P300 with PMC connection catalog specifications

© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III and P300 with PMC connection - Technical description
■ Overview
■ Benefits
• High quality and service life
• High reliability even under extreme chemical and mechanical
loads, e.g. abrasion.
• For aggressive and non-aggressive gases, vapors and liquids
• Extensive diagnosis and simulation functions
• Minimum conformity error
• Small long-term drift
• Wetted parts made of Hastelloy
• Infinitely adjustable span from 0.03 bar to 16 bar
(0.43 psi to 232 psi) for DS III with HART interface
• Nominal measuring range from 1 bar to 16 bar
(14.5 psi to 232 psi) for DS III with PROFIBUS PA and
FOUNDATION Fieldbus interface
• Infinitely adjustable span from 0.03 bar to 16 bar
(0.43 psi to 232 psi) for SITRANS P300 with HART interface
• Nominal measuring range from 1 bar to 16 bar
(14.5 psi to 232 psi) for SITRANS P300 with PROFIBUS PA interface
• High measuring accuracy
• Parameterization over control keys and HART Communication, or over PROFIBUS PA or FOUNDATION Fieldbus interface (DS III only).
■ Application
The pressure transmitters of the DS III series, can be used in industrial areas with extreme chemical and mechanical loads.
Electromagnetic compatibility in the range 10 kHz to 1 GHz
makes the DS III pressure transmitters suitable for locations with
high electromagnetic emissions.
The SITRANS P300 and DS III pressure transmitters have been
fitted with special process connections for the paper industry.
With the two process connection threads 1½" and 1" flush at the
front, the SITRANS P300 and DS III transmitters can be used for
all processes in the paper industry.
SITRANS P300 and SITRANS PDS III series pressure transmitters are digital pressure transmitters featuring extensive userfriendliness and high accuracy. The parameterization is performed using control keys via HART, PROFIBUS-PA or
FOUNDATION Fieldbus interface.
Extensive functionality enables the pressure transmitter to be
precisely adapted to the plant’s requirements. Operation is very
simple in spite of the numerous setting options.
Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The transmitters are provided with
an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX).
Various versions of the pressure transmitters are available for
measuring:
• Gauge pressure
• Level
• Mass level
• Volume level
Pressure transmitters with type of protection "Intrinsic safety" and
"Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitters are
provided with an EC type examination certificate and comply
with the corresponding harmonized European standards
(ATEX).
Pressure transmitters with the type of protection "Intrinsic safety"
for use in zone 0 may be operated with power supply units of category "ia" and "ib".
The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of
highly viscous substances.
The pressure transmitter can be operated locally over 3 control
keys or programmed externally over HART or over
PROFIBUS-PA or FOUNDATION Fieldbus interface (only DS III).
SITRANS P, DS III series
Measured variable: Gauge pressure of aggressive and non-aggressive gases, vapors and liquids.
Span (infinitely adjustable)
For DS III with HART: 0.03 ... 16 bar (0.433 ... 232 psi)
Nominal measuring range
For DS III with PROFIBUS PA or FOUNDATION Fieldbus:
1 ... 16 bar (14.5 ... 232 psi)
SITRANS P300
Span (infinitely adjustable)
For DS III with HART: 0.03 ... 16 bar (0.433 ... 232 psi)
Nominal measuring range
For DS III with PROFIBUS PA or FOUNDATION Fieldbus:
1 ... 16 bar (14.5 ... 232 psi)
Siemens FI 01 · 2015 US Edition
1/73
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P DS III and P300 with PMC connection - Technical description
Example for an attached measuring point label
■ Design
SITRANS P DS III
Y01 or Y02
= max. 27 char.
Y15 = max. 16 char.
.... to .... mbar
Measuring point number (TAG No.)
1
1234
Y99 = max. 10 char.
Y16 = max. 27 char.
Measuring point text
2
SITRANS P300
The device comprises:
• Electronics
• Housing
• Measuring cell
8
3
1
7
5
6
1
2
3
4
5
6
7
8
Plastic cover as access to
the input keys
Screw cover with viewing pane
Digital display
Locking screw
Process connection
Screw cover with viewing pane
Rating plate
Inlet with cable gland
4
4
5
3
Device front view, SITRANS P DS III
The transmitter consists of various components depending on
the order. The possible versions are listed in the ordering information. The components described below are the same for all
transmitters.
The rating plate (7, Figure "Device front view) with the Article No.
is located on the side of the housing. The specified number together with the ordering information provide details on the optional design details and on the possible measuring range
(physical properties of built-in sensor element).
The approval label is located on the opposite side.
The housing is made of die-cast aluminium or stainless steel precision casting. A round cover is screwed on at the front and rear
of the housing. The front cover (2) can be fitted with a viewing
pane so that the measured values can be read directly on the
display. The inlet (8) for the electrical connection is located either
on the left or right side. The unused opening on the opposite side
is sealed by a blanking plug. The protective earth connection is
located on the rear of the housing.
The electrical connections for the power supply and screen are
accessible by unscrewing the rear cover. The bottom part of the
housing contains the measuring cell with process connection
(5). The measuring cell is prevented from rotating by a locking
screw (4). As the result of this modular design, the measuring
cell and the electronics can be replaced separately from each
other. The set parameter data are retained.
At the top of the housing is a plastic cover (1), which hides the
input keys.
1/74
Siemens FI 01 · 2015 US Edition
1
2
3
4
5
Digital display
Process connection
Cable gland
Rating plate
Screw-on lid
2
Perspective view of the SITRANS P300
The housing has a screw-on lid (5) and, depending on the version, is with or without an inspection window. The electrical terminal housing, the buttons for operation of the device are located under this lid and, depending on the version, the display.
The connections for the auxiliary power UH and the shield are in
