Current Transducers HTB 50 .. 400-P/SP5
and HTB 50 .. 100-TP/SP5
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 400 A
Electrical data
Primary nominal
r.m.s. current
IPN (A)
Primary current
measuring range
IP (A)
50
100
200
300
400
VC
IC
Vd
R IS
VOUT
ROUT
RL
±150
±300
±500
±600
±600
Type
HTB 50-P/SP5, HTB 50-TP/SP51)
HTB 100-P/SP5, HTB 100-TP/SP51)
HTB 200-P/SP5
HTB 300-P/SP5
HTB 400-P/SP5
Supply voltage (±5 %)2)
Current consumption
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Output internal resistance
Load resistance
+12 .. +15
V
<15
mA
2.5
kV
>500
MΩ
VOE ±1.667
V
100
Ω
≥10
kΩ
X
L
VOE
VOH
VOT
TC ε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
<±1
% of IPN
Linearity (0 .. ± IPN)
<±1
% of IPN
Electrical offset voltage, TA = 25°C
Vc/2±30
mV
Hysteresis offset voltage @ IP = 0;
after an excursion of 3 x IPN
<±0.5 % of IPN
Thermal drift of VOE
HTB 50-(T)P/SP5
<±1.0
mV/K
HTB 100-(T)P..400-P/SP5 <±0.5
mV/K
Thermal drift (% of reading)
<±0.05
%/K
Response time @ 90% of IP
<3
µs
Frequency bandwidth (-3 dB)3)
DC .. 50 kHz
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass (-TP version)
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500V
• Low power consumption
• Primary bus bar option for 50A and
100A version for ease of connection
Special Features
Accuracy - Dynamic performance data
ε
Features
• Single power supply from 12V to 15V
Advantages
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
-25 .. +85
-25 .. +85
<30 (<36)
°C
°C
g
• AC variable speed drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
Notes : EN 50178 approval pending
1)
-TP version is equipped with a primary bus bar.
2)
Operating at +12V ≤ Vc < +15V will reduce measuring range.
3)
Derating is needed to avoid excessive core heating at high frequency.
• Power supplies for welding
applications.
030221/0
LEM Components
www.lem.com
HTB 50 ... 400-P/SP5
Left view
Back view
Positive Current Flow
39
9 +/-1
1.5
19.5
34
d1
6
14 MAX.
3.5
32 1
34-0.635x0.635
24.5
Secondary Pin Identification
5.5
2-P=2.5
10
Bottom View
1 +Vc
2 0V
3 Output
7
11
3
6 +/-1
2-d2
Mounting Pins
3
19
HTB 50 ... 100-TP/SP5
39
14 MAX.
Left view
10
1.5
1.5
3.5
321
34-0.635x0.635
3.5
1.5
17
34
Back view
1.5
Positive Current Flow
2-P=2.5 10.5 3 3
3.25
6-1.5x1.5
3
11
14
2
9
Secondary Pin Identification
1 +Vc
2 0V
3 Output
3
Bottom view
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.