© Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm ■ Technical specifications SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART PROFIBUS PA and FOUNDATION Fieldbus Input of gauge pressure, with front-flush diaphragm Measured variable Gauge pressure, front-flush Spans (infinitely adjustable) or nominal measur- Span (min. ... max.) ing range and max. permissible test pressure Max. perm. test pressure Nominal measuring range Max. perm. test pressure 0.01 ... 1 bar (0.15 ... 14.5 psi) 6 bar (87 psi) 1 bar (14.5 psi) 6 bar (87 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 10 bar (145 psi) 4 bar (58 psi) 10 bar (145 psi) 0.16 ... 16 bar (2.32 ... 232 psi) 32 bar (464 psi) 16 bar (232 psi) 32 bar (464 psi) 0.6 ... 63 bar (9.14 ... 914 psi) 100 bar (1450 psi) 63 bar (914 psi) 100 bar (1450 psi) Lower measuring limit Upper measuring limit 100 mbar a (1.45 psia) 100 % of max. span 100 % of the max. nominal measuring range Input of absolute pressure, with front-flush diaphragm Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure Absolute pressure, front-flush Span (min. ... max.) Max. perm. test pressure Nominal measuring range Max. perm. test pressure 43 ... 1300 mbar a (0.62 ... 18.85 psia) 10 bar a (145 psia) 1300 mbar a (18.85 psia) 10 bar a (145 psia) 0.16 ... 5 bar a (2.32 ... 72.5 psia) 30 bar a (435 psia) 5 bar a (72.5 psia) 30 bar a (435 psia) 1 ... 30 bar a (14.5 ... 435 psia) 100 bar a (1450 psia) 30 bar a (435 psia) 100 bar a (1450 psia) Lower measuring limit Upper measuring limit 0 bar a (0 psia) 100 % of max. span 100 % of the max. nominal measuring range Output signal 4 ... 20 mA Digital PROFIBUS PA and FOUNDATION Fieldbus signal • Lower limit (infinitely adjustable) 3.55 mA, factory preset to 3.84 mA - • Upper limit (infinitely adjustable) 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA - • Without HART RB (UH - 10.5 V)/0.023 A in , UH: Power supply in V - • With HART RB = 230 ... 500 (SIMATIC PDM) or RB = 230 ... 1100 (HART Communicator) - Physical bus - IEC 61158-2 Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Output Load Electrical damping (step width 0.1 s) Set to 2 s (0 ... 100 s) Acc. to IEC 60770-1 Measuring accuracy Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Gauge pressure, front-flush Absolute pressure, front-flush Gauge pressure, front-flush Absolute pressure, front-flush • Linear characteristic - r 10 (0.0029 r + 0.071) % 0.2 % (0.0029 r + 0.071) % 0.2 % - 10 < r 30 (0.0045 r + 0.071) % 0.4 % (0.0045 r + 0.071) % 0.4 % - 30 < r 100 (0.005 r + 0.05) % (0.005 r + 0.05) % Long-term stability (temperature change 30 °C ( 54 °F)) 1/106 Siemens FI 01 · 2015 US Edition (0.25 r) % per 5 years - (0.25 r) % per 5 years - © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART PROFIBUS PA and FOUNDATION Fieldbus Gauge pressure, front-flush Absolute pressure, front-flush Gauge pressure, front-flush Absolute pressure, front-flush • at -10 ... +60 °C (14 ... 140 °F) (0.1 r + 0.2) %1) (0.2 r + 0.3) % (0.1 r + 0.2) %1) (0.2 r + 0.3) % • at -40 ... -10 °C and 60 ... 85 °C (-40 ... +14 °F and 140 ... 185 °F) (0.1 r + 0.15) %/10 K (0.2 r + 0.3) %/10 K (0.1 r + 0.15) %/10 K (0.2 r + 0.3) %/10 K Influence of ambient temperature Influence of mounting position Measured Value Resolution 0.1 mbar (0.04 inH2O) per 10° inclination - 3 10-5 of nominal measuring range Influence of the medium temperature • Temperature difference between medium temperature and ambient temperature 3 mbar/10 K (0.04 psi/10 K) Rated conditions Installation conditions Ambient temperature Observe the temperature class in areas subject to explosion hazard. • Measuring cell with silicone oil -40 ... +85 °C (-40 ... +185 °F) • Measuring cell with Neobee oil (with front-flush diaphragm) -10 ... +85 °C (14 ... +185 °F) • Measuring cell with inert liquid (not with frontflush diaphragm) -20 ... +85 °C (-4 ... +185 °F) • Transmitter (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) -40 ... +85 °C (-40 ... +185 °F) • Display readable -30 ... +85 °C (-22 ... +185 °F) • Storage temperature -50 ... +85 °C (-58 ... +185 °F) (in the case of Neobee: -20 ... +85 °C (-4 ... +185/°F)) (for high temperature oil: -10 ... + 85 °C (14 ... 