the terminal housing. The cable gland is on the side of the housing. The measuring cell with the process connection (2) is located on the bottom of the housing. The measuring cell with the
process connection may differ from the one shown in the diagram, depending on the device version.
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III and P300 with PMC connection - Technical description
■ Function
Operation of electronics with HART communication
Operation of electronics with PROFIBUS PA
communication
9
8
0.0.0.0.0
00
M
9
8
4
5
IA, UH
μC
2
3
4
5
μC
7
7
PA
interface
HART interface
EEPROM
EEPROM
6
6
Electronics
Electronics
6
1
6
Sensor
Power
supply
unit
Coupler
11
12
EEPROM
Sensor
EEPROM
1
Power supply
10
PROFIBUS DP
3
PROFIBUS-PA
2
0.0.0.0.0
00
M
10
BusMaster
pe Measuring cell
pe
1
2
3
4
5
6
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Digital-to-analog converter
One non-volatile memory each in the measuring cell and
electronics
7 HART interface
8 Three input keys (local operation)
9 Digital display
10 Diode circuit and connection for external ammeter
IA Output current
UH Power supply
Pe Input variable
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of electronics") is amplified by the measuring
amplifier (2) and digitized in the analog-to-digital converter (3).
The digital information is evaluated in a microcontroller, its linearity and temperature response corrected, and converted in a digital-to-analog converter (5) into an output current of 4 to 20 mA.
The diode circuit (10) protects against incorrect polarity.
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The one memory is coupled to the measuring cell, the other
to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from
each other.
Using the 3 input keys (8) you can parameterize the pressure
transmitter directly at the measuring point. The input buttons can
also be used to control the view of the results, the error messages and the operating modes on the display (9).
1
2
3
4
5
6
7
Measuring cell
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Electrical isolation
One non-volatile memory
each in the measuring cell
and electronics
PROFIBUS-PA interface
8
9
10
11
12
Three input keys
(local operation)
Digital display
Power supply
DP/PA coupler or link
Bus master
pe
Input variable
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of electronics") is amplified by the measuring
amplifier(2) and digitized in the analog-to-digital converter (3).
The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the
PROFIBUS PA through an electrically isolated PA interface (7).
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The first memory is linked with the measuring cell, the second with the electronics. This modular design means that the
electronics and the measuring cell can be replaced separately
from one another.
Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error
messages and the operating modes on the display (9).
The results with status values and diagnostic values are transferred by cyclic data transmission on the PROFIBUS PA. Parameterization data and error messages are transferred by acyclic
data transmission. Special software such as SIMATIC PDM is required for this.
The HART modem (7) permits parameterization using a protocol
according to the HART specification.
The pressure transmitters with spans  63 bar (914 psi) measure
the input pressure compared to atmosphere, the transmitters
with spans 160 bar (2320 psi) measure compared to vacuum.
Siemens FI 01 · 2015 US Edition
1/75
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III and P300 with PMC connection - Technical description
Operation of electronics with FOUNDATION Fieldbus
communication
Mode of operation of the measuring cell
Measuring cell for gauge pressure with front-flush diaphragm
9
8
0.0.0.0.0
00
2
3
4
5
5
4
7
FF
interface
μC
EEPROM
6
Foundation Fieldbus
M
1
Power supply
10
Power
supply
unit
Coupler
Electronics
1
6
Sensor
pe
Measuring cell
1
2
3
4
5
6
7
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Electrical isolation
One non-volatile memory
each in the measuring cell
and electronics
FF interface
1
2
3
4
5
pe
Measuring cell
Process connection
Seal diaphragm
Filling liquid
Silicon pressure sensor
Pressure as input variable
2
3
pe
Measuring cell for gauge pressure, with front-flush diaphragm for paper
industry, function diagram
EEPROM
1
8
9
10
Three input keys
(local operation)
Digital display
Power supply
pe
Input variable
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of electronics") is amplified by the measuring
amplifier (2) and digitized in the analog-to-digital converter (3).
The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the
FOUNDATION Fieldbus through an electrically isolated
FOUNDATION Fieldbus interface (7).
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The one memory is coupled to the measuring cell, the other
to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from
each other.
Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error
messages and the operating modes on the display (9).
The results with status values and diagnostic values are transferred by cyclic data transmission on the
FOUNDATION Fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as National Instruments Configurator is required for
this.
The pressure pe is applied through the process connection (2,
Figure "Measuring cell for gauge pressure, with front-flush diaphragm for paper industry, function diagram) to the measuring
cell (1). This pressure is subsequently transmitted further
through the seal diaphragm (3) and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then
flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure.
Parameterization
Depending on the version, there are a range of options for parameterizing the pressure transmitter and for setting or scanning
the parameters.
Parameterization using the input buttons (local operation)
With the input buttons you can easily set the most important parameters without any additional equipment.
Parameterization using HART
Parameterization using HART is performed with a HART Communicator or a PC.
+
230 ... 1100 Ω
SITRANS P
transmitter
Power supply
HART
communicator
Communication between a HART Communicator and a pressure transmitter
When parameterizing with the HART Communicator, the connection is made directly to the 2-wire cable.
