FCX – AX SERIES LEVEL TRANSMITTER FHE, FKE...3 DATA SHEET The FCX–AX level transmitter accurately measures liquid level and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FEATURES 1. High accuracy 0.2% accuracy for all calibrated spans is a standard feature for all models covering 3.2kPa{32mbar} range to 500kPa{5bar} high differential pressure range. 0.1% accuracy is available as option. Fuji's micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The "Advanced Floating Cell" design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Replaceable Communication Module Fuji micro-electronics manufacturing technology offers replaceable communication module that makes FCX –AX transmitter very unique in design. In case of change in communication protocol, all that needs to be done is just to replace the module and the transmitter gets upgraded to the new version. 4. Fuji/HART bilingual communication module The communication module is "bilingual" to speak both Fuji proprietary protocol and HART. Any HART compatible devices can communicate with FCX–AX series transmitters. 5. Application flexibility Various options that render the FCX – AX suitable for almost any process applications include: — Analog indicator at either the electronics side or terminal side — Full range of hazardous area approvals — Built-in RFI filter and lightning arrester 1 — 4 2 digits LCD meter — Stainless steel electronics housing — Wide selection of materials — High temperature, high vacuum service. 6. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) (Available for amplifier unit from version 24 and FXW(HHC) version 5.3.) 7. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW hand Held Communicator (HHC) to comply with NAMUR NE43. (Available for amplifier unit from version 24 and FXW (HHC) version 5.3.) 8. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Type: Model FHE: 4 to 20mA Model FKE: 4 to 20mA with digital signal Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type F E Static pressure 3 F E 5 F E 6 Up to flange rating Span limit [kPa] {m bar} Min. Max. FHE FKE FHE/FKE 3.2 {32} 13 {130} 50 {500} 0.32 {3.2} 1.3 {13} 5 {50} 32 {320} 130 {1300} 500 {5000} Range limit [kPa] {m bar} +/– 32 { +/– 320} +/– 130 { +/– 1300} +/– 500 { +/– 5000} Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. — Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig . 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60 °C. — The maximum span of each sensor can be converted to different units using factors as below. 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O EDSX7-57 Date Mar. 15, 1999 FHE, FKE...3 Overrange limit: To maximum static pressure limit Output signal: Model FHE: 4 to 20mA DC 2-wire, linear signal Model FKE: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below [Ω] Load resistance 2000 1533Ω 1500 1000 600Ω Operating area 500 24V 250 Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. Model FHE: Unless otherwise specified in the order, the transmitter will be shipped in “Output Hold” mode. (Output signal just before failure happens is maintained.) Model FKE: Selectable from HHC “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Approx. 21.6mA (Adjustable within the range 20.8mA to 21.6mA from HHC) “Output Underscale”: Approx. 3.8mA (Adjustable within the range 3.2mA to 3.8mA from HHC) 45V 3.2 10 16.1 10.5V Power voltage 50 Note: For communication with HHC (Model: FXW), min. of 250Ω required. Hazardous locations: (Approval pending) Authorities Flameproof Intrinsic safety BASEEFA Factory Mutual Ex ds IIC T5, T6 Class I II III Div. 1 Groups B thru. G Class I II III Div. 1 Groups C thru. G Ex ds IIB+H2 T4 Ex d II C T5, T6 IP 66/67 EEx ia IIC T4, T5 Class I II III Div. 1 Groups A thru. F Class I II III Div. 1 Groups A thru. G — Ex ia II C T5, T6 IP 66/67 CSA RIIS SAA Type N Nonincendive Ex N II T5 Class I II III Div. 2 Groups A thru. G Class I II III Div. 2 Groups A thru. G — Ex n II C T5, T6 IP 66/67 Zero/span adjustment: Model FHE: Zero is adjustable externally from the adjustment screw (UP and DOWN). The adjustment screw can also function to adjust span when MODE SWITCH (located on the electronics unit) is in the span mode. INHIBIT mode to disable the adjustment screw is also available. Model FKE: Zero and span are adjustable from the HHC. Zero is also adjustable externally from the adjustment screw. Damping: Adjustable electrical damping. Model FHE: The time constant is adjustable to 0, 0.3, 1.2, 4.8, or 19.2 seconds. Model FKE: The time constant is adjustable between 0 to 38.4 seconds. Zero elevation/suppression: – 100% to + 100% of URL Normal/reverse action: Model FHE: Selectable by moving a jumper pin located on the electronics unit. Model FKE: Selectable from HHC Indication: Analog indicator or 4 12 -digit LCD meter, as specified. 2 3.8 4 20 20.8 [V] Over scale Burnout 0 Normal operating range Under scale Probable under range Burnout 21.6 Probable over range Loop-check output: Model FHE: Transmitter can output constant signal of 4mA, 12mA, or 20mA if MODE SWITCH is set to the loop check mode. Model FKE: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC. Temperature limit: Ambient: – 40 to + 85°C (– 20 to + 80°C for LCD indicator) (– 40 to + 60°C for arrester option) (– 10 to + 60°C for fluorinated oil fill transmitter) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: Fill fluid Code in the 13th digit of "Code symbols" Process temperature Fluorinated oil W, A and D –20 to 120°C Silicone oil H – 15 to 250°C J Lower limit of static press Atmospheric pressure 85 to 300°C Y and G – 40 to 120°C S –15 to 250°C T 85 to 300°C 2.7kPa abs {20.3mmHg abs} 0.13kPa abs {0.98mmHg abs} Low pressure side contact liquid temperature on transmitter of Code H, J, S, T is 120°C or lower. Low pressure side contact liquid temperature of Code K is 85°C or lower K Storage: – 40 to + 90°C –15 to 150°C Humidity limit: 0 to 100% RH Communication: (Model FKE only) With HHC (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Items Display Set Tag No. v v Model No. v v Serial No. v — Engineering unit v v Range limit v — Measuring range v v Damping v v Output mode v v Burnout direction v v Adjustment v v Output adjust — v Data v — Self diagnoses v — Printer — — External switch lock v v v v Transmitter display (*) Linearise (**) v v Rerange (**) v v (*) HHC's version must be more than 5.0 (or FXW 1 – 2), to use this function. (**) HHC's version must be more than 5.3, and Amplifier unit version 24. Programmable output linearization function: In smart version, output signal can be characterized with “14 points linear approximation function” from HHC. Performance specifications Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL (Model FKE only): 0.1 x URL ± 0.1 + 0.1 % of span Span (Option) For span greater than 1/10 of URL: 0.1% of span For span below 1/10 of URL (Model FKE only): 0.1 x URL ± 0.05 + 0.05 % of span Span ( ( Linearity: Stability: ) Temperature effect: Effects per 28°C change between the limits of – 40°C and + 85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) Zero shift: ± 0.25% of URL Total effect: ± 0.275% of URL Static pressure effect: Zero shift: ± 0.2% of URL for flange rating pressure Span shift: – 0.2% of calibrated span for flange rating pressure Double the zero shift for material code (7th digit in "Code symbols") "H", "M", "T", "B", "L", "U", "P" and "R". Overrange effect:Zero shift; ± 0.3% of URL for flange rating pressure Double the effects for material code "H", "M", "T", "B", "L", "U", "P" and "R". Supply voltage effect: Less than 0.05% of calibrated span per 10V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Range code Time constant "3" 0.55 s "5" and "6" 0.3 s Dead time approx. 