Data Sheet • Mann Series
M i c r o m a n n U n i ve r s a l , A u x i l i a r y Powe r e d , I s o l a t e d ,
Signal Conditioners with Alarms
U C VA R C u r re n t / Vo l t a g e
U RTA R R e s i s t i v e Te m p e r a t u re D e t e c t o r
UTCAR Thermocouple
U H Z A R F re q u e n c y
C L C A R N o n - l i n e a r C u r re n t / Vo l t a g e
CNDAR Conductivity sensor
Inputs
Inputs
Inputs
Inputs
Inputs
Inputs
Micromann universal transmitters
convert, filter, monitor, display and isolate
measurement signals with a high degree
of accuracy. Each model covers a range of
similar signal and sensor types
• Programmable current/voltage output
• Two versatile alarm channels with LED
status indication
• Display in Engineering units
• Complete isolation
• AC or DC powered
• Removable, screw-type, terminal blocks
• Compact metal housing
% \
Australia
Weidmüller Pty Ltd.
43 Huntingwood Drive, Huntingwood
NSW 2148
Phone +61 (0) 2 9671 9999
Fax
+61 (0) 2 9671 9900
[email protected]
www.mannseries.com
United Kingdom
Other countries
Weidmüller Ltd.
1 Abbey Wood Road, Kings Hill
West Malling, Kent ME19 4YT
Phone +44 1732-877032
Fax
+44 1732-873873
[email protected]
www.weidmueller.com
Weidmüller Interface GmbH & Co.
Postfach 3030
32720 Detmold
Phone +495231-14-0
Fax
+495231-14-2083
[email protected]
www.weidmueller.com
Universal, Signal Conditioners with Alarms
Description
The Micromann series are fully isolated,
microprocessor based, signal transmitters
for use with process measurement signals
and sensors. They also have two alarm
channels.
You can program all features of Micromann
operation through the front panel keypad.
When the set-up is complete, you simply
remove the security link to protect the
setup.
The analogue output calibration is simple
and sets up both current and voltage
outputs. So, you can use any current or
voltage output range without recalibration.
You can tailor each alarm’s operation
individually during setup. If necessary, you
can also allow setpoint adjustment (from the
front panel) during normal operation.
The Micromann can be ordered with one
SPDT contact alarm instead of the standard
normally open relay contacts.
Alarm operation can be set to ‘manual reset’
so that active alarms will remain tripped until
manually cleared.
RIGHT HAND SIDE VIEW
97 mm
General Technical Data
Display
Type
Full 4 digit, red 7mm LED
Scaling
to display in % or engineering units
TOP VIEW
Display range
-999 to 9999
Status indicators
Trip1 /Trip 2 / Processor status
46 mm
Analogue output
Type
Programmable current/voltage
Current range
Inside the range 0.00-22.00 mA
Voltage range
Inside the range 0.00-11.00 V
Recommended minimum span
2mA or 1V
Current drive
up to 900Ω load
Effective depth :
120mm (Top Hat 35mm +/- 0.3, DIN 46277-3, EN 50022)
125mm (G - Rail 32mm +/- 0.3, DIN 46277-1, EN 50035)
To surface (including rail/mounting plate)
Voltage drive
True voltage source (up to 20mA)
Performance
Output action
Direct or reverse acting
Linearity
Output ripple
less than 20mV P/P (voltage)
less than 40μA P/P (current)
Accuracy
Better than ±0.1% typical
Repeatability
±0.05% of span
Temperature drift
Less than 0.02% span per °C
Alarm ouputs
Type
Two normally open relay contact outputs
with common − return and in-built suppression caps
Rating
3A at 250Vac/30Vdc
Setpoints
Any value within 25% of the display range
Better than ±0.1% typical
Long term drift
0.1% per 10,000 hours
Reponse time
320ms for 10-90% output change
Input step response
Programmable (from 250mS to 32s)
Sampling rate
5 samples per second
Setup retention
100 years minimum
Deadband
From 1 display count
Alarm action
High alarm or Low alarm
Output sense
Normally de-energised or energised
NT
No analogue output
Alarm reset
Automatic or manual
DT
Single SPDT alarm output
Alarm timer delay
From 0 to 4200 seconds
FC
Factory configuration - specify values for