+
230 ... 500 Ω
SITRANS P
transmitter
HART
modem
Power supply
PC or
laptop
USB/RS 232
HART communication between a PC communicator and a pressure
transmitter
1/76
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III and P300 with PMC connection - Technical description
When parameterizing with a PC, the connection is made through
a HART modem.
The signals needed for communication in conformity with the
HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method.
Adjustable parameter DS III with HART and P300 with HART
Parameterization through PROFIBUS PA interface
Fully digital communication through PROFIBUS PA, profile 3.0, is
particularly user-friendly. The PROFIBUS connects the DS III PA
to a process control system, e.g. SIMATIC PSC 7. Communication is possible even in a potentially explosive environment.
For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager).
Parameters
Input keys
HART
communication
Start of scale
x
x
Full-scale value
x
x
Electrical damping
x
x
Start-of-scale value without application of a pressure ("Blind setting")
x
x
Fully digital communication through FOUNDATION Fieldbus is
particularly user-friendly. Through the FOUNDATION Fieldbus
the DS III with FOUNDATION Fieldbus is connected to a process
control system. Communication is possible even in a potentially
explosive environment.
Full-scale value without application
of a pressure ("Blind setting")
x
x
For parameterization through the FOUNDATION Fieldbus you
need suitable software, e.g. National Instruments Configurator.
Zero adjustment
x
x
current transmitter
x
x
Fault current
x
x
Parameterization through FOUNDATION Fieldbus interface
Adjustable parameters for DS III with PROFIBUS PA and
FOUNDATION Fieldbus, and P300 with PROFIBUS PA and
FOUNDATION Fieldbus
Adjustable parameters
Input keys
PROFIBUS PA
and FOUNDATION Fieldbus
interface
x
Electrical damping
x
x
Input of characteristic
x
Zero adjustment (correction of position)
x
x
Freely-programmable LCD
x
Buttons and/or function disabling
x
x
Diagnostic functions
x
Source of measured-value display
x
x
Physical dimension of display
x
x
Position of decimal point
x
x
Bus address
x
x
Adjustment of characteristic
x
x
Disabling of buttons, write protection x
x1)
Type of dimension and actual dimen- x
sion
x
x
Characteristic (linear)
1)
Cancel apart from write protection
Diagnostic functions for DS III with HART and P300 with HART
• Zero correction display
• Event counter
• Limit transmitter
• Saturation alarm
• Slave pointer
• Simulation functions
• Maintenance timer
Available physical units of display for DS III with HART and
P300 with HART
Input of characteristic
x
Freely-programmable LCD
x
Diagnostic functions
x
Diagnostic functions for DS III with PROFIBUS PA and
FOUNDATION Fieldbus, and P300 with PROFIBUS PA and
FOUNDATION Fieldbus
•
•
•
•
•
•
•
Event counter
Slave pointer
Maintenance timer
Simulation functions
Display of zero correction
Limit transmitter
Saturation alarm
Physical variable
Physical dimensions
Pressure (setting can also be
made in the factory)
Pa, MPa, kPa, bar, mbar, torr, atm,
psi, g/cm2, kg/cm2, inH2O, inH2O
(4 °C), mmH2O, ftH2O (20 °C),
inHg, mmHg
Level (height data)
m, cm, mm, ft, in
Volume
m3, dm3, hl, yd3, ft3, in3, US gallon,
lmp. gallon, bushel, barrel, barrel
liquid
Mass
g, kg, t, lb, Ston, Lton, oz
Physical variable
Physical dimensions
Temperature
K, °C, °F, °R
Miscellaneous
%, mA
Pressure (setting can also be
made in the factory)
MPa, hPa, kPa, Pa, bar, mbar, torr,
atm, psi, g/cm2, kg/cm2, mmH2O,
mmH2O (4 °C), inH2O, inH20 (
4 °C), ftH2O, mmHg, inHg
Physical dimensions available for the display
Level (height data)
m, cm, mm, ft, in, yd
Mass
g, kg, t, lb, Ston, Lton, oz
Volume
m3, dm3, hl, yd3, ft3, in3, US gallon,
lmp. gallon, bushel, barrel, barrel
liquid
Temperature
K, °C, °F, °R
Miscellaneous
%
Siemens FI 01 · 2015 US Edition
1/77
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P DS III with PMC connection
■ Technical specifications
SITRANS P, DS III series for gauge pressure with PMC connection for the paper industry
HART
PROFIBUS PA and FOUNDATION Fieldbus
Input
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure
Gauge pressure
Span (min. ... max.)
Max. perm. test
pressure
Nominal measuring
range
Max. perm. test
pressure
0.01 ... 1 bar
(0.15 ... 14.5 psi)
6 bar
(87 psi)
1 bar
(14.5 psi)
6 bar
(87 psi)
0.04 ... 4 bar
(0.58 ... 58 psi)
10 bar
(145 psi)
4 bar
(58 psi)
10 bar
(145 psi)
0.16 ... 16 bar
(2.32 ... 232 psi)
32 bar
(464 psi)
16 bar
(232 psi)
32 bar
(464 psi)
Lower measuring limit
• Measuring cell with silicone oil filling
100 mbar a(1.45 psia)
Upper measuring limit
100% of max. span
Output
Output signal
4 ... 20 mA
Digital PROFIBUS PA and
FOUNDATION Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or optionally
set to 22.0 mA
-
• Without HART communication
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
-
• With HART communication
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
-
Physical bus
-
IEC 61158-2
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the other with max.
supply voltage.
Load
Electrical damping T63 (step width 0.1 s)
Set to 2 s (0 ... 100 s)
Measuring accuracy
Acc. to IEC 60770-1
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm,
silicone oil filling, room temperature 25 °C (77 °F)
Reference conditions
(All error data refer always refer to the set span)
Span ratio r = max. span/set span
Nominal measuring range ratio r = nominal
measuring range/set measuring range
Error in measurement at limit setting incl.
hysteresis and reproducibility
• Linear characteristic
- r  10
 (0.0029  r + 0.071) %
 (0.0029  r + 0.071) %
- 10 < r  30
 (0.0045  r + 0.071) %
 (0.0045  r + 0.071) %
- 30 < r  100
 (0.005  r + 0.05) %
 (0.005  r + 0.05) %
1- to 4-bar measuring cell
 (0.25  r) % per 5 years
 (0.25  r) % per 5 years
16-bar measuring cell
 (0.125  r) % per 5 years
 (0.125  r) % per 5 years
• at -10 ... +60 °C (14 ... 140 °F)
 (0.08  r + 0.1 ) %1)
 (0.08  r + 0.1 ) %1)
• at -40 ... -10 °C and +60 ... +85 °C
(-40 ... +14 °F and 140 ... 185 °F)
 (0.1  r + 0.15) %/10 K
 (0.1  r + 0.15) %/10 K
Long-term stability (temperature change 30 °C
(54 °F))
Influence of ambient temperature
Influence of the medium temperature (only with
front-flush diaphragm)
• Temperature difference between medium
temperature and ambient temperature