185 °F)) • Climatic class - Condensation Degree of protection (to IEC 60529) Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics IP66 (optional IP66/IP68), NEMA 4X • Electromagnetic Compatibility - Emitted interference and interference immunity Medium conditions Acc. to IEC 61326 and NAMUR NE 21 The max. medium temperature of the front-flush process connections is to be taken into account in accordance with the relevant connection standards (e. g. DIN 32676, DIN 11851 etc.). Temperature of medium • Measuring cell with silicone oil -40 ... +100 °C (-40 ... +212 °F) • Measuring cell with silicone oil (with front-flush diaphragm) -40 ... +150 °C (-40 ... +302 °F) • Measuring cell with Neobee oil (with front-flush diaphragm) -10 ... +150 °C (14 ... 302 °F) • Measuring cell with silicone oil, with temperature decoupler (only for gauge pressure version with front-flush diaphragm) -40 ... +200 °C (-40 ... +392 °F) • Measuring cell with Neobee oil, with temperature decoupler (only for gauge pressure version with flush-mounted diaphragm) -10 ... +200 °C (14 ... 392 °F) • Measuring cell with inert filling liquid -20 ... +100 °C (-4 ... +212 °F) • Measuring cell with high-temperature oil (only for gauge pressure version with front-flush diaphragm) -10 ... +250 °C (14 ... 482 °F) Design Weight (without options) Enclosure material Wetted parts materials 1.5 kg ( 3.3 lb) Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408 Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 Measuring cell filling Silicone oil or inert filling liquid Process connection • Flanges as per EN and ASME • F&B and pharmaceutical flanges Surface quality touched-by-media Ra-values 0.8 µm (32 µ-inch)/welds Ra) 1.6 µm (64 µ-inch) (Process connections acc. to 3A; Ra-values 0.8 µm (32 µ-inch)/welds Ra) 0.8 µm (32 µ-inch) Siemens FI 01 · 2015 US Edition 1/107 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART PROFIBUS PA and FOUNDATION Fieldbus Supplied through bus Power supply UH Terminal voltage on transmitter 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode - Separate 24 V power supply necessary - No • Not Ex - 9 ... 32 V • With intrinsically-safe operation - 9 ... 24 V Bus voltage Current consumption • Basic current (max.) - 12.5 mA • Start-up current basic current - Yes • Max. current in event of fault - 15.5 mA Fault disconnection electronics (FDE) available - Yes Certificates and approvals Classification according to PED 97/23/EC For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) Explosion protection • Intrinsic safety "i" PTB 13 ATEX 2007 X Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Marking - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 • Explosion-proof "d" - Marking Ex II 1/2 G Ex d IIC T4/T6 Gb -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Permissible ambient temperature - Connection To circuits with values: UH = 10.5 ... 45 V DC To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 • Dust explosion protection for zone 20 - Marking Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Max. surface temperature 120 °C (248 °F) - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 • Dust explosion protection for zone 21/22 - Marking Ex II 2 D IP65 T 120 °C - Connection To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W • Type of protection "n" (zone 2) To circuits with values: UH = 9 ... 