Liebert NXL 625-1100 kVA, N+1 (Central Bypass) Multi-Module System Site Planning Data (R02/14) (SL-25530)

LIEBERT® NXL™ 625-1100KVA, N+1 (CENTRAL BYPASS) MULTI-MODULE SYSTEM SITE PLANNING DATA
Table 1
Site planning data—625-1100kVA
UPS Rating
Rectifier AC
Input Current
Output AC
Output Current
Maximum Battery
Current at End
of Discharge, A
Maximum Heat
Dissipation Full
Load, BTU/h (kW)
kVA
kW
AC Input/Output
Voltage, VAC
625
625
480
907
952
752
625
625
575
757
795
628
625
625
600
726
762
601
800
800
480
1139
1195
962
2061
177,240 (51.9)
1100
1100
480
1534
1611
1323
2853
252,540 (74.0)
1100
1100
575
1313
1379
1104
2860
264,714 (77.6)
1100
1100
600
1252
1314
1058
2856
254,817 (74.7)
2,3,4,6,7,8,10,11
5,6,7,8,10,11
—
See Notes below:
Nom
Max
Nom
1,3,6,7,8,10,11
Dimensions
WxDxH, in. (mm)
Approximate Weight
Unpacked, lb. (kg)
125x39.4x76.8
3174x1000x1950
12,380 (5615)
155.9x47.2x78.7
(3959x1200x2000)
15,010 (6808)
197.5x47.2x78.7
(5015x1200x2000)
20,050 (9095)
9,12
9,12
195,742 (57.4)
1639
183,079 (53.7)
183,079 (53.7)
Notes for Table 1
1.
2.
3.
4.
5.
6.
Nominal rectifier AC input current (considered continuous) is based on full
rated output load. Maximum current includes nominal input current and
maximum battery recharge current (considered non-continuous). Maximum
input current is controlled by current limit setting, which is adjustable from
25 to 150% of nominal input current.
Bypass AC input and AC output current (considered continuous) is based on
full rated output load. Maximum current includes nominal output current
and 125% overload current for 10 minutes.
Emerson recommends that feeder protection (by others) for the rectifier AC
input and the bypass AC input be provided by separate overcurrent
protection devices.
UPS output load cables must be run in separate conduit from input cables.
Power cable from module DC bus to battery should be sized for a total
maximum 2.0V line drop (power cable drop plus return cable drop as
measured at the module) at maximum discharge current.
Grounding conductors to be sized per NEC 250-95. Neutral conductors must
be sized for full capacity-per NEC 310-16, Note 10, for systems with 4-wire
loads and 20% minimum capacity for 3-wire loads.
NOTE: A neutral conductor is required from each Multi-Module Unit output to
the System Bypass Switchgear.
7. Rectifier AC Input: 3-phase, 3-wire, plus ground
Bypass AC Input: 3-phase, 4-wire, plus ground (3-wire plus ground in certain
circumstances)
AC Output to Load: 3-phase, 3- or 4-wire, plus ground
Module DC Input from Battery: 2-wire (positive and negative), plus ground
8. All wiring is to be in accordance with National and Local Electrical Codes.
9. Minimum overhead clearance is 2 ft. (0.6m) above the UPS.
10. Top or bottom cable entry through removable access plates. Cut plate to suit
conduit size.
11. Control wiring and power cables must be run in separate conduits. Control
wiring must be stranded tinned conductors.
12. Dimensions and weights do not include the System Paralleling Cabinet.
13. For optimal load sharing performance, the difference in bypass circuit cable
length must be 10% or less from longest to shortest. Cable length should be
measured from common point of input to common point of output. If needed,
contact your Emerson representative to determine if other lengths are be
acceptable.
1
1
7
7
Rectifier
AC
Input
3
3
1
2
7
7
3
System Control
Cabinet
(SCC)
Maintenance
Bypass
2 (optional)
CB1
1
CB1
3
CB1
3
4 6 7
6
UPS Module No. 2
CB2
UPS Module No. 3
CB2
6
4 6 7
UPS Module No. 1
CB2
BFB
6
SBB
Continuous
Duty
Static
Switch
MBB
EO
4 6 7
2
UPS Output
5
MBD
7
5
5
MBD
MBD
7
7
UOB
2
MIB
Numbers in this illustration refer
to notes below the table on page 1
The Liebert NXL is compatible with High Resistance Ground Systems. See your local Emerson representative for details.
© 2014 Liebert Corporation
Technical Support / Service
United States
All rights reserved throughout the world. Specifications subject to change without notice.
1050
Dearborn Drive
800-543-2378
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186
SL-25530_REV0_02-14
Web site: www.liebert.com
2
Columbus, OH 43229