3 mbar/10 K (1.2 inH2O/10 K)
 0.1 mbar (0.04 inH2O g) per 10° inclination
Influence of mounting position
Measured Value Resolution
1/78
Siemens FI 01 · 2015 US Edition
-
3  10-5 of nominal measuring range
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III with PMC connection
SITRANS P, DS III series for gauge pressure with PMC connection for the paper industry
HART
PROFIBUS PA and FOUNDATION Fieldbus
Rated conditions
Degree of protection to IEC 60529
IP66 (optional IP66/IP68), NEMA 4X
Temperature of medium
-40 ... +100 °C (-40 ... +212 °F)
Ambient conditions
• Ambient temperature
-20 ... +85 °C (-4 ... +185 °F)
-40 ... +85 °C (-40 ... +185 °F)
- Transmitter
(with 4-wire connection, observe temperature
values of supplementary 4-wire electronics)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics
• Electromagnetic Compatibility
- Emitted interference and interference immunity
Acc. to IEC 61326 and NAMUR NE 21
Design
 1.5 kg ( 3.3 lb)
Weight (without options)
Enclosure material
Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408
Wetted parts materials
• Gasket (standard)
PTFE flat gasket
FPM (Viton) or optionally: FFPM or NBR
• O-ring (minibolt)
Measuring cell filling
Silicone oil or inert filling liquid
Process connection (standard)
Flush-mounted, 1½", PMC Standard design
Process connection (minibolt)
Flush-mounted, 1", minibolt design
Supplied through bus
Power supply UH
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
-
Separate 24 V power supply necessary
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
Bus voltage
Current consumption
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Certificates and approvals
Classification according to PED 97/23/EC
1)
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3,
paragraph 3 (sound engineering practice)
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) %/28 °C (50 °F).
Siemens FI 01 · 2015 US Edition
1/79
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P DS III with PMC connection
.
HART communication
HART communication
230 ... 1100 
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local operation (standard setting
address 126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input /Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Register (totalizer)
Can be reset, preset, optional
direction of counting, simulation
function of register output
• Analog input
- Failure mode
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
1/80
Siemens FI 01 · 2015 US Edition
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III with PMC connection
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS P pressure transmitters for gauge
pressure, with PMC connection
series DS III with HART
7MF 4 1 3 3 77777 - 7777
SITRANS P pressure transmitter for gauge
pressure, with PMC connection
DS III with PROFIBUS PA (PA)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Inert liquid
Measuring cellcleaning
normal
grease-free to
cleanliness level 2
Measuring span (min. ... max.)
0.01 ... 1 bar1)
(0.15 ... 14.5 psi)1)
0.04 ... 4 bar
(0.58 ... 58 psi)
0.1.6 ... 16 bar
(2.32 ... 232 psi)
DS III with FOUNDATION Fieldbus (FF)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
1
3
Silicone oil
Inert liquid
B
C
D
Nominal measuring range
1 bar1)
(14.5 psi)1)
4 bar
(58 psi)
16 bar
(232 psi)
Wetted parts materials
Seal diaphragm
Connection shank
Hastelloy
Stainless steel
Process connection
• PMC Style Standard: Thread 1½"
• PMC Style Minibolt: front-flush 1" (not with minimum span: 500 mbar (7.25 psi) - version "B")
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting
Measuring cell cleaning
normal
grease-free to
cleanliness level 2
Article No.
7MF 4 1 3 4 7MF 4 1 3 5 77777 - 7777
1
3
B
C
D
Wetted parts materials
Seal diaphragm
Connection shank
B
Hastelloy
2
3
0
3
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)" 2)
- „Ex nA/ic (Zone 2)“3)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)4)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"3)
Electrical connection / cable entry
• Female thread M20 x 1.5
• Female thread ½-14 NPT
• M12 connectors (stainless steel)5) 6)
Display
• Without display
• Without visible display (display concealed,
setting: mA)
• With visible display (setting: mA)
• With customer-specific display (setting as specified, Order code "Y21" required)
Stainless steel
Process connection2)
• PMC Style Standard: Thread 1½"
• PMC Style Minibolt: front-flush 1" (minimum
span: 500 mbar (7.25 psi), not available with
1-bar-measuring cell (Option B))
B
2
3
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting
1
2
0
3
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
A
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)" 3)
- „Ex nA/ic (Zone 2)“4)
• FM + CSA intrinsic safe (is)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"3)
B
D
E
F
S
NC
B
C
F
0
1
Electrical connection / cable entry
• Female thread M20 x 1.5
• Female thread ½-14 NPT
• M12 connectors (stainless steel)5) 6)
Power supply units see Chap. 7 "Supplementary Components".
Display
• Without display
• Without visible display (display concealed,
setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting as specified, Order code "Y21" required)
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• sealing ring
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• sealing ring
6
7
1)
Only with "PMC Style Standard" process connection
1)
2)
Only with "PMC Style Standard"process connection
Without cable gland, with blanking plug
2)
3)
Sealing is included in delivery.
Configurations with M12 connectors are only available in Ex ic.
3)
4)
Without cable gland, with blanking plug
Only in connection with IP65.
4)
5)
Configurations with M12 connectors are only available in Ex ic.
Only in connection with Ex approval A, B, E or F.
5)
6)
Only in connection with Ex approval A, B, E or F.
M12 delivered without cable socket
6)
M12 delivered without cable socket
Siemens FI 01 · 2015 US Edition
1
2
A
B
D
E
F
NC
B
C
F
0
1
6
7
1/81
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P DS III with PMC connection
Selection and Ordering data
Order code
Further designs
Selection and Ordering data
HART PA
FF
Add "-Z" to Article No. and specify Order
code.
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text (max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
Y01