32 V DC; Pmax = 1 W PTB 13 ATEX 2007 X Ex II 2/3 G Ex nA II T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc - Marking - Connection (Ex nA) Um = 45 V Um = 32 V - Connections (Ex ic) To circuits with values: Ui = 45 V FISCO supply unit ic: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF 1/108 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART PROFIBUS PA and FOUNDATION Fieldbus Certificates and approvals (continued) • Explosion protection acc. to FM - Identification (XP/DIP) or (IS); (NI) • Explosion protection to CSA - Identification (XP/DIP) or (IS) 1) Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) % / 28 °C (50 °F). Hygiene version In the case of SITRANS P DSIII with 7MF413x front-flush diaphragm, selected connections comply with the requirements of EHEDG. Siemens FI 01 · 2015 US Edition 1/109 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm HART communication HART 230 ... 1100 Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with master class 2 (max.) 4 The address can be set using Configuration tool or local operation (standard setting address 126) Cyclic data usage • Output byte 5 (one measured value) or 10 (two measured values) • Input byte 0, 1, or 2 (register operating mode and reset function for metering) Internal preprocessing FOUNDATION Fieldbus communication Function blocks 3 function blocks analog input, 1 function block PID • Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 ... 100 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic for flow measurement Yes Device profile PROFIBUS PA Profile for Process Control Devices Version 3.0, class B • PID Standard FOUNDATION Fieldbus function block • Physical block 1 resource block Function blocks 2 Transducer blocks - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic 1 transducer block Pressure with calibration, 1 transducer block LCD • Pressure transducer block - Electrical damping, adjustable 0 ... 100 s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively • Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output • Analog input - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively • Physical block 1 Transducer blocks 2 • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Specification of a container characteristic with Max. 30 nodes - Square-rooted characteristic for flow measurement Yes - Gradual volume suppression and implementation point of square-root extraction Parameterizable - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function 1/110 Siemens FI 01 · 2015 US Edition - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Article No. Pressure transmitter for gauge and absolute pressure, front-flush diaphragm, SITRANS P DS III HART 77777 - 7777 7MF 4 1 3 3 - Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid FDA compliant fill fluid • Neobee oil Measuring cell cleaning normal grease-free to cleanliness level 2 1 3 normal 4 Measuring span (min. ... max.) 0.01 ... 1 bar (0.15 ... 14.5 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 0.16 ... 16 bar (2.32 ... 232 psi) 0.63 ... 63 bar (9.14 ... 914 psi) B C D E 43 ... 1300 mbar a1) 0.16 ... 5 bar a1) 1 ... 30 bar a1) S T U (0.62 ... 18.85 psia)1) (0.7 ... 72.5 psia)1) (4.35 ... 435 psia)1) 1) Not with temperature decoupler P00 and P10, not for process connections R02, R04, R10 and R11, and can only be ordered in conjunction with silicone oil. 2) Only available for flanges with options M.., N.. and Q.. 3) Without cable gland, with blanking plug 4) Configurations with HAN and M12 connectors are only available in Ex ic. 5) Only in connection with IP65. 