LIEBERT® NXL™ 625-1100KVA, SINGLE-MODULE SYSTEM SITE PLANNING DATA Table 1 Site planning data—625-1100kVA UPS Rating kVA kW AC Input/Output Voltage, VAC 625 625 480 625 625 575 625 625 600 800 800 480 1100 1100 480 1100 1100 575 1100 1100 600 See Notes below: Input Isolation Transformer YES NO YES — Rectifier AC Input Current Bypass/Output AC Output Current Maximum Battery Current at End of Discharge, A Maximum Heat Dissipation Full Load, BTU/h (kW) Nom Max Nom 907 952 752 757 795 628 726 762 601 1139 1195 962 2061 177,240 (51.9) 1534 1611 1323 2853 252,540 (74.0) 1313 1379 1104 2860 264,714 (77.6) 1252 1314 1058 2856 254,817 (74.7) 2,3,4,6,7,8,10,11 5,6,8,10,11 — 1,3,6,7,8,10,11 Dimensions WxDxH, in. (mm) Approximate Weight Unpacked, lb. (kg) 140.5x39.4x76.8 (3568x1000x1950) 12,980 (5888) 184.8x47.2x78.7 (4694x1200x2000) 16,120 (7312) 228.3x47.2x78.7 (5800x1200x2000) 21,450 (9730) 9 9 195,742 (57.4) 1639 183,079 (53.7) Notes for Table 1 1. Nominal rectifier AC input current (considered continuous) is based on full 6. rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered non-continuous). Maximum input current is controlled by current limit setting, which is adjustable from 7. 25 to 150% of nominal input current. 2. Bypass AC input and AC output current (considered continuous) is based on full rated output load. Maximum current includes nominal output current and 125% overload current for 10 minutes. 3. Emerson recommends that feeder protection (by others) for the rectifier AC input and the bypass AC input be provided by separate overcurrent protection devices. 4. UPS output load cables must be run in separate conduit from input cables. 5. Power cable from module DC bus to battery should be sized for a total maximum 2.0V line drop (power cable drop plus return cable drop as measured at the module) at maximum discharge current. Grounding conductors must be sized per NEC 250-95. Neutral conductors must be sized for full capacity-per NEC 310-16, Note 10-for systems with 4wire loads and 20% minimum capacity for 3-wire loads. Rectifier AC Input: 3-phase, 3-wire, plus ground Bypass AC Input: 3-phase, 4-wire, plus ground (3-wire plus ground in certain circumstances) AC Output to Load: 3-phase, 3- or 4-wire, plus ground Module DC Input from Battery: 2-wire (positive and negative), plus ground 8. All wiring is to be in accordance with national and local electrical codes. 9. Minimum overhead clearance is 2 ft. (0.6m) above the UPS. 10. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. 11. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors. 1 Maintenance Bypass Panel (Option) 3 MBB 2 MIB 2 AC Output To load UPS Module 3 7 2 Bypass AC input 3 7 BFB 2 1 Rectifier AC input DC Bus CB1 Battery System 5 CB2 Numbers in this illustration refer to notes below the table on page 1 7 MBD The Liebert NXL is compatible with high resistance ground systems. See your local Emerson representative for details. © 2014 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186 SL-25529_REV0_02-14 Web site: www.liebert.com 2 Columbus, OH 43229