all settings
Type
AC or DC powered
FPS
Custom transducer power supply
AC
110Vac (100-132Vac) at 47-63Hz or
240Vac (200-264Vac) at 47-63Hz
DC
12 to 50Vdc (other voltages on request)
Power Usage
AC 6VA or 6W at 24Vdc
Options
Power Supply
Insulation Co-ordination
Connections
Terminal
Ports
Input / Output / Case
Rated Insulation Voltage
300Veff
Overvoltage Category
III
Impulse Withstand
4kV (1.2 / 50)
Isolation
2 kV (between ports)
Signal
1
2
3
See individual models
Input signals
Link to change the set-up
Security Link
4
5
Environmental Conditions
6
Operating temperature
0 to 60 °C
Storage temperature
–25 to +70 °C
Pollution Degree
2
Relative humidity
10–90% (non–condensing)
7
8
Housing
9
Neutral (−)
10
Live (+)
Power supply
Type
Dual DIN rail mount, Aluminium Enclosure
11
Channel one
Weight
0.5kg
12
Channel two
Connection type
Plug in terminals with screw connections
13
Common
Approvals
Standard
14
Output (+)
CAN/CSA C22.2 No. 1010.1:92
UL61010-1: 2004
15
Current (−)
16
Voltage (−)
EN50178:1998
BS EN 61326:1998 + A2
Case
Earthing is via a stud on lower side of case
Micromann
Series
Page 2
Mark
\
E256486
%
LV Directive
EMC
Alarm outputs
Analogue outputs
Subject to technical alterations without notice • Printed in Australia • 7940015645 • 04/03/2008
Universal, Signal Conditioners with Alarms
%
%
%
\
\
\
UCVAR Current/Voltage
• Convert, filter and Isolate
current and voltage signals
• Power for active input devices
• Linearises square law signals
• Bipolar inputs
UTCAR Temperature (T/C)
• Select J, K, N, T, E, B, S, R or
mV inputs
• Temperature Display in °C/°F
• Burn-out alarm
• CJC Temperature display
URTAR Temperature (RTD)
• Accepts 2-wire and 3-wire
PT100 RTD inputs
• Temperature Display in °C/°F
• Automatic lead length
compensation
Technical Data
Inputs
Input Type
Analogue current/voltage signals
Standard range limits
–55.00mA to +55.00mA or
–55.00V to +55.00V
(without recalibration)
Input impedance
22Ω (current inputs)
1MΩ (voltage inputs)
Resolution
1μA/1mV per bit for small ranges
Minimum recommended span
1mA or 1V
Linearisation
Linear or square root
Transducer supply
24Vdc (to 25mA) output
Maximum input impedance
Thermocouple (type J, K, N, T, E, B, S, R)
or millivolt signals
2-wire or 3-wire, Pt100 RTD
(to BS1904:1984/IEC751:1983)
Display Limits
Display Limits
Input
Type
Upper
J
Resolution
Upper
Lower
870°C (1598°F)
700°C
-200°C
K
1372°C (2502°F)
1292°F
-328°F
1°F
N
1300°C (2372°F)
200.0°C
-99.9°C
0.1°C
400.0°F
-99.9°F
0.1°F
T
400°C (752°F)
E
700°C (1292°F)
B
1800°C (3272°F)
S
1768°C (3214°F)
R
1768°C (3214°F)
mV
60.00mV
Lower
–50°C (–58°F)
1°C
0°C (32°F)
–50°C (–58°F)
-9.99mV
1kΩ (e.g., IS barrier resistance)
30Ω (lead resistance)
to display temperature (in °C or °F)
Display
Scaling
to display in % or engineering units
to display temperature (in °C or °F) or mV
Display range
-999 to 9999
See table above
See table above
Resolution
0.001 engineering units
1°C/°F or 0.01mV
1°C/°F or 0.1°C/°F
Performance
Accuracy
<1°C for 1°C resolution or
<0.25°C for 0.1°C resolution
CJC tracking error
Less than 0.02% per °C ambient change
Lead length compensation
Better than 0.05% error for equal changes
in lead resistance
Input Connections
Terminal
Signal
Terminal
1
24Vdc (out)
1
2
Current +
2
3
Common −
3
4
Voltage +
4
5
mV Signal
T/C Signal
mV +
mV −
CJC Board
(white dot to
terminal 2)
5
Terminal
Signal
1
Not used
2
A
3
B
4
B sense
5
Not used
6
Not used
Not used
6
6
Not used
Ordering Information
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
UCVAR 12-50Vdc
7940010195
UTCAR 12-50Vdc
7940012190
URTAR 12-50Vdc
7940010250
Note: For other ranges please specify as
UCVAR 1 where 1 = Power Supply Voltage
Page 3
Note: For other ranges please specify as
UTCAR 1 where 1 = Power Supply Voltage
Default Burnout Action is Upscale. For
Downscale please specify on order.