6) Only in connection with Ex approval A, B or E. 7) Only in connection with Ex approval A, B, E or F. 8) M12 delivered without cable socket Wetted parts materials Seal diaphragm Connection shank Stainless steel Hastelloy2) Stainless steel Stainless steel Process connection • Flange version with Order code M.., N.., R.. or Q.. Non-wetted parts materials • Housing made of die-cast aluminium • Housing stainless steel precision casting A B 7 0 3 Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)" 3) - „Ex nA/ic (Zone 2)“4) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"3) Electrical connection/cable entry • Inner thread M20 x 1.5 • Female thread ½-14 NPT • Han 7D plug (plastic housing) incl. mating connector6) • M12 connectors (stainless steel)7) 8) 1 2 A B D E F S NC B C D F Display • Without display • Without visible display (display concealed, setting: mA) 0 1 • With visible display (setting: mA) 6 • With customer-specific display (setting as specified, Order code "Y21" or "Y22" required) 7 Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation Siemens FI 01 · 2015 US Edition 1/111 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Article No. Selection and Ordering data Pressure transmitter P for gauge and absolute pressure, front-flush diaphragm: SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 1 3 4 - SITRANS P DS III with PROFIBUS PA (PA) SITRANS P DS III with FOUNDATION Fieldbus (FF) 7MF 4 1 3 5 - SITRANS P DS III with FOUNDATION Fieldbus (FF) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid FDA compliant fill fluid • Neobee oil Measuring cell cleaning normal grease-free to cleanliness level 2 normal Nominal measuring range 1 bar (14.5 psi) 4 bar (58 psi) 16 bar (232 psi) 63 bar (914 psi) 1300 mbar a1) (18.85 psia)1) 5 bar a1) (72.5 psia)1) 30 bar a1) (435 psia)1) 77777 - 7777 Stainless steel Stainless steel Process connection • Flange version with Order code M.., N.., R.. or Q.. Non-wetted parts materials • Housing made of die-cast aluminium • Housing stainless steel precision casting Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"3) - „Ex nA/ic (Zone 2)“4) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"3) (Available soon) Electrical connection/cable entry • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • M12 connectors (stainless steel)6) 7) 1/112 Siemens FI 01 · 2015 US Edition 7MF 4 1 3 4 7MF 4 1 3 5 77777 - 7777 Display • Without display • Without visible display (display concealed, setting: bar) • With visible display (setting: bar) • With customer-specific display (setting as specified, Order code "Y21" required) 1 3 4 0 1 6 7 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation B C D E S T U Wetted parts materials Seal diaphragm Connection shank Stainless steel Hastelloy2) Article No. Pressure transmitter P for gauge and absolute pressure, front-flush diaphragm: A B 7 0 3 1 2 A B D E F S NC B C F 1) Not with temperature decoupler P00 and P10, not for process connections R01, R02, R04, R10 and R11, and can only be ordered in conjunction with silicone oil. 2) Only available for flanges with options M.., N.. and Q.. 3) Without cable gland, with blanking plug 4) 5) Configurations with HAN and M12 connectors are only available in Ex ic. Only in connection with IP65. 6) Only in connection with Ex approval A, B, E or F. 7) M12 delivered without cable socket © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Plug • Han 7D (metal) • Han 8D (instead of Han 7D) • Angled • Han 8D (metal) Cable sockets for M12 connectors (metal (CuZn)) Rating plate inscription (instead of German) • English • French • Spanish • Italian • Cyrillic (russian) Selection and Ordering data HART PA A30 A31 A32 A33 A50 FF Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Explosion-proof "Intrinsic safety" to NEPSI E552) (China) (only for transmitter 7MF4...-.....-.B..) Explosion protection "Explosion-proof" to E562) NEPSI (China) (only for transmitter 7MF4...-.....-.D..) E572) Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E582) to NEPSI (China) (only for transmitter 7MF4...-.....-.R..) "Intrinsic safety" and "Explosion-proof" explosion protection acc. to Kosha (Korea) (only for transmitter 7MF4...-.....-.[B, D]..-Z + E11) E702) Ex protection "Zone 2" to NEPSI (China) (only for transmitter 7MF4...-.....