OPEN FRAME & ENCLOSED NAP A C F I LT E R Features • • • • • High-voltage pulse high attenuation type. Single Phase 250Vac. Selectable leakage current. Quick and easy push down terminal. Din rail installation type (Option). Ordering Information Specifications INPUT Voltage 250Vac/250Vdc, 1 phase Test voltage (Terminal-mounting plate) 2.5kVac (cutoff current = 20mA), 1 minute at room temperature and humidity. Isolation resistance (Terminal-mounting plate) 500Vdc, 100MW minute at room temperature and humidity. OUTPUT Current See table. Leakage current 5mA/10mA max (125/250Vac, 60Hz) Voltage drop 1.0V max NAM (1) CODE CURRENT 04 4A -25°C to 85°C (Refer to derating curve). Operating temperature -40°C to 85°C (Refer to derating curve). Storage temperature -40°C to 85°C Humidity 20% to 95% RH (Non-condensing) Vibration 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1 hour each X, Y and Z axis. Impact 196.1m/s2 (20G), 11ms once each X, Y and Z axis. STANDARDS Safety UL1283, CSA C 22.2 No. 8 (C-UL), DIN EN133200 VDE0565 Teil3-1, ENEC (At only AC input). -000 (3) _ (4) 1. Model name 2. Rated current 3. Line to ground capacitor code 4. Options D: Din rail installation type. ENVIRONMENTAL Safety agency approval Temperature -10 (2) 06 6A 10 10A 16 16A 20 20A 30 30A CODE LEAKAGE CURRENT(INPUT 125/250V 60HZ) LINE TO GROUND CAPACITOR(NOMINAL VALUE) 000 5mA / 10mA max Not Provided 101 12.5mA / 25mA max 100pF 221 25mA / 50mA max 220pF 331 37.5mA / 75mA max 330pF 471 50mA / 100mA max 470pF 681 75.5mA / 150mA max 680pF 102 0.13mA / 0.25mA max 1000pF 222 0.25mA / 0.5mA max 2200pF 332 0.38A / 0.75mA max 3300pF 472 0.5mA / 1.0mA max 4700pF When the line to ground capacitor code is different, the attenuation characteristic is different. Your dependable power partner – www.powerbox.com.au 143