Note: For other ranges please specify as
URTAR 1 where 1 = Power Supply Voltage
Subject to technical alterations without notice • Printed in Australia • 7940015645 • 04/03/2008
Universal, Signal Conditioners with Alarms
%
%
%
\
\
\
UHZAR Frequency
• Connects directly to a wide
range of frequency sources
• Power for active input
devices
CNDAR Conductivity
• Suits any conductivity probe
• Autoranging
• Probe temperature
compensation
• Programmable cell constant
• Linearises probe
characteristic
CLCAR Lineariser
• Generate any input to output
characteristic
• Linearise measurements from
non-linear sensors
• Tailor control signals to suit
non-linear control elements
Technical Data
Inputs
Input Type
Programmable frequency
(includes debouncing for voltfree contacts)
Conductivity cell, conductance and PT100
RTD (probe temperature compensation)
Process current or voltage signals
Standard range limits
Any range inside the limits 0 to 10kHz
(0-10Hz for debounced volt-free contacts)
Any range inside the limits 0 to 20,000μS
using 4 selectable ranges: 0-200μS;
0-1,000μS; 0-5,000μS; or 0-20mS.
Any range inside the limits
-24.00mA to +24.00mA or
-12V to 12V
Minimum recommended span
0.001Hz
20% of selected range
2mA or 1V
Input voltage range
50mV to 250V (ac and dc)
others on request
Sensor supply output
Nominally 12Vdc to 25mA
others on request (see /FPS option)
Nominally 24Vdc to 25mA
others on request (see /FPS option)
Temperature range
0-200°C (for RTD)
Cell Constants
0-01 to 99.99/cm
Excitation voltage
Less than 6V p/p @ 400Hz
Lead length compensation
< 2% of change for equal changes in lead
resistance (up to 30Ω)
Temperature Compensation
Linear or user defi ned up to 5 points
Input impedance
22Ω (Current) or 1mΩ (Voltage)
Display
Scaling
to display in % or engineering units
μS, mS, μS/cm, mS/cm or °C
to display in % or engineering units
Display range
-999 to 9999
-999 to 9999
Resolution
0.001 engineering units
0-200.0μS (0.1μS resolution)
0-1,000μS (1μS resolution)
0-5,000μS (1μS resolution)
0-20.00mS (0.01mS resolution)
0-200.0°C (0.1°C resolution)
0.001 engineering units
Performance
Accuracy
Better than 0.05% of span
±0.5% of full scale display
Linearity
Better than 0.05% of span
±0.5% of span
Repeatability
±0.02% of span
To suit any signal using up to 101 breakpoint linerisation (programmable)
±0.05% of span
Noise immunity
40dB CMRR (1.5kVrms limit)
Input Connections
Terminal
Signal
Terminal
Cell
Terminal
Signal
1
12Vdc (out)
1
Not used
Pt100 RTD
1
24Vdc (out)
2
Pull Up/Down
2
A
2
Current +
3
0V
3
B
3
Input −
4
Low Voltage (<24Vdc) Signal +
4
A
4
Voltage +
5
Signal −
5
B
5
Not used
6
High Voltage (>24Vdc) Signal +
6
B sense
6
Not used
Ordering Information
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
UHZAR 12-50Vdc
7940010184
CNDAR 12-50Vdc
7940010232
CLCAR 12-50Vdc
7940010489
Note: For other ranges please specify as
UHZAR 1 where 1 = Power Supply Voltage
Page 4
Note: For other ranges please specify as
CNDAR 1 where 1 = Power Supply Voltage
Note: For other ranges please specify as
CLCAR 1 where 1 = Power Supply Voltage
Subject to technical alterations without notice • Printed in Australia • 7940015645 • 04/03/2008