-.E..) B11 B12 B13 B14 B16 English rating plate Pressure units in inH20 and/or psi B21 Quality inspection certificate (Five-step factory calibration) to IEC 60770-2 C11 Two coats of lacquer on casing and cover (PU on epoxy) G10 Inspection certificate Acc. to EN 10204-3.1 C12 Transient protector 6 kV (lightning protec- J01 tion) Factory certificate Acc. to EN 10204-2.2 C14 Functional safety (SIL2) C20 Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C211) Functional safety (SIL2/3) C23 Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration Device passport Russia C99 Setting of upper limit of output signal to 22.0 mA D05 Degree of protection IP66/IP68 (only for M20x1.5 and ½-14 NPT) D12 Capri cable gland 4F CrNi and clamping device (848699 + 810634) included D59 Oxygen application E10 (In the case of oxygen measurement and inert liquid max. 100 bar (1450 psi) at 60°C (140 °F)) Export approval Korea E11 CRN approval Canada (Canadian Registration Number) E22 Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E252) INMETRO (Brazil) (only for transmitter 7MF4...-.....-.B..) "Flameproof" explosion protection accord- E262) ing to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.D..) Explosion-proof "Intrinsic safety" (Ex ia + Ex d) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.P..) E282) Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF4...-.....-.B..) E452) Ex Approval IEC Ex (Ex d) (only for transmitter 7MF4...-.....-.D..) E462) (For price request please contact the technical support www.siemens.com/automation/support-request.) Flanges to EN 1092-1, Form B1 • DN 25, PN 403) • DN 25, PN 1003) • DN 40, PN 40 • DN 40, PN 100 • DN 50, PN 16 • DN 50, PN 40 • DN 80, PN 16 • DN 80, PN 40 M11 M21 M13 M23 M04 M14 M06 M16 Flanges to ASME B16.5 • Stainless steel flange 1" class 1503) • Stainless steel flange 1½" class 150 • Stainless steel flange 2" class 150 • Stainless steel flange 3" class 150 • Stainless steel flange 4" class 150 • Stainless steel flange 1" class 3003) • Stainless steel flange 1½" class 300 • Stainless steel flange 2" class 300 • Stainless steel flange 3" class 300 • Stainless steel flange 4" class 300 M40 M41 M42 M43 M44 M45 M46 M47 M48 M49 Threaded connector to DIN 3852-2, form A, thread to ISO 2284) • G ¾"-A, front-flush • G 1"-A, front-flush • G 2"-A, front-flush R01 R02 R04 Tank connection5) Sealing is included in delivery • TG 52/50, PN 40 • TG 52/150, PN 40 R10 R11 Sanitary process connection according DIN 11851 (Dairy connection with slotted union nut) • DN 50, PN 25 • DN 80, PN 25 N04 N06 Tri-Clamp connection according DIN 32676/ISO 2852 • DN 50/2", PN 16 • DN 65/3", PN 10 N14 N15 N28 Varivent connection Certified to EHEDG • Type N = 68 for Varivent housing DN 40 ... 125 und 1½" ... 6", PN 40 Siemens FI 01 · 2015 US Edition 1/113 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Temperature decoupler up to 200 °C6) for version with front-flush diaphragm Selection and Ordering data HART PA Further designs Add "-Z" to Article No. and specify Order code. Aseptic threaded socket to DIN 11864-1 Form A approved according to EHEDG • DN 50, PN 25 • DN 65, PN 25 • DN 80, PN 25 • DN 100, PN 25 N33 N34 N35 N36 Aseptic flange with notch to DIN 11864-2 Form A approved according to EHEDG • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 N43 N44 N45 N46 N43 + P11 N44 + P11 N45 + P11 N46 + P11 N53 N54 N55 N56 P00 Temperature decoupler up to 250 °C P10 Measuring cell filling: High-temperature oil, only in conjunction with measuring cell filling silicone oil Sanitary process connection to DRD • DN 50, PN 40 M32 SMS socket with union nut • 2“ • 2½“ • 3“ M67 M68 M69 SMS threaded socket • 2“ • 2½“ • 3“ M73 M74 M75 M82 M83 M84 IDF threaded socket ISO 2853 • 2“ • 2½“ • 3“ M92 M93 M94 Q05 Q06 Q07 Q08 Q13 Q14 Q15 Q16 Sanitary process connection to NEUMO Bio-Connect flange connection Certified to EHEDG • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 • DN 2", PN 16 • DN 2½", PN 16 • DN 3", PN 16 • DN 4", PN 16 Q23 Q24 Q25 Q26 Q31 Q32 Q33 Q34 Sanitary process connection to NEUMO Bio-Connect clamp connection Certified to EHEDG • DN 50, PN 16 • DN 65, PN 10 • DN 80, PN 10 • DN 100, PN 10 • DN 2½", PN 16 • DN 3", PN 10 • DN 4", PN 10 Q39 Q40 Q41 Q42 Q48 Q49 Q50 Sanitary process connection to NEUMO Bio-Connect S flange connection Certified to EHEDG • DN 2", PN 16 Q72 1/114 Siemens FI 01 · 2015 US Edition HART PA FF Aseptic flange with groove to DIN 11864-2 Form A approved according to EHEDG • DN 50, PN 16 IDF socket with union nut ISO 2853 • 2“ • 2½“ • 3“ Sanitary process connection to NEUMO Bio-Connect screw connection Certified to EHEDG • DN 50, PN 16 • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 • DN 2", PN 16 • DN 2½", PN 16 • DN 3", PN 16 • DN 4", PN 16 Order code FF • DN 65, PN 16 • DN 80, PN 16 • DN 100, PN 16 Aseptic clamp with groove to DIN 11864-3 FormA approved according to EHEDG • DN 50, PN 25 • DN 65, PN 25 • DN 80, PN 16 • DN 100, PN 16 1) Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H. 2) Option does not include ATEX approval, but instead includes only the country-specific approval. 3) Special seal in Viton included in the scope of delivery 4) Lower measuring limit -100 mbar (1.45 psi). 5) The weldable socket can be ordered under accessories. 6) Certified to 3A and EHEDG. The maximum permissible temperatures of the medium depend on the respective cell fillings (see medium conditions). © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi Y01 1) Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Y15 Measuring point text (entry in device variable) Max. 27 characters, specify in plain text: Y16: ........................................... Y16 Entry of HART address (TAG) Y17 Setting of pressure indicator in pressure Y21 units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Setting of pressure indication in Y22 + non-pressure units2) Y01 Specify in plain text: 3 Y22: ..... up to ..... l/min, m /h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Max. 8 characters, specify in plain text: Y17: ........................................... Preset bus address possible between 1 and 126 Specify in plain text: Y25: ..................... Y25 Damping adjustment in seconds (0 ... 100 s) Y30 Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset = available Ordering example Item line: 7MF4133-1DB20-1AB7-Z B line: A22 + Y01 + Y21 C line: Y01: 1 ... 10 bar (14.5 ... 145 psi) C line: Y21: bar (psi) 1) Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. Siemens FI 01 · 2015 US Edition 1/115 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm 15 (0.6) 53 (2.1) Ø80 (3.15) 1 2 3 5 7 Space for rotation of housing 3 2 Temperature decoupler 4 84 (3.31) 50 (1.97) 1 29 (1.14) 6 H1 = approx. 130 (5.12) 143 (5.6) 74 (2.9) H 2 = approx. 55 (2.17) 15 (0.6) 24 (0.94) ■ Dimensional drawings 50 (1.97) 1 min. 90 (3.54) 2) Electronic side, digital display (longer overall length for cover with window)1) 4 Protective cover over keys 5 Blanking plug Terminal side1) 6 Electrical connection: Screwed gland M20 x 1,5 or screwed gland ½-14 NPT or M12 conector Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 7 Process connection: see flange tables 1) 2) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 92 mm (3.6 inch) for minimum distance to permit rotation with indicator SITRANS P pressure transmitters, DS III series for gauge pressure, with front-flush diaphragm, dimensions in mm (inch) The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H1 and H2. H1 = Height of the SITRANS P300 up to a defined cross-section H2 = Height of the flange up to this defined cross-section Only the height H2 is indicated in the dimensions of the flanges. 