LEM AK200C420L

AC Current transducer AK-C420L
IPN = 2 .. 200 A
Transducer for the electronic measurement AC sinusoidal waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Jumper selectable ranges
and 4-20mA current output.
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
Features
Analogue Output Signal1)
IOUT (mA)
2, 5
10, 20, 50
100, 150, 200
4-20
4-20
4-20
Type
AK 5 C420L
AK 50 C420L
AK 200 C420L
Vc
RL
Supply voltage (Loop powered)
Load resistance
24
see power supply diagram
Vb
Vd
Rated voltage (CAT III, PD2)
RMS Isolation voltage test, 50 Hz, 1mn
150
3
f
Frequency bandwith
20-100
RoHS
Date Code
• AC sinusoïdal Measurement
MAY 2006
MAY 2006
planned
• Loop powered transducers
• Panel mounting
• Average responding
• Current output
• Accurate
• Jumper selectable ranges
V DC
V AC
kV AC
Hz
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy - Dynamic performance data
Applications
X
Accuracy @ IPN, TA=25°C
±1
%
tr
Response time @ 90% of IPN
< 300
ms
General data
TA
TS
Ambient operating temperature (0-95% RH)
Ambient storage temperature
-20..+50
-20..+85
°C
°C
m
Mass
Safety
120
IEC 61010-1
g
EMC
EN 61326
Note:
1)
For 4-20mA output model, no saturation output up to 25 mA.
• Automation systems
Analog current reading for remote
monitoring (e.g. motor).
• Data loggers
Self-powered transducer does not
drain data logger batteries.
• Panel meters
Simple connection displays power
consumption.
Options on request
• DIN mounting
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
060512/6
Page 1/2
www.lem.com
Dimensions
AK-C420L
(unit : mm, 1mm = 0.0394 inch)
61.0
49
24.5
55.4
19
3.2
23.5
23.7
88.9
15
4.5
39
78
Remark
Mechanical characteristics
• General tolerance
• Primary aperture
± 1 mm
19 mm
• Panel mounting
Distance between holes
2 holes ∅ 4.5mm
78 mm
Connections
• 2 x UNC8 Cylindric Head
• Temperature of the primary conductor should
not exceed 60°C.
Power Supply diagram
25
20
15
10
5
060512/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/2
www.lem.com