LIEBERT® NXL™ 500-750KVA, SINGLE-MODULE SYSTEM SITE PLANNING DATA Table 1 Site planning data—500-750kVA kVA kW AC Input/ Output Voltage VAC 500 450 480 UPS Rating 625 562.5 480 750 675 480 750 675 750 675 Input Isolation Transformer Rectifier AC Input Current Nom Max Bypass/Output AC Output Current Nom 643 804 601 Maximum Battery Current at End of Discharge, A Maximum Heat Dissipation, Full Load, BTU/h (kW) 1241 124,805 (36.6) 799 995 752 1530 167,265 (49.0) 975 1219 902 1845 213,587 (62.6) 575 815 1018 753 1851 215,790 (63.2) 600 759 949 722 1845 200,173 (58.7) 2,3,4,6,7,8,10,11 5,6,8,10,11 — See Notes below: YES — 1,3,6,7,8,10,11 Dimensions WxDxH, in. (mm) Approximate Weight Unpacked lb. (kg) 111.6x39.4x76.8 (2835x1000x1950) 10,310 (4677) 140.5x39.4x76.8 (3568x1000x1950) 13,650 (6192) 9 9 Notes for Table 1 1. Nominal rectifier AC input current (considered continuous) is based on full 6. rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered non-continuous). Maximum input current is controlled by current limit setting, which is adjustable 25 to 7. 125% of nominal input current. Grounding conductors to be sized per NEC 250-95. Neutral conductors to be sized for full capacity-per NEC 310-16, Note 10-for systems with 4-wire loads and 20% minimum capacity for 3-wire loads. Rectifier AC Input: 3-phase, 3-wire, plus ground Bypass AC Input: 3-phase, 4-wire, plus ground (3-wire plus ground in certain circumstances) AC Output to Load: 3-phase, 3- or 4-wire, plus ground Module DC Input from Battery: 2-wire (positive and negative), plus ground 2. Bypass AC input and AC output current (considered continuous) is based on full rated output load. Maximum current includes nominal output current and overload current for 10 minutes. 3. Feeder protection (by others) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices. 8. All wiring is to be in accordance with National and Local Electrical Codes. 4. UPS output load cables must be run in separate conduit from input cables. 9. Minimum overhead clearance is 2 ft. (0.6m) above the UPS. 5. Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (power cable drop plus return cable drop as measured at the module) at maximum discharge current 10. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. 11. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors. 1 Liebert® NXL™ 500-750kVA, Single-Module System Site Planning Data Maintenance Bypass Panel (Option) 3 MBB 2 MIB 2 AC Output To load UPS Module 3 7 2 Bypass AC input 3 7 BFB 2 1 Rectifier AC input DC Bus CB1 Battery System 5 CB2 Numbers in this illustration refer to notes below the table on page 1 7 MBD The Liebert NXL is compatible with high resistance ground systems. See your local Emerson representative for details. © 2009 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186 SL-25517_REV6_09-14 Web site: www.liebert.com 2 Columbus, OH 43229