0.3 s Step response: (without electrical damping) Mounting position effect: Zero shift, less than 0.3kPa{3m bar} for a 10° tilt in any plane. (No extension) No effect on span. This error can be corrected by adjusting zero. (Double the effect for fluorinated fill sensors) Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec Internal resistance for external field indicator: 12Ω or less ) 0.1% of calibrated span ± 0.2% of upper range limit (URL) for 24 months 3 FHE, FKE...3 Optional features Physical specifications Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: LP side: 1/4-18 NPT or Rc1/4. HP side: ANSI, DIN, or JIS raised face flange. See OUTLINE DIAGRAM for detailed dimensions. Refer to "Code symbols" Process-wetted parts material: Indicator: LP side HP side Material code Diaphragm & Process Wetted (7th figure Diaphragm sensor body flange face cover in "Code symbols") 316 stainless 316L stainless 316 stainless 316L stainless V steel (*2) steel steel steel 316 stainless Hastelloy-C Hastelloy-C Hastelloy-C H lining steel (*2) Monel lining 316 stainless M Monel Monel 2 steel (* ) Tantalum 316 stainless T Tantalum Tantalum lining steel (*2) Hastelloy-C Hastelloy-C Hastelloy-C B Hastelloy-C lining lining Monel lining Monel lining L Monel Monel Tantalum Tantalum U Tantalum Tantalum lining lining Titanium 316 stainless P Titanium Titanium 2 steel (* ) Zirconium 316 stainless R Zirconium Zirconium steel (*2) *(1) Sensor O-rings: Viton or teflon selectable (2) SCS14 Per JIS G5121 Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See below figure. 4KV (1.2 × 50µs) Silicone (Code Y,G) [kPa abs] {mbar abs} Silicone (Code S) Silicone (Code T) Operating pressure 101 {1010} 53.3 {533} Operating arear 13.3 {133} 2.7 {27} –40 –15 Fig. 1 60 85 120 Process temperature[°C ] 200 230 250 Relation between process temperature and operating pressure [kPa abs] {mbar abs} Sealing liquid:Silicone (Code K) 101 {1010} Operating pressure Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy (standard), finished with polyester coating, or 316 stainless steel (SCS14 per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard) or 304 stainless steel Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting flange: Carbon steel or 304 stainless steel, as specified Environmental protection: IEC IP67 and NEMA 4X Flange mounting:See drawings Mass{weight}: Transmitter approximately 13kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.0kg per 50mm extension of diaphragm A plug-in analog indicator (1.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. 1 An optional 4 2 digits LCD meter is also available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: Operating arear Non-operating area 0.13 {1.3} –15 100 Process temperature[°C ] Fig. 2 4 Relation between process temperature and operating pressure 300 Customer tag: Coating of cell: A stainless steel tag with customer tag data is wired to the transmitter. Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TN510412. The applicable standards used to demonstrate compliance are :EMI (Emission) EN50081-1 : 1992 Test item Frequency range Basic standard Applicable Electromagnetic Radiation Disturbance 30-1000MHz EN55022 Class B EMS (Immunity) ACCESSORIES Oval flanges: (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Hand held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Communication module: (Standard for model FKE) By adding communication module, remote setting function becomes available for model FHE. Remark: When the communication module is connected, the operation mode of external zero/span adjustament screw is limited to zero adjustment only. EN50082-1 : 1992 No. Test item Test specification 1 Electrostatic discharge 8kV (Air) 2 Radio-frequency 27-500MHz IEC 801-3:1984 electromagnetic 3V/m field. (Unmodulated) 3 Fast transients common mode 0.5kV, 5/50 (Tr/Th) ns 5kHz Rep. Basic Performance standard criteria IEC 801-2:1984 B IEC 801-4:1988 A B "LVD - The transmitter is not covered by the requirements of the LVD standard." 