LEM AP400

AC Current transducer AP-B420L
IPN = 10 .. 400 A
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 4-20mA current output.
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
Vd
Features
Analogue Output Signal
IOUT (mA)
4-20
4-20
4-20
4-20
Load resistance
Supply voltage (loop powered)
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
Limitation of output current
Type
• RMS output
• Split core type
AP 50 B420L
AP 100 B420L
AP 200 B420L
AP 400 B420L
< 350
+24
5
< 25
Ω
V DC
kV
mA
• Loop powered 4-20mA current output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy-Dynamic performance data
X
ε
L
IOE
IOT
TC ε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset current, TA = 25°C
Thermal drift of IOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (-3 dB)
< ±1
% of IPN
< ±0.5 % of IPN
4
mA
±1
µA/K
±0.1
%/K
< 500
ms
10 .. 6000
Hz
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
• Panelmeters
Simple connection displays power
consumption.
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Reliable isolation according to EN50178, EN61010
Creepage distance
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
300
V AC
> 5.5
mm
Notes : Installation and maintenance should be done with power supply disconnected.
030708/0
LEM Components
www.lem.com
Dimensions AP(R)-B420L
(unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
• General tolerance
±1 mm
• Primary aperture
• Panel mounting
∅ 18.5 mm
2 holes ∅ 4.0 mm
• Distance between holes
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
Load
24 VDC P ower
4-20mA
Load Resistance vs. Supply Voltage
(C o n troller,
(+)
(+)
(-)
A P /A P R
30
25
20
15
10
5
0
O u tp u t
C o n n e c to r
0
100
200
300
400
Load Resistance
3 n o n e 2 (-) 1 (+)
F ront
M e te r, e tc ,)
Supply Voltage
(-)
R a n g e S w itc h
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.