1)
Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Y15



Measuring point text (entry in device variable)
Max. 27 characters, specify in plain text:
Y16: ...........................................
Y16




Entry of HART address (TAG)
Max. 8 characters, specify in plain text:
Y17: ...........................................
Y17









C14



C20

Setting of pressure indication in pressure Y21
units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C
"Functional safety (SIL2/3)" certificate acc. C23
to IEC 61508


Device passport Russia
(For price request please contact the technical
C99



Output signal can be set to upper limit of
22.0mA
D05



Setting of pressure indication in nonY22 +
pressure units2)
Y01
Specify in plain text:
Y22: ..... up to ..... l, m3, m, USg, ...
(specification of measuring range in pressure
units "Y01" is essential, unit with max. 5 characters)


Degree of protection IP66/IP68
(only for M20 x 1.5 and ½-14 NPT)
D12



Export approval Korea
E11



Explosion-proof "Intrinsic safety" to
NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
E551)



Explosion protection "Explosion-proof"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)
E561)



Ex protection "Zone 2" to NEPSI (China)
(only for transmitter 7MF4...-.....-.E..)
E571)



Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E581)
to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)



Plug
• Angled
• Han 8D (metal, gray)
A32
A33


M12 cable sockets (metal (CuZn))
A50



• English
• French
• Spanish
• Italian
• Cyrillic (russian)
B11
B12
B13
B14
B16















English rating plate
Pressure units in inH20 and/or psi
B21


Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11

Inspection certificate
Acc. to EN 10204-3.1
C12
Factory certificate
Acc. to EN 10204-2.2
"Functional safety (SIL2)" certificate acc.
to IEC 61508
Rating plate inscription
(instead of German)
support
www.siemens.com/automation/support-request)
Mounting
• Weldable sockets for standard 1½"
threaded connection
• Weldable socket for minibolt connection 1"
(incl. screw 5/16-18 UNC-2B and washer)
1)
P01