5 FHE, FKE...3 CODE SYMBOLS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description 3 Type 4 to 20mA, Output type 4 to 20mA with digital signal, Output type FHE FKE Connections Process connection Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT S T V W X Oval flange screw 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF Conduit connection G 1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5 Mounting flange Material Size and rating 304 stainless JIS 10K 80A steel JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 Carbon steel JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 0 1 2 3 4 5 6 7 8 9 A B C D E F G H J K Span limit (*1) [kPa] {m bar} FHE/FKE 3.2/0.32…32/32 {32 /3.2…320/320} 13/1.3…130/130 {130/13…1300/1300} 50/5…500/500 {500/50…5000/5000} 3 5 6 Material LP side (*2) V H M T B L U P (*3) R Process cover Diaphragm Wetted sensor body HP side Diaphragm and flange face 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316L stainless steel Hastelloy-C 316 stainless steel Hastelloy-C lining 316L stainless steel Hastelloy-C Monel Monel lining Monel Tantalum Tantalum lining Tantalum Hastelloy-C Monel Tantalum Titanium Hastelloy-C lining Monel lining Tantalum lining Titanium Hastelloy-C Monel Tantalum Titanium Zirconium Zirconium Zirconium Notes: * (1) 100; 1 turn down is possible for model FKE, but should be used at a span greater than 1/40 of the maximum span for better performance. (2) In case of 6th digit code "6", LP side diaphrgm is Hastelloy-C. (3) Material Code R; 6th digit code "6" is not available. 6 1 2 3 4 5 6 7 8 FHE 3 F KE 3 9 10 11 12 13 14 15 Description Indicator and arrester Indicator None Analog, 0 to 100% linear scale Analog, custom scale Analog, double scale None Analog, 0 to 100% linear scale Analog, custom scale Analog, double scale Digital, 0 to 100% Digital, custom scale Digital, 0 to 100% Digital, custom scale A B D J E F H K L P Q S Arrester None None None None Yes Yes Yes Yes None None (Model FKE only) Yes Yes (Model FKE only) Approvals for hazardous locations (Approval pending) None (for ordinary locations) JIS, Flameproof (Conduit seal) (Available for 4th digit code “S“) JIS, Flameproof (Cable gland seal) (Available for 4th digit code “S“) FM, Flameproof (or explosionproof) (Available for 4th digit code “T“) CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“) BASEEFA, Flameproof (Conduit seal) BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only) FM, Intrinsic safety and nonincendive CSA, Intrinsic safety and nonincendive CENELEC, Intrinsic safety CENELEC, Intrinsic safety and BASEEFA, Type N SAA Flameproof (Conduit seal)(Available for 4th digit cord (“S,T,W) SAA Intrinsic safety (Available for 4th digit cord (“S,T,W) SAA Type–N (non-sparking)(Available for 4th digit cord (“S,T,W) A B C D E M N H J K P R T Q Diaphragm extension [mm] Extension [mm] Applicable material code 0 Any 50 100 (7th digit code "V" only) 150 200 50 100 (7th digit code "H" or "B" only) 150 200 Y A B C D E F G H } } Stainless steel parts Stainless steel tag plate None Yes None Yes None Yes None Yes Y B C E M N P Q Stainless steel elec. housing None None Yes Yes None None Yes Yes Coating of cell None None None None Yes Yes Yes Yes Special applications and fill fluid Treatment Fill fluid None (standard) Silicone oil None (standard) Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V" only) Chlorine service Fluorinated oil (7th digit code "H", "T", "B" and "U") High temp. 250°C High temp. 300°C (*1) High temp. and vacuum (250°C) 7th digit code "V" High temp. and vacuum (300°C) High temp. and high vacuum Silicone oil Y W G A D H J S T K } A B C D } O-ring and Teflon membrane O-ring Teflon membrane Viton None Teflon None Viton Yes (5th digit code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", Teflon Yes and 11th digit code "Y") Bolt/nut Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut 304 stainless steel/304 stainless steel (*2) } A B E Notes: * (1) Treatment; None (2) In case of tropical use, select a stainless bolts and nuts. 7 FHE, FKE...3 OUTLINE DIAGRAM (Unit:mm) DETAIL “B“ (Conduit conn.) Detail “A“ (L.P conn.) φ18.5 In case of 4th digit code “S,V,W,X“ φ15 8 Flange : ANSI/JPI –150LB–3" “A“ L.P. conn. M