FUJI EDSX5-80K

PRESSURE TRANSMITTER
FKG...4
DATA SHEET
The FCX – A2 pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA
signal.
The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ±0.07%
0.07% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional
adjustment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART ® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available.
4. Application flexibility
Various options that render the FCX – A2 suitable for almost any process applications include:
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Span limit [kPa] {bar}
Type
F KG 01
F KG 02
F KG 03
F KG 04
F KG 05
Range limit
[kPa] {bar}
Min.
Max.
Lower limit
Upper limit
1.3
{0.013}
5
{0.05}
30
{0.3}
100
{1}
500
{5}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
–100
{–1}
–100
{–1}
–100
{–1}
–100
{–1}
–100
{–1}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
Overrange
limit
[MPa] {bar}
1
{10}
1.5
{15}
9
{90}
15
{150}
75
{750}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 60°C
– Conversion factors to different units;
1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
1kPa=10mbar=101.9716mmH2O =4.01463inH2O
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
EDSX5-80k
Date
Mar. 7, 2007
FKG...4
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
Authorities
ATEX
Load resistance
1533Ω
1500
Factory
Mutual
1000
600Ω
24V
250
0
10
16.1
10.5V
Power voltage
45V
50
[V]
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = –40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
Flameproof
ATEX
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = – 40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = – 40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp. = +120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = – 40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = – 40°C to +65°C
Note) “Seal Not Required” enclosure is allowed.
2
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
CSA
Hazardous locations:
Authorities
13th digit
Y,G,N,R
Y,G,N,R
Y,G,N,R
Y,G,N,R
W,A,D
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
Note: For communication with HHC (1) (Model: FXW), min. of 250 Ω
required.
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
Operating
area
500
Ex II 1 GD
EEx ia IIC T5 Tamb = –40°C to +40°C
EEx ia IIC T4 Tamb = –40°C to +80°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
[Ω]
2000
Intrinsic safety
ATEX
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = –40°C to +40°C
EEx nL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
3.2
Normal operating range
Under scale
Probable under range
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
13th digit
Y,G,N,R
Y,G,N,R
Y,G,N,R
Y,G,N,R
W,A,D
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
CSA
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
–
IECEx
Scheme
/SAA
–
20 20.8
21.6 [mA]
Over scale
Burnout
EEx nAL IIC T5 Tamb = –40°C to +40°C
EEx nAL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
3.8 4
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(span adjustment is not available with 9th
digit code “L, P, Q, S”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
Zero can be elevated or suppressed within
the specified range limit of each sensor
model.
Normal/reverse action:
Selectable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit:
Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil fill
transmitter)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified by
each standard.
Process: – 40 to +100°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: –40 to +90°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
EMC Conformity:EN61326
(Note)
(1) HHC: Hand Held Communicator
3
FKG...4
Performance specifications
Physical specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
Max span below 10000kPa model:
For spans greater than 1/10 of URL: ± 0.07% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.02+0.05
% of span
Span
Max span 50000kPa model:
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.05+0.05
% of span
Span
Stability:
± 0.1% of upper range limit (URL) for 3
years.
Temperature effect:
Effects per 28°C change between the limits of –40°C and +85°C
URL
Zero shift: ± (0.075+0.0125 span )%
URL
Total effect: ± (0.095+0.0125 span )%
Overrange effect: Zero shift; 0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Update period: 120 msec *)
Step response: Time constant: 0.2s *)
Dead time: approximately 0.2s *)
(without electrical damping)
(
(
)
)
*) Faster response is available as option
(maximum update rate: 25 times per
second).
Mounting position effect:
Zero shift, less than 0.1kPa {1m bar} for a
10° tilt in any plane.
No effect on span. This error can be corrected by adjusting Zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
4
Electrical connections:
G1 /2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
1-port (standard) or 2-port with each conduit, as spcified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meet DIN 19213
Process-wetted parts material:
Material
code
(7th digit Process cover
in Code
symbols)
V
J
H
M
T
B
L
U
316 stainless
steel(*1)
316 stainless
steel(*1)
Diaphragm
316L stainless
steel
316L stainless
steel
+Au coating
316 stainless Hastelloy-C
steel(*1)
316 stainless
Monel
steel(*1)
316 stainless
Tantalum
steel(*1)
Hastelloy-C
Hastelloy-C
lining
Monel lining
Monel
Tantalum
Tantalum
lining
Wetted
sensor body
Vent/drain
316 stainless
steel
316 stainless
steel
316/316L
stainless steel
316/316L
stainless steel
Hastelloy-C
lining
Monel lining
316/316L
stainless steel
316/316L
stainless steel
316/316L
stainless steel
Hastelloy-C
Tantalum
lining
Hastelloy-C
lining
Monel lining
Tantalum
lining
Monel
Hastelloy-C
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remarks: Sensor O-rings: Viton O-ring and teflon gasket selectable
Availability of above material design depends on ranges.
Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating (standard), or 316 stainless steel (SCS14A
per JIS G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard), or
304 stainless steel (630 stainless steel
for 50MPa unit).
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct
process mounting.
Mass {weight}:
Transmitter approximately 3.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
ACCESSORIES
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig.1.
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extermely corrosive.
Silicone oil (Code:Y,G,N)
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1 /2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
Operating pressure
Operating
area
20
{200}
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Silicone oil (Code:R)
[kPa abs]
{mbar abs}
101
{1010}
EN61326 : 1997
Class A (standard for Industrial Location)
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
4
{40}
2.7
{27}
None-operating
area
–40
–15
60 85 120
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
5
FKG...4
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
6, 7
9
<Connections>
Oval flange
Process
screw
connection
7/16-20UNF
Rc1/4
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
7/16-20UNF
7/16-20UNF
Rc1/4
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
M10 (or M12)(*1)
1/4-18NPT
7/16-20UNF
<Span and materials>
Process cover
Span limit
[kPa]{bar}(*2)
316 stainless steel
1.3…130
316 stainless steel
{0.013…1.3}
5…500
{0.05…5}
316 stainless steel
316 stainless steel
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
30…3000
{0.3…30}
316 stainless steel
316 stainless steel
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
100…10000
{1…100}
316 stainless steel
316 stainless steel
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
500…50000
{5…500}
316 stainless steel
316 stainless steel
316 stainless steel
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
Conduit
connection
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
(×1)
(×1)
(×1)
(×1)
(×1)
(×2)
(×2)
(×2)
(×2)
(×2)
Combination with
12th digit code
"C, E, P, Q" are not
available.
Note 1
Note 1
Note 1
Note 1
F KG
0
9 10 11 12 13
4
A
B
C
D
E
S
T
V
W
X
Diaphragm
Wetted cell body
316L stainless steel
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
316L stainless steel
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
316L stainless steel
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
316L stainless steel
316L stainless steel
+Au coating
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
316L stainless steel
316L stainless steel
+Au coating
316 stainless steel
316 stainless stee
1V
1J
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless stee
1H
1M
1T
1B
1L
1U
2V
2J
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless stee
2H
2M
2T
2B
2L
2U
3V
3J
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
3H
3M
3T
3B
3L
3U
4V
4J
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
4H
4M
4T
4B
4L
4U
5V
5J
Note 2
<Indicator and arrester>
Indicator
None
Analog, 0 to 100% linear scale
Analog, custom scale
None
Analog, 0 to 100% linear scale
Analog, custom scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Digital, custom scale
(Local adjustment unit with LCD display)
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Digital, custom scale
(Local adjustment unit with LCD display)
Note 1 : (*1)
Note 2 : (*2)
6
Note
Description
Arrester
None
None Z/S board
None attached.
Yes
Yes
Yes
None
None
Yes
Yes
A
B
D
E
F
H
L
P
Q
S
1
None
2
None
4
Yes
5
Yes
For 50MPa {500bar} units, M12 is provided rather than M10.
100: 1 turn down is possible, but should be used at the span greater than
1/40 of the maximum span for better performance.
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
10
11
12
13
14
15
21
Description
Note
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code "A", "S")
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code "A", "S")
FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
CSA, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and Nonincendive
CSA, Intrinsic safety and Nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Standard
None
Specify "A", or "C" for the 7th
Standard
Yes, stainless steel digit code "B", "L", or "U"
Side
None
Side
Yes, stainless steel
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Note3
(*3)
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "J" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T" ,"B", "U")
NACE specification
Silicone oil (Not available for 6th digit code "5", 7th
digit code "T", "U", 15th digit code "A", "B")
Vacuum service
Silicone oil for vacuum use
<Sensor O-ring / Gasket>
Viton (O-ring)
Teflon (gasket)
<Bolt/nut>
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
Not available for 6th digit
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
code "5"
304 stainless steel bolt/304 stainless steel nut
630 stainless steel bolt/304 stainless steel nut Available for 6th digit code "5"
<Other options> (*4)
Note4
Instruction manual unattached
Note 3 : (*3)
Note 4 : (*4)
F KG
0
9 10 11 12 13
14 15
21
4
Digit No.
of code
A
B
C
D
E
X
R
G
H
J
K
P
T
V
A
C
D
F
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
N
R
A
B
A
B
C
D
E
F
L
Costomer tag number can be engraved on standartd stainless steel
name plate. If extra tag plate is required, select "Yes".