1/116 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Flanges as per EN and ASME Sanitary process screw connection to NEUMO Bio-Connect Flange to EN Order DN code H2 Order DN code D M11 M21 M13 M23 M04 M14 M06 M16 25 25 40 40 50 50 80 80 PN D H2 40 100 40 100 16 40 16 40 115 mm (4.5“) 140 mm (5.5“) 150 mm (5.9“) 170 mm (6.7“) 165 mm (6.5“) 165 mm (6.5“) 200 mm (7.9“) 200 mm (7.9“) Approx. 52 mm (2“) H2 EN 1092-1 D Order DN code H2 Order DN code M40 M41 M42 M43 M44 M45 M46 M47 M48 M49 1“ 1½“ 2“ 3“ 4“ 1“ 1½“ 2“ 3“ 4“ H2 ASME B16.5 PN D 150 150 150 150 150 300 300 300 300 300 110 mm (4.3“) Approx. 130 mm (5.1“) 52 mm (2“) 150 mm (5.9“) 190 mm (7.5“) 230 mm (9.1“) 125 mm (4.9“) 155 mm (6.1“) 165 mm (6.5“) 210 mm (8.1“) 255 mm (10.0“) H2 D H2 DIN 11851 (milk pipe union with slotted union nut) H2 N04 N06 50 80 PN D H2 25 25 92 mm (3.6“) 127 mm (5.0“) Approx. 52 mm (2“) D Q23 Q24 Q25 Q26 Q31 Q32 Q33 Q34 50 65 80 100 2“ 2½“ 3“ 4“ Order DN code Connections to DIN Order DN code H2 16 16 16 16 16 16 16 16 82 mm (3.2“) 105 mm (4.1“) 115 mm (4.5“) 145 mm (5.7“) 82 mm (3.2“) 105 mm (4.1“) 105 mm (4.1“) 145 mm (5.7“) Approx. 52 mm (2“) PN D H2 16 16 16 16 16 16 16 16 110 mm (4.3“) 140 mm (5.5“) 150 mm (5.9“) 175 mm (6.9“) 100 mm (3.9“) 110 mm (4.3“) 140 mm (5.5“) 175 mm (6.9“) Approx. 52 mm (2“) Sanitary process connection to NEUMO Bio-Connect clamp connection NuG and pharmaceutical connections D 2 Q39 Q40 Q41 Q42 Q47 Q48 Q49 Q50 50 65 80 100 2“ 2½“ 3“ 4“ PN D 16 10 10 10 16 16 10 10 77.4 mm (3.0“) Approx. 90.9 mm (3.6“) 52 mm (2“) 106 mm (4.2“) 119 mm (4.7“) 77.4 mm (3.0“) 90.9 mm (3.6“) 106 mm (4.2“) 119 mm (4.7“) H2 Sanitary process connection to NEUMO Bio-Connect S flange connection Order DN code Order DN code N14 N15 50 65 PN D H2 16 10 64 mm (2.5“) 91 mm (3.6“) Approx. 52 mm (2“) H2 Tri-Clamp nach DIN 32676 H2 50 65 80 100 2“ 2½“ 3“ 4“ D Sanitary process connection to NEUMO Bio-Connect flange connection Flanges to ASME D Q05 Q06 Q07 Q08 Q13 Q14 Q15 Q16 PN Q72 2“ PN D H2 16 125 mm (4.9“) Approx. 52 mm (2“) D Threaded connection G¾", G1" and G2" acc. to DIN 3852 D D H2 Varivent connection R01 ¾“ 60 37 mm (1.5“) R02 1“ 60 48 mm (1.9“) R04 2“ 60 78 mm (3.1“) Approx. 45 mm (1.8“) Approx. 47 mm (1.9“) Approx. 52 mm (2“) H2 Order DN code PN Other connections Order DN code H2 N28 PN D H2 40 84 mm (3.3“) Approx. 52 mm (2“) D 40 ... 125 D Sanitary process connection to DRD H2 Order DN code M32 50 PN D H2 40 105 mm (4.1“) Approx. 52 mm (2“) D Siemens FI 01 · 2015 US Edition 1/117 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Tank connection TG 52/50 and TG52/150 Aseptic threaded socket to DIN 11864-1 Form A PN D H2 Order DN code PN D H2 Approx. 63 mm (2.5“) Approx. 170 mm (6.7“) N33 N34 N35 N36 50 65 80 100 25 25 25 25 78 x 1/6“ 95 x 1/6“ 110 x ¼“ 130 x ¼“ Approx. 52 mm (2“) 25 40 63 mm (2.5“) R11 25 40 63 mm (2.5“) H2 R10 D H2 Order DN code D SMS socket with union nut M67 M68 M69 PN 2“ 25 2½“ 25 3“ 25 D H2 84 mm (3.3“) 100 mm (3.9“) 114 mm (4.5“) Approx. 52 mm (2“) Aseptic flange with notch to DIN 11864-2 Form A H2 H2 Order DN code D D SMS threaded socket H2 M73 M74 M75 PN 2“ 25 2½“ 25 3“ 25 H2 70 x 1/6 mm 85 x 1/6 mm 98 x 1/6 mm Approx. 52 mm (2“) D D IDF socket with union nut H2 Order DN code M82 M83 M84 PN 2“ 25 2½“ 25 3“ 25 D H2 77 mm (3“) 91 mm (3.6“) 106 mm (4.2“) Approx. 52 mm (2“) H2 M92 M93 M94 2“ 25 2½“ 25 3“ 25 D 1/118 H2 64 mm (2.5“) Approx. 77.5 mm (3.1“) 52 mm (2“) 91 mm (3.6“) D Siemens FI 01 · 2015 US Edition D H2 50 65 80 100 16 16 16 16 94 113 133 159 Approx. 52 mm (2“) N43 N44 N45 N46 Order DN code PN D H2 N43 + 50 P11 N44 + 65 P11 N45 + 80 P11 N46 + 100 P11 16 94 Approx. 52 mm (2“) 16 113 16 133 16 159 Order DN code PN D H2 50 65 80 100 25 25 16 16 77.5 91 106 130 Approx. 52 mm (2“) N53 N54 N55 N56 IDF threaded socket PN PN Aseptic clamp with groove to DIN 11864-3 Form A D Order DN code Order DN code Aseptic flange with groove to DIN 11864-2 Form A D H2 Order DN code H2 1 D