P02



Option does not include ATEX approval, but instead includes only the country-specific approval.
1/82
Siemens FI 01 · 2015 US Edition
Preset bus address
possible between 1 and 126
Max. 8 characters, specify in plain text:
Y25: ...........
Y25
Only "Y01" and "Y21" can be factory preset
 = available
Ordering example
Item line:
7MF4133-1DB20-1AB7-Z
B line:
C11 + Y01 + Y21
C line:
Y01: 1 ... 10 bar (14.5 ... 145 psi)
C line:
Y21: bar (psi)
1)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
2)
Preset values can only be changed over SIMATIC PDM.
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P DS III with PMC connection
143 (5.6)
74 (2.9)
53 (2.1)
4
84 (3.31)
Ø80 (3.15)
50 (1.97)
1
29 (1.14)
5
3
6
2
7
H2
Space for rotation
of housing
min. 90 (3.54) 2)
H1 = approx. 130 (5.12)
15
(0.6)
24
(0.94)
■ Dimensional drawings
Electronic side, digital display
(longer overall length for cover with window)1)
4
Protective cover over keys
5
Blanking plug
2
Terminal side1)
6
3
Electrical connection:
Screwed gland M20 x 1,5 or screwed gland ½-14 NPT or
M12 conector
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
7
Process connection: PMC standard
1
1)
2)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
92 mm (3.6 inch) for minimum distance to permit rotation with indicator
SITRANS P DS III pressure transmitters for gauge pressure, with PMC connection, dimensions in mm (inch)
The diagram shows a SITRANS P DS III with an example of a
flange. In this drawing the height is subdivided into H1 and H2.
PMC Style standard
DN
H2 = Height of the flange up to this defined cross-section
PN
D
H2
40.9 mm (1.6")
approx.
36.8 mm
(1.4")
D
H2
26.3 mm (1.0")
approx.
33.1 mm
(1.3")
H2
H1 = Height of the SITRANS P DS III up to a defined cross-section
Only the height H2 is indicated in the dimensions of the flanges.
D
1)
PMC Style minibolt
DN
PN
H2
Ø 8 (0.3)
20,9
(0.82)
Ø 36,6 (1.44)
Ø 58,9 (2.32)
17,8 (0.7)
25,4 (1)
Ø 33,4 (1.31)
Ø 26,7 (1.05)
M44 x 1,25
D
1) O-ring surface
(bore hole Ø 8 mm (0.3“) without burr)
PMC Style Standard (left) and PMC Style Minibolt (right) weldable
sockets, dimensions in mm (inch)
Material: Stainless steel, Mat. No. 1.4404/316L
Siemens FI 01 · 2015 US Edition
1/83
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P300 with PMC connection
■ Technical specifications
SITRANS P300 for gauge pressure with PMC connection for the paper industry
HART
PROFIBUS PA and FOUNDATION Fieldbus
Input
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. pemissible test pressure
Gauge pressure (front-flush)
Span (min. ... max.)
Max. perm. test
pressure
Nominal measuring
range
Max. perm. test
pressure
0.01 ... 1 bar
(0.15 ... 14.5 psi)
6 bar
(87 psi)
1 bar
(14.5 psi)
6 bar
(87 psi)
0.04 ... 4 bar
(0.58 ... 58 psi)
10 bar
(145 psi)
4 bar
(58 psi)
10 bar
(145 psi)
0.16 ... 16 bar
(2.3 ... 232 psi)
32 bar
(464 psi)
16 bar
(232 psi)
32 bar
(464 psi)
Depending on the process connection, the span Depending on the process connection, the nomimay differ from these values
nal measuring range may differ from these values
Lower measuring limit
• Measuring cell with silicone oil
100 mbar a (1.45 psia)
Upper measuring limit
• Measuring cell with silicone oil
100 % of max. span
100 % of the max. nominal measuring range
Output signal
4 ... 20 mA
Digital PROFIBUS PA signal
Physical bus
-
IEC 61158-2
Output
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the other with
max. supply voltage.
Electrical damping (step width 0.1 s)
Set to 2 s (0 ... 100 s)
Acc. to IEC 60770-1
Measuring accuracy
Reference conditions (All error data always refer
to the set span)
RIncreasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm,
measuring cell with silicone oil, room temperature 25 °C (77 °F)
Span ratio r = max. span/set span
Nominal measuring range ratio r = nominal
measuring range/set measuring range
Error in measurement at limit setting incl. hysteresis and reproducibility
Linear characteristic
• r + 10
 (0.0029  r + 0.071) %
 (0.0029  r + 0.071) %
• 10 < r  30
 (0.0045  r + 0.071) %
 (0.0045  r + 0.071) %
• 30 < r  100
 (0.005  r + 0.05) %
Long-term stability at  30 °C ( 54 °F)
 (0.005  r + 0.05) %
approx. 2 s
Step response time T63
 (0.25  r) %/5 years
 (0.25  r) %/5 years
• at -10 ... +60 °C (14 ... 140 °F)
 (0.1  r + 0.2) %1)
 (0.1  r + 0.2) %1)
• at -40 ... -10 °C and 60 ... 85 °C
(-40 ... 14 °F and 140 ... 185 °F)
 (0.1  r + 0.15) %/10 K
 (0.1  r + 0.15) %/10 K
Influence of ambient temperature
Influence of the medium temperature (only with
front-flush diaphragm)
• Temperature difference between medium temperature and ambient temperature
3 mbar/10 K (1.2 inH2O/10 K)
Rated conditions
Installation conditions
Ambient temperature
Observe the temperature class in areas subject to explosion hazard.
• Measuring cell with silicone oil
-40 ... +85 °C (-40 ... +185 °F)
• Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
Climatic class
Condensation
Degree of protection acc. to EN 60529
Relative humidity 0 ... 100 %. Condensation permissible, suitable for use in the tropics
IP65, IP68, NEMA 4X, enclosure cleaning, resistant to lyes, steam to 150 °C (302 °F)
Electromagnetic Compatibility
• Emitted interference and interference immunity
1/84
Siemens FI 01 · 2015 US Edition
Acc. to IEC 61326 and NAMUR NE 21
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P300 with PMC connection
SITRANS P300 for gauge pressure with PMC connection for the paper industry
HART
PROFIBUS PA and FOUNDATION Fieldbus
Medium conditions
Temperature of medium
• Measuring cell with silicone oil
-40 ... +100 °C (-40 ... +212 °F)
Design
Weight (without options)
Approx. 1 kg (2.2 lb)
Stainless steel, mat. no. 1.4301/304
Enclosure material
Material of parts in contact with the medium
• Seal diaphragm
Hastelloy C276, mat. no. 2.4819
• Measuring cell filling
Silicone oil
Ra-values  0.8 µm (32 µ inch)/welds Ra  1.6 µm (64 µ inch)
Surface quality touched-by-media
Power supply UH
Terminal voltage on transmitter
10.5 ... 42 V DC
for intrinsically safe operation: 10.5 ... 30 V DC
Supplied through bus
Separate power supply
-
Not necessary
• Without Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
Bus voltage