N 2.5 J Vent/drain plug Note2) (When the vent/drain plug attatched on the upper side of the detector) Up See table 1 See table 1 Down ø13 88 Detail “C“ 50 110 K ø7 17 2 1 “C“ Conduit conn. t Zero/span ADJ. screw L 20 With field ind. (option) Inner of gasket 27 51 Vent/drain plug φF φE φD φH 46.4 φ80 71 ø80 43.5 (27) N Holes h dia φG Fastener (In case of 10th digit code “B,C,M,N“) Cable gland (option) see note G 1/2 “B“ Conduit conn. 41.3 Earth terminal (both side ) see table1 Oval flange screw see table 1 H.P conn. P 3 View form P Vent/drain plug 11th digit code Y φD 0 9.5 to 13 A E 50 B F 100 10.5 to 17.5 C G 150 11 D H 200 11.5 to 18.5 10 2 3 1 355 150 325 to 17 349 144 319 φH to 18 Vent/drain plug (When the vent/drain plug attached on the upper side of the detector) φF φG t N - φh Flange 150 126 100 73 38 8–19 JIS–10K–80A 210 175 151 103 96 38 8–19 JIS–10K–100A S 210 170 126 100 73 48 8–23 JIS–30K–80A 240 195 151 103 96 52 8–25 JIS–30K–100A 185 φE Mass.approx L (mm) (kg) 4th digit code 191 152.5 126 100 73 44 4–20 ANSI/JPI–150LB-3" 229 190.5 151 103 96 44 8–20 ANSI/JPI–150LB-4" 210 168 126 100 73 49 8–23 ANSI/JPI–300LB-3" 254 200 151 103 96 52 8–23 ANSI/JPI–300LB-4" 200 160 126 100 73 44 8–18 220 180 151 103 96 40 8–18 DIN DIN PN40 PN16 DN80 Conduit conn. D E F "A" L.P. conn. Oval flange screw Press. conn. H 17 8 Rc1/4 T G1/2 1/2 –14NPT 16 5 1/4–18NPT V Pg13.5 8 4.5 1/4–18NPT W M20 × 1.5 16 5 1/4–18NPT X Pg13.5 8 4.5 1/4–18NPT 7/16-20UNF Screw depth13 7/16-20UNF Screw depth13 M10 Screw depth13 7M10 Screw depth13 7/16-20UNF Screw depth13 Earth terminal M4 No. 8-32UNC M4 M4 M4 Table 1 DN100 Note1) : Cable gand is supplied in of flamproof packing type. φ11 cable is suitable. Note2) : The pressure connention is loated on the down side surfaace of the detector, when the vent/dranplug is attatched on the upper (when the 21th digit of the code symbols : C,E or D.) CONNECTION DIAGRAM + – CK+ CK– + – S T H E F V K W X 8 W V H 3 M T Detail “B“ (L.P conn.) 4th digit code “T, V ,W, X“ Detail “A“ (L.P conn.) 4th digit code “S“ Flange : ANSI/JPI –150LB–3" 2 -0.1 φ16 1/4-18NPT 110 10 Up 50 107 0 1 φ16 +0.2 φ12 +0.1 In case of 4th digit code “S,V,W,X“ Down Detail “C“ (conduit conn) 88 φ4 Detail “D“ 2 φ13 φ15 N 1 M 17 Cable gland (option) see note “D“ Conduit conn. t G1/2 (27) See table 1 Zero/span ADJ. screw Inner of gasket With field ind. (option) φ80 40.5 51 φ80 43.5 71 φH N Holes h dia Mass.approx L (mm) (kg) 11th digit code Y φD A E 50 B F 100 10 10.5 to 17.5 317 144 319 C G 150 11 D H 200 11.5 to 18.5 φH to 18 φF φG t N - φh Flange 126 100 73 38 8–19 JIS–10K–80A 210 175 151 103 96 38 8–19 JIS–10K–100A 210 170 126 100 73 48 8–23 JIS–30K–80A 3 Conduit conn. D E F “A“ or “B“ L.P. conn. Oval flange screw Press. conn. H 17 8 Rc1/4 T G1/2 1/2 –14NPT 16 5 1/4–18NPT V Pg13.5 8 4.5 1/4–18NPT W M20 × 1.5 16 5 1/4–18NPT X Pg13.5 8 4.5 1/4–18NPT S to 17 41.3 Vent/drain plug 4th digit code 2 3 1 323 150 325 150 185 φE 9.5 to 13 0 H.P conn. Oval flange screw see table 1 Earth terminal (both side ) see table1 “C“ Conduit conn. φG 46.4 Fastener (In case of 10th digit code “B,C,M,N“) L 20 φF φE φD K 7/16-20UNF Screw depth13 7/16-20UNF Screw depth13 M10 Screw depth13 7M10 Screw depth13 7/16-20UNF Screw depth13 Earth terminal M4 No. 8-32UNC M4 M4 M4 Table 1 240 195 151 103 96 52 8–25 JIS–30K–100A 191 152.5 126 100 73 44 4–20 ANSI/JPI–150LB-3" 229 190.5 151 103 96 44 8–20 ANSI/JPI–150LB-4" 210 168 126 100 73 49 8–23 ANSI/JPI–300LB-3" 254 200 151 103 96 52 8–23 ANSI/JPI–300LB-4" 200 160 126 100 73 44 8–18 DIN PN40 DN80 220 180 151 103 96 40 8–18 DIN PN16 DN100 CONNECTION DIAGRAM + – CK+ CK– + – S T H E V F K W X B L 3 U Note) : Cable gland is supplied in case of flameproof packing type. φ11 cable is suitable. 9 FHE, FKE...3 Head office 11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan Phone: 81-3-5435-7111 http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187, 6189 Information in this catalog is subject to change without notice. Printed in Japan