Current Transducer HAIS 50..400-P and HAIS 50..100-TP IPN = 50 .. 400 A For the electronic measurement of currents : DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit). All Data are given with a R L = 10 kΩ Electrical data Primary nominal current rms IPN (A) 50 100 150 200 400 VOUT VREF RL ROUT CL VC IC Primary current, measuring range IPM (A) ± ± ± ± ± 150 300 450 600 600 Type RoHS since date code HAIS 50-P, HAIS 50-TP1) HAIS 100-P, HAIS 100-TP1) HAIS 150-P HAIS 200-P HAIS 400-P Output voltage (Analog) @ IP IP = 0 Reference voltage 2) - Output voltage VREF Output impedance VREF Load impedance Load resistance Output internal resistance Capacitive loading Supply voltage (± 5 %) Current consumption @ VC = 5 V 45231, 46272 45231, 46012 46172 45231 planned VREF ± (0.625·IP/IPN) V VREF ± 0.025 V 2.5 ± 0.025 V typ. 200 Ω ≥ 200 kΩ ≥2 kΩ < 10 Ω <1 µF 5 V 22 mA Features • Hall effect measuring principle • Galvanic isolation between primary and secondary circuit • Isolation test voltage 2500V • Low power consumption • Single power supply +5V • Fixed offset & gain • Bus bar version available for 50A and 100A ratings. • Insulated plastic case recognized according to UL94-V0. Advantages • Small size and space saving • Only one design for wide current ratings range • High immunity to external Accuracy - Dynamic performance data X ε L TCVOE TCVREF TCVOUT / VREF TCVOUT VOM t ra tr di/dt Vno BW Accuracy 3) @ IPN , TA = 25°C Linearity error 0 .. 3 x IPN Temperature coefficient of VOE @ IP = 0 Temperature coefficient of VREF Temperature coefficient of VOUT / VREF @ IP = 0 Temperature coefficient of VOUT Magnetic offset voltage @ IP = 0, after an overload of 3 x IPN DC Reaction time @ 10 % of IPN Response time to 90 % of IPN step di/dt accurately followed Output voltage noise (DC ..10 kHz) (DC .. 1 MHz) Frequency bandwidth (-3 dB) 4) ≤± ≤± ≤± ≤± ≤± 1 0.5 0.3 0.01 0.2 % of IPN % of IPN mV/K %/K mV/K ≤ ± 0.05% of reading/K < ± 0.4 <3 <5 > 100 < 15 < 40 DC .. 50 % of IPN µs µs A/µs mVpp mVpp kHz interference. • VREF. IN/OUT Applications • AC variable speed drives • Static converters for DC motor drives • Battery supplied applications • Uninterruptible Power Supplies (UPS) • Switched Mode Power Supplies (SMPS) • Power supplies for welding applications. Application Domain Notes : 1) -TP version is equipped with a primary bus bar. 2) It is possible to overdrive VREF with an external reference voltage between 2 - 2.8 V providing its ability to sink or source approximately 2.5 mA. 3) Excluding offset and hysteresis. 4) Small signal only to avoid excessive heatings of the magnetic core. • Industrial Page 1/3 061018/6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Current Transducer HAIS 50..400-P and HAIS 50..100-TP General data TA TS m Ambient operating temperature Ambient storage temperature Mass (in brackets : TP version) Standards - 40 .. + 85 °C - 40 .. + 85 °C 20 (30) g EN 50178: 1997 Isolation characteristics Vb Vb Vd Ve Vw dCp dCl CTI Rated isolation voltage rms with IEC 61010-1 standards and following conditions - Single insulation - Over voltage category III - Pollution degree 2 - Heterogeneous field Rated isolation voltage rms with EN 50178 standards and following conditions - Reinforced insulation - Over voltage category III - Pollution degree 2 - Heterogeneous field Rms voltage for AC isolation test, 50 Hz, 1 min Partial discharge extinction voltage rms @ 10pC HAIS 50..400-P HAIS 50..100-TP Impulse withstand voltage 1.2/50 µs Creepage distance Clearance distance Comparative tracking index (Group I) 300 V rms 600 V rms 2.5 >1 > 1.4 8 >8 >8 > 600 kV kV kV kV mm mm If insulated cable is used for the primary circuit, the voltage category could be improved with the following table : Cable insulation (primary) Category HAR 03 450V CAT III HAR 05 550V CAT III HAR 07 650V CAT III Safety This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions. Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. Page 2/3 061018/6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Dimensions HAIS 50..400-P and HAIS 50..100-TP (in mm. 1 mm = 0.0394 inch) HAIS 50..100-TP HAIS 50..400-P Front view Front view Right view 33 15 0.5 3.5 3 3 3.5 0.5 16 29 29 8 33 1.5 2-D1.0 2-D1.0 6 4-0.25x0.45 Bottom view 1.5 Bottom view 10 3-P1.8 6 14.5 Terminal Pin Identification 25.9 19.9 5 4 4.3 6 11 1 11 6.5 5 4 6 4.3 14.5 1.5 1.5 11 6.5 14 1 3-P1.8 11 Recommended connection Required Connection Circuitcircuit 1...+5V 2...0V 3...OUTPUT 4...Vref. (IN/OUT) 5...Core Earth (*) 6...NC. 1 2 3 4 47nF 4.7nF 47nF +5V 0V OUTPUT Vref. (IN/OUT) 5 Recommended PCB hole Pin 1-4 : 0.7 ±0.1mm Pin 5-6 : 1.5 ±0.1mm Primary bus bar : 2.3 ±0.1mm General tolerance : ±0.2mm Unit : mm Operation Principle +Vc Vout Vref.(IN/OUT) Ip 0V (*) should be connected to 0V of Power Supply for better dv/dt immunity. Arrow indicates positive current direction. Page 3/3 061018/6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com