Current consumption
• Max. basic current
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. fault current in the event of a fault
-
15.5 mA
Fault disconnection electronics (FDE)
-
Available
Certificates and approvals
Classification according to PED 97/23/EC
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3,
paragraph 3 (sound engineering practice)
Explosion protection
Intrinsic safety "i"
PTB 05 ATEX 2048
Marking
Ex II 1/2 G Ex ia/ib IIB/IIC T4, T5, T6
Permissible ambient temperature
• Temperature class T4
-40 ... +85 °C (-40 ... +185 °F)
• Temperature class T5
-40 ... +70 °C (-40 ... +158 °F)
-40 ... +60 °C (-40 ... +140 °F)
• Temperature class T6
Connection
To certified intrinsically-safe circuits with peak
values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
To certified intrinsically-safe circuits with peak
values:
FISCO supply unit:
Ui = 17.5 V, Ii = 380 mA,
Pi = 5.32 W
Linear barrier:
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W
Effective inner capacitance:
Ci = 6 nF
Ci = 1.1 nF
Effective internal inductance:
Li = 0.4 mH
Li  7 H
Explosion protection to FM for USA and Canada
(cFMUS)
• Identification (DIP) or (IS); (NI)
• Identification (DIP) or (IS)
1)
Certificate of Compliance 3025099
CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6;
CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III
Certificate of Compliance 3025099C
CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC 4 ... T6; CL I, DIV 2,
GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.08 . r + 0.16) % / 28 °C (50 °F).
Siemens FI 01 · 2015 US Edition
1/85
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P300 with PMC connection
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool
Local operation
(standard setting Address 126)
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customerspecific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
Cyclic data usage
• Output byte
One measured value: 5 bytes
Two measured values: 10 bytes
- Limit monitoring
• Input byte
Register operating mode:
1 bytes
Reset function due to metering.
1 bytes
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
Function blocks
PROFIBUS PA Profile for Process Control Devices
Version 3.0, class B
2
• PID
Standard FOUNDATION Fieldbus function block
• Physical block
1 resource block
Transducer blocks
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Analog input
• Pressure transducer block
- Adaptation to customer-specific process variables
Linearly rising or falling characteristic
0 ... 100 s adjustable
- Can be calibrated by applying
two pressures
Yes
- Electrical damping
- Simulation function
Input /Output
- Monitoring of sensor limits
Yes
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
Constant value or over parameterizable ramp function
• Register (totalizer)
Can be reset and preset
Optional direction of counting
Simulation function of the register output
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 31 nodes
- Characteristic curve
Linear
- Simulation function
Available
• Transducer block "Electronic
temperature"
Simulation function
1/86
Available
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P300 with PMC connection
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS P300 pressure transmitters with PMC
connection, single-chamber measuring housing,
rating plate inscription in English
Article No.
SITRANS P300 pressure transmitters with PMC
connection, single-chamber measuring housing,
rating plate inscription in English
with 4 ... 20 mA / HART
7MF 8 1 2 3 -
with 4 ... 20 mA / HART
7MF 8 1 2 3 -
with PROFIBUS PA
7MF 8 1 2 4 -
with PROFIBUS PA
7MF 8 1 2 4 -
with FOUNDATION Fieldbus (FF)
7MF 8 1 2 5 -
with FOUNDATION Fieldbus (FF)
7MF 8 1 2 5 -
77777 - 7777
Display
• Without display, with keys, closed lid
• With display and keys, closed lid 6)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Inert liquid
Measuring span
1 bar1)
4 bar
16 bar
Measuring cell cleaning
normal
Cleanliness level 2 to
DIN 25410
(14.5 psi)
(58 psi)
(232 psi)
1
3
B
C
D
Wetted parts materials
Seal diaphragm
Measuring cell
Hastelloy
Stainless steel
Process connection
• PMC Style Standard: Thread 1½"
• PMC Style Minibolt: front-flush 1" (minimum span:
500 mbar (7.25 psi), not available with
1-bar-measuring cell (Option B))
Non-wetted parts materials
• Stainless steel, deep-drawn and electrolytically
polished
Version
• Standard versions
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
• Zone 20/21/222)
• Ex nA/nL (Zone 2)3)
• With FM + CSA, Type of protection:
- "Intrinsic Safe (is)" (planned)
Electrical connection/cable entry
• Screwed gland M20 x .5 (polyamide)4)
• Screwed gland M20 x 1.5 (metal)
• Screwed gland M20 x 1.5 (stainless steel)
• M12 connectors (without cable socket)
• M12 connectors (stainless steel), without cable
socket)
• ½-14 NPT metal thread5)
• ½-14 NPT stainless steel thread5)
B
2
3
1
2
• With display and keys, lid with Makrolon pane
(setting on HART devices: mA, with PROFIBUS PA
and FOUNDATION Fieldbus equipment: pressure
units)6)
4
• With display and keys (setting acc. to specifications, Order code "Y21" or "Y22" required), lid with
Makrolon pane6)
• With display and keys, lid with glass pane (setting
on HART devices: mA, with PROFIBUS PA and
FOUNDATION Fieldbus equipment: pressure
unit)6)
• With display (setting acc. to specifications, Order
code "Y21" or "Y22" required), lid with glass
panel6)
5
6
7
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• sealing ring
4
1
A
B
C
E
1)
Only with "Standard" process connection"
2)
Not in conjunction with electrical connection option A.
3)
Only available together with electrical connection options B, C or G.
4)
Only together with HART electronics.
5)
Without cable gland.
6)
Display cannot be turned.
M
A
B
C
F
G
H
J
Siemens FI 01 · 2015 US Edition
1/87
1
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
1
SITRANS P300 with PMC connection
Selection and Ordering data
Order code
Further designs
Selection and Ordering data
HART PA
FF
Add "-Z" to Article No. and
specify Order code.
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text (max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
Y01

