25
• DN 80, PN 25
• DN 100, PN 25
N33
N34
N35
N36












Aseptic flange with notch to DIN 11864-2
Form A
approved according to EHEDG
• DN 50, PN 16
• DN 65, PN 16
• DN 80, PN 16
• DN 100, PN 16
N43
N44
N45
N46












N43 +
P11
N44 +
P11
N45 +
P11
N46 +
P11












N53
N54
N55
N56












P00



Temperature decoupler up to 250 °C
P10
Measuring cell filling: High-temperature oil,
only in conjunction with measuring cell filling
silicone oil



Sanitary process connection to DRD
• DN 50, PN 40
M32



SMS socket with union nut
• 2“
• 2½“
• 3“
M67
M68
M69









SMS threaded socket
• 2“
• 2½“
• 3“
M73
M74
M75









M82
M83
M84









IDF threaded socket ISO 2853
• 2“
• 2½“
• 3“
M92
M93
M94









Q05
Q06
Q07
Q08
Q13
Q14
Q15
Q16
























Sanitary process connection to NEUMO
Bio-Connect flange connection
Certified to EHEDG
• DN 50, PN 16
• DN 65, PN 16
• DN 80, PN 16
• DN 100, PN 16
• DN 2", PN 16
• DN 2½", PN 16
• DN 3", PN 16
• DN 4", PN 16
Q23
Q24
Q25
Q26
Q31
Q32
Q33
Q34
























Sanitary process connection to
NEUMO Bio-Connect clamp connection
Certified to EHEDG
• DN 50, PN 16
• DN 65, PN 10
• DN 80, PN 10
• DN 100, PN 10
• DN 2½", PN 16
• DN 3", PN 10
• DN 4", PN 10
Q39
Q40
Q41
Q42
Q48
Q49
Q50





















Sanitary process connection to
NEUMO Bio-Connect S flange connection
Certified to EHEDG
• DN 2", PN 16
Q72



1/114
Siemens FI 01 · 2015 US Edition
HART PA
FF
Aseptic flange with groove to DIN 11864-2
Form A approved according to EHEDG
• DN 50, PN 16
IDF socket with union nut ISO 2853
• 2“
• 2½“
• 3“
Sanitary process connection to
NEUMO Bio-Connect screw connection
Certified to EHEDG
• DN 50, PN 16
• DN 65, PN 16
• DN 80, PN 16
• DN 100, PN 16
• DN 2", PN 16
• DN 2½", PN 16
• DN 3", PN 16
• DN 4", PN 16
Order code
FF
• DN 65, PN 16
• DN 80, PN 16
• DN 100, PN 16
Aseptic clamp with groove to DIN 11864-3
FormA
approved according to EHEDG
• DN 50, PN 25
• DN 65, PN 25
• DN 80, PN 16
• DN 100, PN 16
1)
Profisafe transmitters can only be operated with the S7 F Systems V6.1
configuration software in combination with S7-400H.
2)
Option does not include ATEX approval, but instead includes only the
country-specific approval.
3)
Special seal in Viton included in the scope of delivery
4)
Lower measuring limit -100 mbar (1.45 psi).
5)
The weldable socket can be ordered under accessories.
6)
Certified to 3A and EHEDG. The maximum permissible temperatures of the
medium depend on the respective cell fillings (see medium conditions).
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Selection and Ordering data
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text (max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
Y01

1)
Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Y15



Measuring point text (entry in device variable)
Max. 27 characters, specify in plain text:
Y16: ...........................................
Y16



Entry of HART address (TAG)
Y17

Setting of pressure indicator in pressure
Y21
units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C



Setting of pressure indication in
Y22 +
non-pressure units2)
Y01
Specify in plain text:
3
Y22: ..... up to ..... l/min, m /h, m, USgpm, ...
(specification of measuring range in pressure
units "Y01" is essential, unit with max. 5
characters)





Max. 8 characters, specify in plain text:
Y17: ...........................................
Preset bus address
possible between 1 and 126
Specify in plain text:
Y25: .....................
Y25
Damping adjustment in seconds
(0 ... 100 s)
Y30

Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset
 = available
Ordering example
Item line:
7MF4133-1DB20-1AB7-Z
B line:
A22 + Y01 + Y21
C line:
Y01: 1 ... 10 bar (14.5 ... 145 psi)
C line:
Y21: bar (psi)
1)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
2)
Preset values can only be changed over SIMATIC PDM.
Siemens FI 01 · 2015 US Edition
1/115
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
15
(0.6)
53 (2.1)
Ø80 (3.15)
1
2
3
5
7
Space for rotation
of housing
3
2
Temperature decoupler
4
84 (3.31)
50 (1.97)
1
29 (1.14)
6
H1 = approx. 130 (5.12)
143 (5.6)
74 (2.9)
H 2 = approx.
55 (2.17)
15
(0.6)
24
(0.94)
■ Dimensional drawings
50 (1.97)
1
min. 90 (3.54) 2)
Electronic side, digital display
(longer overall length for cover with window)1)
4
Protective cover over keys
5
Blanking plug
Terminal side1)
6
Electrical connection:
Screwed gland M20 x 1,5 or screwed gland ½-14 NPT or
M12 conector
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
7
Process connection: see flange tables
1)
2) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
92 mm (3.6 inch) for minimum distance to permit rotation with indicator
SITRANS P pressure transmitters, DS III series for gauge pressure, with front-flush diaphragm, dimensions in mm (inch)
The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H1 and H2.
H1 = Height of the SITRANS P300 up to a defined cross-section
H2 = Height of the flange up to this defined cross-section
Only the height H2 is indicated in the dimensions of the flanges.
1/116
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Flanges as per EN and ASME
Sanitary process screw connection to NEUMO Bio-Connect
Flange to EN
Order DN
code
H2
Order DN
code
D
M11
M21
M13
M23
M04
M14
M06
M16
25
25
40
40
50
50
80
80
PN
D
H2
40
100
40
100
16
40
16
40
115 mm (4.5“)
140 mm (5.5“)
150 mm (5.9“)
170 mm (6.7“)
165 mm (6.5“)
165 mm (6.5“)
200 mm (7.9“)
200 mm (7.9“)
Approx.
52 mm (2“)
H2
EN 1092-1
D
Order DN
code
H2
Order DN
code
M40
M41
M42
M43
M44
M45
M46
M47
M48
M49
1“
1½“
2“
3“
4“
1“
1½“
2“
3“
4“
H2
ASME B16.5
PN
D
150
150
150
150
150
300
300
300
300
300
110 mm (4.3“) Approx.
130 mm (5.1“) 52 mm (2“)
150 mm (5.9“)
190 mm (7.5“)
230 mm (9.1“)
125 mm (4.9“)
155 mm (6.1“)
165 mm (6.5“)
210 mm (8.1“)
255 mm (10.0“)
H2
D
H2
DIN 11851 (milk pipe union with slotted union nut)
H2
N04
N06
50
80
PN
D
H2
25
25
92 mm (3.6“)
127 mm (5.0“)
Approx.
52 mm (2“)
D
Q23
Q24
Q25
Q26
Q31
Q32
Q33
Q34
50
65
80
100
2“
2½“
3“
4“
Order DN
code
Connections to DIN
Order DN
code
H2
16
16
16
16
16
16
16
16
82 mm (3.2“)
105 mm (4.1“)
115 mm (4.5“)
145 mm (5.7“)
82 mm (3.2“)
105 mm (4.1“)
105 mm (4.1“)
145 mm (5.7“)
Approx.
52 mm (2“)
PN
D
H2
16
16
16
16
16
16
16
16
110 mm (4.3“)
140 mm (5.5“)
150 mm (5.9“)
