Liebert NXL 500-750 kVA, N+1 (Central Bypass) Multi-Module System Site Planning Data (R02/14) (SL-25518)

LIEBERT® NXL™ 500-750KVA, N+1 (CENTRAL BYPASS) MULTI-MODULE SYSTEM SITE PLANNING DATA
Table 1
Site planning data—500-750kVA
UPS Rating
AC Input/Output Input Isolation
Transformer
Voltage, VAC
kVA
kW
500
450
480
625
562.5
480
YES
Rectifier AC
Input Current
Bypass/Output
AC Current
Maximum Battery
Maximum Heat
Current at End
Dissipation, Full
of Discharge (A) Load, BTU/h (kW)
Nom
Max
Nom
643
804
601
1241
124,805 (36.6)
799
995
752
1530
167,265 (49.0)
975
1219
902
1845
213,587 (62.6)
750
675
480
750
675
575
815
1018
753
1851
215,790 (63.2)
750
675
600
759
949
722
1845
200,173 (58.7)
5,6,7,8,10,11
—
See Notes below:
—
1,3,6,7,8,10,11 2,3,4,6,7,8,10,11
Dimensions
WxDxH, in. (mm)
Approx. Weight
Unpacked, lb. (kg)
111.6x39.4x76.8
(2835x1000x1950)
10,210 (4631)
125x39.4x76.8
(3174x1000x1950)
13,100 (5942)
9,12
9,12
Notes for Table 1
1.
2.
3.
4.
5.
6.
Nominal rectifier AC input current (considered continuous) is based on full
rated output load. Maximum current includes nominal input current and
maximum battery recharge current (considered non-continuous). Maximum
input current is controlled by current limit setting which is adjustable 25 to
125% of nominal input current.
AC output current (considered continuous) is based on full rated output load.
Emerson recommends that feeder protection (by others) for the rectifier AC
input and the bypass AC input be provided by separate overcurrent
protection devices.
UPS output load cables must be run in separate conduit from input cables.
Power cable from module DC bus to battery should be sized for a total
maximum 2.0V line drop (power cable drop plus return cable drop as
measured at the module) at maximum discharge current.
Grounding conductors to be sized per NEC 250-95. Neutral conductors to be
sized for full capacity-per NEC 310-16, Note 10-for systems with 4-wire loads
and 20% minimum capacity for 3-wire loads.
NOTE: A neutral conductor is required from each Multi-Module Unit output
to the System Bypass Switchgear.
7.
Rectifier AC Input: 3-phase, 3-wire, plus ground
Bypass AC Input: 3-phase, 4-wire, plus ground (3-wire plus ground in certain
circumstances)
AC Output to Load: 3-phase, 3- or 4-wire, plus ground
Module DC Input from Battery: 2-wire (positive and negative), plus ground
Module Output to SCC: 3-phase, 4-wire, plus ground
8. All wiring is to be in accordance with National and Local Electrical Codes.
9. Minimum overhead clearance is 2 ft. (0.6m) above the UPS.
10. Top or bottom cable entry through removable access plates. Cut plate to suit
conduit size.
11. Control wiring and power cables must be run in separate conduits. Control
wiring must be stranded tinned conductors.
12. Dimensions and weights do not include the System Control Cabinet required
for Multi-Module Systems.
1
Liebert® NXL™ 500-750kVA, N+1 (Central Bypass) Multi-Module System Site Planning Data
1
7
7
Rectifier
AC
Input
3
3
1
2
7
7
3
System Control
Cabinet
(SCC)
Maintenance
Bypass
2 (optional)
CB1
1
CB1
3
CB1
3
4 6 7
6
UPS Module No. 2
CB2
UPS Module No. 3
CB2
6
4 6 7
UPS Module No. 1
CB2
BFB
6
SBB
Continuous
Duty
Static
Switch
MBB
EO
4 6 7
2
UPS Output
5
MBD
7
5
5
MBD
MBD
7
7
UOB
2
MIB
Numbers in this illustration refer
to notes below the table on page 1
The Liebert NXL is compatible with High Resistance Ground Systems. See your local Emerson representative for details.
© 2009 Liebert Corporation
Technical Support / Service
United States
All rights reserved throughout the world. Specifications subject to change without notice.