1)
Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Y15




Measuring point text (entry in device variable)
Max. 27 char., specify in plain text: Y16: ......
Y16





Entry of HART address (TAG)
Y17




Y21



C14



Set output signal to upper limit of 22.0mA
D05



Degree of protection IP65/IP68
(only for M20x1.5 and ½-14 NPT)
D12



P01



P02





Cable socket for M12 plug
• Stainless steel
A51
Rating plate inscription
(instead of English)
• German
• French
• Spanish
• Italian
B10
B12
B13
B14
English rating plate
Pressure units in inH20 and/or psi














B21


Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11

Inspection certificate
Acc. to EN 10204-3.1
C12
Factory certificate
Acc. to EN 10204-2.2
Mounting
• Weldable sockets for standard 1½"
threaded connection
• Weldable socket for minibolt connection 1"
(incl. screw 5/16-18 UNC-2B and washer)
Max. 8 char., specify in plain text: Y17: .........
Setting of pressure indication in
pressure units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note: The following pressure units can
be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C
Setting of pressure indication in non-pres- Y22 +
sure units2)
Y01
Specify in plain text:
Y22: ..... up to ..... l, m3, m, USg, ...
(specification of measuring range in pressure
units "Y01" is essential, unit with max. 5 characters)
Preset bus address
possible between 1 and 126
Specify in plain text: Y25: .....................
Y25

Only "Y01" and "Y21" can be factory preset
 = available
1/88
Siemens FI 01 · 2015 US Edition
1)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
2)
Preset values can only be changed over SIMATIC PDM.
© Siemens AG 2015
Pressure Measurement
Transmitters for gauge pressure for the paper industry
SITRANS P300 with PMC connection
■ Dimensional drawings
Ø 91 (3.58)
H 2 = approx. 36,8 (1.4)
26,5 (1.0
4)
H1 = approx. 120 (4.72)
69 (2.72)
26 (1.02)
66 (2.6)
82
°
SITRANS P300 pressure transmitters for gauge pressure, with PMC connection, dimensions in mm (inch)
The diagram shows a SITRANS P300 with an example of a
flange. In this drawing the height is subdivided into H1 and H2.
PMC Style Standard
DN
H1 = Height of the SITRANS P300 up to a defined cross-section
Only the height H2 is indicated in the dimensions of the flanges.
17,8 (0.7)
25,4 (1)
Ø 8 (0.3)
20,9
(0.82)
Ø 36,6 (1.44)
Ø 58,9 (2.32)
H2
D
Ø 33,4 (1.31)
Ø 26,7 (1.05)
M44 x 1,25
D
40.4 mm (1.6“) Approx.
36.8 mm
(1.4’’)
H2
H2 = Height of the flange up to this defined cross-section
PN
PMC Style Mini bolt
DN
PN
D
H2
26.3 mm (1.0“) Approx.
33.1 mm
(1.3’’)
H2
1)
D
1) O-ring surface
(bore hole Ø 8 mm (0.3“) without burr)
PMC Style Standard (left) and PMC Style Minibolt (right) weldable sockets, dimensions in mm (inch)
Material: Stainless steel, mat. No. 1.4404 / 316L
Siemens FI 01 · 2015 US Edition
1/89