If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
7
FKG...4
ORDERING INFORMATION
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occured in the transmitter.
Hold/Overscale (21.6mA)/Overscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the actual scale (code D,H,P,S on 9th digit).
5. Tag No.(up to 26 alphanumerical characters), if required.
8
OUTLINE DIAGRAM (Unit:mm)
< 7th digit code : V, J, H, M, T, J >
Vent/drain plug
(When the vent/drain plug
attatched on the upper side
of the detector) Note2)
In case of 4th digit code “A.B.C.D.E”
In case of 4th digit code “S.V.W.X”
In case of 4th digit code “T”
“A” Press. conn.
Fastener
(Flameproof only)
φ80
105
105
52.5
Down
41
70
φ80
Up
130
120
43.5
8
94.5
MTG. Pipe JIS 50A
(2B)
10
Zero ADJ. screw
88
38
U - bolt M8
58
37
Note1)
210 (189)
4 holes
9 dia.
Note3)
Cable gland (option)
(27)
“B” Conduit conn.
Vent / drain plug
“C” Conduit conn.
With field ind. (option)
154
Earth terminal
Detail “A”
(Press. conn.)
φ18.5
Detail “B”
(Conduit conn.)
H
φ15
59
43
Detail “C”
φ13
231 (210)
41.3
E
17
8
F
Oval flange
screw
See Table 1
φ7
G 1/2
D
Note3)
2.5
Electronics
unit
Side vent
(option)
See Table 1
See Table 1
Sensor
unit
4-M8×12
4th digit of the
code symbols
Press. conn.
Conduit conn.
D
A, S
G1/2
E
17
F
8
H
Rc1/4
B, T
1/2-14NPT 16
5
1/4-18NPT
C, V
Pg13.5
8
4.5
1/4-18NPT
D, W
M20×1.5
16
5
1/4-18NPT
E, X
Pg13.5
8
4.5
1/4-18NPT
Oval flange screw
7/16-20UNF
Screw depth 15
7/16-20UNF
Screw depth 15
M10
Screw depth 15
M10
Screw depth 15
7/16-20UNF
Screw depth 15
Table 1
Note1) Cable gland is supplied in case of flamproof packing type.
φ11 cable is suitable.
Note2) The pressure connector is located on the down side surface of
the detector, when the vent / drainplug is attatched on the upper
side of the detector.
(When the 21st digit of the code symbols : C, E or D).
CONNECTION
DIAGRAM
+
–
CK+ CK–
+
27
70
54
104
–
Note3) In case of 6th digit code “5”
9
FKG...4
< 7th digit code : B, L, U >
In case of 4th digit code “A.B.C.D.E”
U - bolt M8
Fastener
(Flameproof only)
94.5
105
52.5
70
φ80
105
Up
φ80
Zero ADJ. screw
104
43.5
41.3
10
In case of 4th digit code “T”
8
MTG. Pipe
JIS 50A (2B)
In case of 4th digit code “S.V.W.X”
41
Down
88
38
58
40
Cable gland (option)
4 holes 9 dia.
(27)
213
Note)
“C” Conduit conn.
“D” Conduit conn.
With field ind.
Detail “A”
(Press. conn.)
Detail “C”
4th digit code “A,S”
φ16
Earth
terminal
φ13
60
43
Electronics
unit
17
H
0
2 -0.1
1
φ12
+0.2
+0.1
155
Detail “D”
(Conduit conn.)
φ15
F
φ4
E
G 1/2
Detail “B”
4th digit code
“B, C, D, E, T,V,W,X”
View from P
Vent / drain plug
φ16
234
See Table 1
L.P.
P
1/4-18NPT
H.P.
10
4-M8×12
“A” or “B”
Press. conn.
φ4
4th digit of the
code symbols
Conduit conn.
E
F
H
A, S
G1/2
17
8
B, T
1/2-14NPT 16
5
C, V
Pg13.5
8
4.5
D, W
M20×1.5
16
5
E, X
Pg13.5
8
4.5
54
70
120
Oval flange screw
7/16-20UNF
Screw depth 15
7/16-20UNF
Screw depth 15
M10
Screw depth 15
M10
Screw depth 15
7/16-20UNF
Screw depth 15
Table 1
Note 1) Cable gland is supplied in case of flamproof packing type.
φ11 cable is suitable.
10
98
41.3
Oval flange
screw
See Table1
CONNECTION
DIAGRAM
+
–
CK+ CK–
+ –
Sensor
unit
11
FKG...4
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,