175 mm (6.9“)
100 mm (3.9“)
110 mm (4.3“)
140 mm (5.5“)
175 mm (6.9“)
Approx.
52 mm (2“)
Sanitary process connection to NEUMO Bio-Connect clamp
connection
NuG and pharmaceutical connections
D
2
Q39
Q40
Q41
Q42
Q47
Q48
Q49
Q50
50
65
80
100
2“
2½“
3“
4“
PN
D
16
10
10
10
16
16
10
10
77.4 mm (3.0“) Approx.
90.9 mm (3.6“) 52 mm (2“)
106 mm (4.2“)
119 mm (4.7“)
77.4 mm (3.0“)
90.9 mm (3.6“)
106 mm (4.2“)
119 mm (4.7“)
H2
Sanitary process connection to NEUMO Bio-Connect S flange
connection
Order DN
code
Order DN
code
N14
N15
50
65
PN
D
H2
16
10
64 mm (2.5“)
91 mm (3.6“)
Approx.
52 mm (2“)
H2
Tri-Clamp nach DIN 32676
H2
50
65
80
100
2“
2½“
3“
4“
D
Sanitary process connection to NEUMO Bio-Connect flange
connection
Flanges to ASME
D
Q05
Q06
Q07
Q08
Q13
Q14
Q15
Q16
PN
Q72
2“
PN
D
H2
16
125 mm (4.9“)
Approx.
52 mm (2“)
D
Threaded connection G¾", G1" and G2" acc. to DIN 3852
D
D
H2
Varivent connection
R01
¾“
60
37 mm (1.5“)
R02
1“
60
48 mm (1.9“)
R04
2“
60
78 mm (3.1“)
Approx.
45 mm
(1.8“)
Approx.
47 mm
(1.9“)
Approx.
52 mm (2“)
H2
Order DN
code
PN
Other connections
Order DN
code
H2
N28
PN
D
H2
40
84 mm
(3.3“)
Approx.
52 mm (2“)
D
40 ... 125
D
Sanitary process connection to DRD
H2
Order DN
code
M32
50
PN
D
H2
40
105 mm (4.1“)
Approx.
52 mm (2“)
D
Siemens FI 01 · 2015 US Edition
1/117
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm
Tank connection TG 52/50 and TG52/150
Aseptic threaded socket to DIN 11864-1 Form A
PN
D
H2
Order DN
code
PN
D
H2
Approx.
63 mm
(2.5“)
Approx.
170 mm
(6.7“)
N33
N34
N35
N36
50
65
80
100
25
25
25
25
78 x 1/6“
95 x 1/6“
110 x ¼“
130 x ¼“
Approx.
52 mm (2“)
25
40
63 mm (2.5“)
R11
25
40
63 mm (2.5“)
H2
R10
D
H2
Order DN
code
D
SMS socket with union nut
M67
M68
M69
PN
2“
25
2½“ 25
3“
25
D
H2
84 mm (3.3“)
100 mm (3.9“)
114 mm (4.5“)
Approx.
52 mm (2“)
Aseptic flange with notch to DIN 11864-2 Form A
H2
H2
Order DN
code
D
D
SMS threaded socket
H2
M73
M74
M75
PN
2“
25
2½“ 25
3“
25
H2
70 x 1/6 mm
85 x 1/6 mm
98 x 1/6 mm
Approx.
52 mm (2“)
D
D
IDF socket with union nut
H2
Order DN
code
M82
M83
M84
PN
2“
25
2½“ 25
3“
25
D
H2
77 mm (3“)
91 mm (3.6“)
106 mm (4.2“)
Approx.
52 mm (2“)
H2
M92
M93
M94
2“
25
2½“ 25
3“
25
D
1/118
H2
64 mm (2.5“)
Approx.
77.5 mm (3.1“) 52 mm (2“)
91 mm (3.6“)
D
Siemens FI 01 · 2015 US Edition
D
H2
50
65
80
100
16
16
16
16
94
113
133
159
Approx.
52 mm (2“)
N43
N44
N45
N46
Order DN
code
PN
D
H2
N43 + 50
P11
N44 + 65
P11
N45 + 80
P11
N46 + 100
P11
16
94
Approx.
52 mm (2“)
16
113
16
133
16
159
Order DN
code
PN
D
H2
50
65
80
100
25
25
16
16
77.5
91
106
130
Approx.
52 mm (2“)
N53
N54
N55
N56
IDF threaded socket
PN
PN
Aseptic clamp with groove to DIN 11864-3 Form A
D
Order DN
code
Order DN
code
Aseptic flange with groove to DIN 11864-2 Form A
D
H2
Order DN
code
H2
1
D