LEM AP100-B10

AC Current transducer AP-B10
IPN = 10 .. 400 A
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
Vd
Features
Analogue Output Signal
VOUT (V)
Type
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
AP 50 B10
AP 100 B10
AP 200 B10
AP 400 B10
Load resistance
Supply voltage
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
Limitation voltage output
≥ 10
kΩ
+24 ±5% V DC
5
kV
18
V
• RMS output
• Split core type
• 5V & 10V switch selectable voltage
output.
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy-Dynamic performance data
X
ε
L
VOE
VOT
TC ε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (-3 dB)
< ±1
% of IPN
< ±0.5 % of IPN
< ±0.5 % of IPN
±1
mV/K
±0.1
%/K
< 500
ms
10 .. 6000
Hz
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
• Panelmeters
Simple connection displays power
consumption.
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Reliable isolation according to EN50178, EN61010
Creepage distance
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
300
V AC
> 5.5
mm
Notes : Installation and maintenance should be done with power supply disconnected.
030708/0
LEM Components
www.lem.com
Dimensions AP(R)-B10
(unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
• General tolerance
±1 mm
• Primary aperture
• Panel mounting
∅ 18.5 mm
2 holes ∅ 4.0 mm
• Distance between holes
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
0-5, 10V S e lec table
GND
RL
OUTPUT
A P /A P R
+2 4 V D C
O u tp u t
C o n n e c to r
3 (-) 2 (out)1 (+)
O u tp u t S w itc h
R a n g e S w itc h
F ront
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.